Section 11
Control
11.3.5
Table 250:
STBRREC (79) Group settings (basic)
Name
Values (Range)
Operation
Disabled
External ctrl
Enabled
ARMode
3 phase
1/3ph
1 phase
1ph+1*3ph
t1 1Ph
0.000 - 60.000
t1 3Ph
0.000 - 60.000
tReset
0.00 - 6000.00
tSync
0.00 - 6000.00
tTrip
0.000 - 60.000
tCBClosedMin
0.00 - 6000.00
tUnsucCl
0.00 - 6000.00
Priority
None
Low
High
tWaitForMaster
0.00 - 6000.00
Table 251:
STBRREC (79) Group settings (advanced)
Name
Values (Range)
NoOfShots
1
2
3
4
5
StartByCBOpen
Disabled
Enabled
CBAuxContType
NormClosed
NormOpen
CBReadyType
CO
OCO
Table continues on next page
378
Name
Type
COUNT3P4
INTEGER
COUNT3P5
INTEGER
COUNTAR
INTEGER

Settings

Unit
Step
-
-
-
-
s
0.001
s
0.001
s
0.01
s
0.01
s
0.001
s
0.01
s
0.01
-
-
s
0.01
Unit
Step
-
-
-
-
-
-
-
-
Description
Counting the number of three-phase reclosing shot 4
Counting the number of three-phase reclosing shot 5
Counting total number of reclosing shots
Default
Description
External ctrl
Disable/ExternalCtrl/Enable
3 phase
AR mode selection e.g. 3ph, 1/3ph
1.000
Open time for shot 1, single-phase
6.000
Open time for shot 1, delayed reclosing 3ph
60.00
Duration of the reset time
30.00
Maximum wait time for synchronism-check OK
0.200
Maximum trip pulse duration
5.00
Minimum time that CB must be closed before
new sequence allows
30.00
Wait time for CB before indicating
Unsuccessful/Successful
None
Priority selection between adjacent terminals
None/Low/High
60.00
Maximum wait time for release from Master
Default
Description
1
Maximum number of reclosing shots 1-5
Disabled
To be set ON if AR is to be started by CB open
position
NormOpen
Select CB auxilary contact type NC/NO for
CBPOS input
CO
Select type of circuit breaker ready signal
CO/OCO
1MRK 506 335-UUS A