ABB REL650 series Technical Manual page 291

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
Technical manual
Chosen current
phasors
Complex
power
Chosen voltage
calculation
phasors
ANSI06000438 V2 EN
Figure 134:
Simplified logic diagram of the power protection function
The function will use voltage and current phasors calculated in the pre-processing blocks.
The apparent complex power is calculated according to chosen formula as shown in
table 175.
Table 175:
Complex power calculation
Mode
Set value:
A, B, C
Arone
PosSeq
AB
BC
Table continues on next page
P
Derivation of
S( angle)
S( composant)
in Char angle
Q
Formula used for complex power calculation
=
×
S
V
I
A
EQUATION2055-ANSI V1 EN
=
S
V
AB
EQUATION2056-ANSI V1 EN
= ×
S
3
V
PosSeq
EQUATION2057-ANSI V1 EN
=
×
S
V
AB
EQUATION2058-ANSI V1 EN
=
×
S
V
BC
EQUATION2059-ANSI V1 EN
Section 7
Current protection
S( angle) <
t
TRIP 1
Power1
0
PICKUP1
S( angle) <
t
TRIP2
Power2
0
PICKUP2
P = POWRE
Q = POWIM
ANSI06000438-2-en.vsd
*
*
*
+
×
+
×
V
I
V
I
A
B
B
C
C
(Equation 61)
*
*
×
-
×
I
V
I
A
BC
C
(Equation 62)
*
×
I
PosSeq
(Equation 63)
*
*
-
(
I
I
)
A
B
(Equation 64)
*
*
-
(
I
I
)
B
C
(Equation 65)
285

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents