1MRK 506 335-UUS A
11.2.7
11.3
11.3.1
11.3.2
Technical manual

Technical data

Table 247:
SMBRREC (79) technical data
Function
Number of autoreclosing shots
Autoreclosing open time:
shot 1 - t1 3Ph
shot 2 - t2 3Ph
shot 3 - t3 3Ph
shot 4 - t4 3Ph
shot 5 - t5 3Ph
Autorecloser maximum wait time for sync
Maximum trip pulse duration
Inhibit reset time
Reset time
Minimum time CB must be closed before AR
becomes ready for autoreclosing cycle
CB check time before unsuccessful
Wait for master release
Wait time after close command before proceeding
to next shot
Autorecloser for 1/3-phase operation STBRREC (79)
Identification
Function Description
Autorecloser for 1/3-phase operation
Functionality
The autoreclosing function provides high-speed and/or delayed auto-reclosing for single
breaker applications.
Range or value
1 - 5
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
STBRREC
O->I
SYMBOL-L V1 EN
Section 11
Control
Accuracy
-
± 0.5% ± 25 ms
ANSI/IEEE C37.2
device number
79
375