Function Block - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
14.6.2
14.6.3
14.6.3.1
14.6.4
Technical manual

Function block

The Event recorder has no function block of it's own.
Signals
Input signals
The Event recorder function logs the same binary input signals as the Disturbance report
function.
Operation principle
When one of the trig conditions for the disturbance report is activated, the event recorder
logs every status change in the 96 selected binary signals. The events can be generated by
both internal logical signals and binary input channels. The internal signals are time-
tagged in the main processor module, while the binary input channels are time-tagged
directly in each I/O module. The events are collected during the total recording time (pre-,
post-fault and limit time), and are stored in the disturbance report flash memory at the end
of each recording.
In case of overlapping recordings, due to PostRetrig = Enabled and a new trig signal
appears during post-fault time, events will be saved in both recording files.
The name of the binary input signal that appears in the event recording is the user-defined
name assigned when configuring the IED. The same name is used in the disturbance
recorder function , indications and event recorder function.
The event record is stored as a part of the disturbance report information and managed via
the local HMI or PCM600.
Events can not be read from the IED if more than one user is accessing the
IED simultaneously.
Section 14
Monitoring
647

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents