Section 6
Impedance protection
Name
Values (Range)
LEModeZ4
Disabled
Enabled
BlndModeZ4
Disabled
Enabled
LEModeZ5
Disabled
Enabled
BlndModeZ5
Disabled
Enabled
Table 28:
ZQMPDIS (21) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
6.1.6
6.1.6.1
98
Unit
Step
-
-
-
-
-
-
-
-
Unit
Step
-
1
Operation principle
General
Five zone distance protection, quadrilateral and mho characteristic ZQMPDIS (21)
function is designed to operate in the following characteristic modes for separate phase-
to-ground and phase-to-phase loops:
•
Mho characteristic
•
Quadrilateral characteristic
•
Combined Mho and Quadrilateral characteristic
The overall functionality is defined in the logic diagram as shown in figure 30. There is a
pre-calculation block where zero sequence compensated current calculation is done.
These calculated values, along with the phase voltage and current values will be given to
each zone.
Default
Description
Disabled
Enable load enchroachment mode Zone 4
Disabled
Blinder mode Zone 4
Disabled
Enable load enchroachment mode Zone 5
Disabled
Blinder mode Zone 5
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 506 335-UUS A
Technical manual