Settings - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
14.18.5
Table 512:
SSCBR Non group settings (basic)
Name
Values (Range)
Operation
Off
On
AccDisLevel
5.00 - 500.00
CurrExp
0.00 - 2.00
RatedFaultCurr
500.00 - 75000.00
RatedOpCurr
100.00 - 5000.00
AccCurrAlmLvl
0.00 - 20000.00
AccCurrLO
0.00 - 20000.00
DirCoef
-3.00 - -0.50
LifeAlmLevel
0 - 99999
OpNumRatCurr
1 - 99999
OpNumFaultCurr
1 - 10000
OpNumAlm
0 - 9999
OpNumLO
0 - 9999
tOpenAlm
0 - 200
tCloseAlm
0 - 200
OpenTimeCorr
0 - 100
CloseTimeCorr
0 - 100
DifTimeCorr
-10 - 10
tSprngChrgAlm
0.00 - 60.00
tPressAlm
0.00 - 60.00
TPressLO
0.00 - 60.00
AccEnerInitVal
0.00 - 9999.99
CountInitVal
0 - 9999
CBRemLife
0 - 9999
InactDayAlm
0 - 9999
InactDayInit
0 - 9999
InactHourAlm
0 - 23
Technical manual

Settings

Unit
Step
-
-
A
0.01
-
0.01
A
0.01
A
0.01
-
0.01
-
0.01
-
0.01
-
1
-
1
-
1
-
1
-
1
ms
1
ms
1
ms
1
ms
1
ms
1
s
0.01
s
0.01
s
0.01
-
0.01
-
1
-
1
Day
1
Day
1
Hour
1
Default
Description
On
Operation Off / On
10.00
RMS current setting below which energy
accumulation stops
2.00
Current exponent setting for energy calculation
5000.00
Rated fault current of the breaker
1000.00
Rated operating current of the breaker
2500.00
Setting of alarm level for accumulated currents
power
2500.00
Lockout limit setting for accumulated currents
power
-1.50
Directional coefficient for CB life calculation
5000
Alarm level for CB remaining life
10000
Number of operations possible at rated current
1000
Number of operations possible at rated fault
current
200
Alarm limit for number of operations
300
Lockout limit for number of operations
40
Alarm level setting for open travel time
40
Alarm level setting for close travel time
10
Correction factor for open travel time
10
Correction factor for CB close travel time
5
Correction factor for time difference in auxiliary
and main contacts open time
1.00
Setting of alarm for spring charging time
0.10
Time delay for gas pressure alarm
0.10
Time delay for gas pressure lockout
0.00
Accumulation energy initial value
0
Operation numbers counter initialization value
5000
Initial value for the CB remaining life estimates
2000
Alarm limit value of the inactive days counter
0
Initial value of the inactive days counter
0
Alarm time of the inactive days counter in hours
Section 14