Dimensions - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
Section 19
19.1
19.2
Technical manual
Technical data

Dimensions

Table 634:
Dimensions of the IED - 3U full 19" rack
Description
Width
Height
Depth
Weight box
Power supply
Table 635:
Power supply
Description
600PSM01
V
n
V
variation
n
Maximum load of
auxiliary voltage supply
Ripple in the DC auxiliary
voltage
Maximum interruption
time in the auxiliary DC
voltage without resetting
the IED
Resolution of the voltage
measurement in PSM
module
Value
17.48 inches (444 mm)
5.20 inches (132 mm), 3U
9.82 inches (249.5 mm)
<22.04 lbs (10 kg)
600PSM02
24, 30 V DC
48, 60, 110, 125 V DC
80...120% of V
(24...30
80...120% of V
n
V DC)
(38.4...150 V DC)
35 W for DC
40 VA for AC
Max 15% of the DC value (at frequency of 100 and 120 Hz)
50 ms at V
n
1 bit represents 0,5 V
1 bit represents 1 V (+/-
(+/- 1 VDC)
1 VDC)
Section 19
Technical data
600PSM03
100, 110, 120, 220, 240
V AC, 50 and 60 Hz
110, 125, 220, 250 V DC
85...110% of V
n
n
(85...264 V AC)
80...120% of V
n
(88...300 V DC)
1 bit represents 2 V (+/-
1 VDC)
801