Settings; Operation Principle; Goose Function Block To Receive An Integer Value Gooseintrcv; Identification - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

Section 14
Station communication
14.5.5
Table 358:
GOOSEDPRCV Non group settings (basic)
Name
Operation
14.5.6
14.6
14.6.1
444
Table 357:
GOOSEDPRCV Output signals
Name
DPOUT
DATAVALID
COMMVALID
TEST

Settings

Values (Range)
Unit
Off
-
On

Operation principle

The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of
a cross to receive the double point values.
The implementation for IEC61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the
DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
GOOSE function block to receive an integer value
GOOSEINTRCV

Identification

Function description
GOOSE function block to receive an
integer value
Type
Description
INTEGER
Double point output
BOOLEAN
Data valid for double point output
BOOLEAN
Communication valid for double point output
BOOLEAN
Test output
Step
Default
-
Off
IEC 61850
identification
GOOSEINTRCV
1MRK 505 288-UEN A
Description
Operation Off/On
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Technical manual