Settings - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 12
Scheme communication
12.5.5
Table 354:
ECPSCH (85) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
SchemeType
Disabled
Intertrip
Permissive UR
Permissive OR
Blocking
tCoord
0.000 - 60.000
tSendMin
0.000 - 60.000
Table 355:
ECPSCH (85) Group settings (advanced)
Name
Values (Range)
Unblock
Disabled
NoRestart
Restart
tSecurity
0.000 - 60.000
518
Name
Type
CSUR
BOOLEAN
CR
BOOLEAN
CR_GUARD
BOOLEAN
Table 353:
ECPSCH (85) Output signals
Name
Type
TRIP
BOOLEAN
CS
BOOLEAN
CRL
BOOLEAN
LCG
BOOLEAN

Settings

Unit
Step
-
-
-
-
s
0.001
s
0.001
Unit
Step
-
-
s
0.001
Default
Description
0
Signal to be used for channel start with underreaching
pilot schemes
0
Channel receive input signal from communications
apparatus/module for pilot communication scheme logic
0
Carrier channel guard input signal
Description
Trip by pilot communication scheme logic
Pilot channel start signal
Channel receive signal output from communication
scheme logic
Loss of channel guard signal output from
communication scheme logic
Default
Description
Disabled
Disable/Enable Operation
Permissive UR
Scheme type, Mode of Operation
0.035
Communication scheme channel coordination
time
0.100
Minimum duration of a carrier send signal
(carrier continuation)
Default
Description
Disabled
Operation mode of unblocking logic
0.035
Security timer for loss of carrier guard detection
1MRK 506 335-UUS A
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents