Signals - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 12
Scheme communication
12.1.4
496

Signals

Table 331:
ZCPSCH (85) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
BLKCS
BOOLEAN
CS_STOP
BOOLEAN
PLTR_CRD
BOOLEAN
CSOR
BOOLEAN
CSUR
BOOLEAN
CR
BOOLEAN
CR_GUARD
BOOLEAN
CBOPEN
BOOLEAN
Table 332:
ZCPSCH (85) Output signals
Name
Type
TRIP
BOOLEAN
CS
BOOLEAN
CHSTOP
BOOLEAN
CRL
BOOLEAN
LCG
BOOLEAN
Default
Description
-
Current group connection
-
Voltage group connection
0
Block of function
0
Block pilot (communication assisted) trip
0
Block pilot channel start
0
Block of channel start (CS) due to reverse fault detection
0
Signal to be used for coordinating local pilot tripping with
the channel receive (CR) signal
0
Signal to be used for channel start with overreaching
pilot schemes
0
Signal to be used for channel start with underreaching
pilot schemes
0
Channel receive input signal from communications
apparatus/module for pilot communication scheme logic
0
Carrier channel guard input signal
0
Indicates that the breaker is open
Description
Trip by pilot communication scheme logic
Pilot channel start signal
Stops the blocking signal to remote end
Channel receive signal output from communication
scheme logic
Loss of channel guard signal output from
communication scheme logic
1MRK 506 335-UUS A
Technical manual