Signals - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 7
Current protection
7.13.4
7.13.5
Table 153:
CCRPLD (52PD) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tTrip
0.000 - 60.000
ContactSel
Disabled
PD signal from CB
CurrentSel
Disabled
CB oper monitor
Continuous monitor
CurrUnsymPU
0 - 100
CurrRelPU
0 - 100
Table 154:
CCRPLD (52PD) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
272

Signals

Table 151:
CCRPLD (52PD) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
CLOSECMD
BOOLEAN
OPENCMD
BOOLEAN
EXTPDIND
BOOLEAN
Table 152:
CCRPLD (52PD) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Settings
Unit
Step
-
-
s
0.001
-
-
-
-
%
1
%IB
1
Unit
Step
-
1
Default
Description
-
Three phase group signal for current inputs
0
Block of function
0
Close command to CB
0
Open command to CB
0
Pole discrepancy signal from CB logic
Description
Trip signal to CB
Trip condition TRUE, waiting for time delay
Default
Description
Disabled
Disable/Enable Operation
0.300
Time delay between trip condition and trip
signal
Disabled
Contact function selection
Disabled
Current function selection
80
Unsym magn of lowest phase current
compared to the highest.
10
Current magnitude for release of the function in
% of IBase
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 506 335-UUS A