Section 15
Station communication
15.5.5
Table 387:
GOOSEDPRCV Non group settings (basic)
Name
Operation
15.5.6
15.6
15.6.1
15.6.2
472
Settings
Values (Range)
Unit
Off
-
On
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be crossed in the SMT to
receive the double point values.
The implementation for IEC61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
GOOSE function block to receive an integer value
GOOSEINTRCV
Identification
Function description
GOOSE function block to receive an
integer value
Functionality
GOOSEINTRCV is used to receive an integer value from the sender using
IEC61850 protocol over GOOSE.
Step
Default
-
Off
IEC 61850
identification
GOOSEINTRCV
1MRK 502 034-UEN -
Description
Operation Off/On
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Technical Manual