Ied Status For Iec 60870-5-103 I103Ied - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
14.24
14.24.1
14.24.2
14.24.3
14.24.4
Table 526:
I103IED Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
Technical manual

IED status for IEC 60870-5-103 I103IED

Functionality
I103IED is a function block with defined IED functions in monitor direction. This block
uses parameter as FunctionType, and information number parameter is defined for each
input signal.
Function block
I103IED
BLOCK
19_LEDRS
21_TESTM
22_SETCH
23_GRP1
24_GRP2
25_GRP3
26_GRP4
IEC10000292-2-en.vsd
IEC10000292 V2 EN
Figure 329:
I103IED function block
Signals
Table 525:
I103IED Input signals
Name
Type
BLOCK
BOOLEAN
19_LEDRS
BOOLEAN
21_TESTM
BOOLEAN
22_SETCH
BOOLEAN
23_GRP1
BOOLEAN
24_GRP2
BOOLEAN
25_GRP3
BOOLEAN
26_GRP4
BOOLEAN
Settings
Unit
Step
-
1
Default
Description
0
Block of status reporting
0
Information number 19, reset LEDs
0
Information number 21, test mode is active
0
Information number 22, setting changed
0
Information number 23, setting group 1 is active
0
Information number 24, setting group 2 is active
0
Information number 25, setting group 3 is active
0
Information number 26, setting group 4 is active
Default
Description
1
Function type (1-255)
Section 14
Monitoring
703

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents