Technical Data - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 14
Monitoring
14.9.6
14.10
14.10.1
14.10.2
14.10.3
654

Technical data

Table 478:
DRPRDRE technical data
Function
Buffer capacity
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of disturbance reports
Maximum total recording time (3.4 s recording time and maximum number of
channels, typical value)
IEC 61850 generic communication I/O functions
SPGGIO
Identification
Function description
IEC 61850 generic communication I/O
functions
Functionality
IEC61850 generic communication I/O functions SPGGIO is used to send one single
logical signal to other systems or equipment in the substation.
Function block
SPGGIO
BLOCK
^IN
IEC09000237_en_1.vsd
IEC09000237 V1 EN
Figure 302:
SPGGIO function block
IEC 61850
IEC 60617
identification
identification
SPGGIO
-
1MRK 506 335-UUS A
Value
40
96
100
340 seconds (100
recordings) at 50 Hz
280 seconds (80
recordings) at 60 Hz
ANSI/IEEE C37.2
device number
-
Technical manual