Function Block - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
14.14.3
14.14.4
Technical manual
with recorded load (pre-fault) currents, is used to exactly calculate the fault position. The
fault can be recalculated with new source data at the actual fault to further increase the
accuracy.
Especially on heavily loaded long lines, where the source voltage angles can be up to
35-40 degrees apart, the accuracy can be still maintained with the advanced compensation
included in fault locator.

Function block

LMBRFLO
PHSEL_A*
CALCMADE
PHSEL_B*
FLTDISTX
PHSEL_C*
BCD_80
CALCDIST*
BCD_40
BCD_20
BCD_10
BCD_8
BCD_4
BCD_2
BCD_1
ANSI09000621-2-en.vsd
ANSI09000621 V2 EN
Figure 305:
LMBRFLO function block
Signals
Table 489:
LMBRFLO Input signals
Name
Type
PHSEL_A
BOOLEAN
PHSEL_B
BOOLEAN
PHSEL_C
BOOLEAN
CALCDIST
BOOLEAN
Table 490:
LMBRFLO Output signals
Name
Type
CALCMADE
BOOLEAN
FLT_X
REAL
BCD_80
BOOLEAN
BCD_40
BOOLEAN
BCD_20
BOOLEAN
BCD_10
BOOLEAN
Table continues on next page
Default
Description
0
Phase selection phase A
0
Phase selection phase B
0
Phase selection phase C
0
Input signal to initiate fault distance calculation
Description
Fault calculation made
Reactive distance to fault
Distance in binary coded data, bit represents 80%
Distance in binary coded data, bit represents 40%
Distance in binary coded data, bit represents 20%
Distance in binary coded data, bit represents 10%
Section 14
Monitoring
663

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents