Settings - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 12
Scheme communication
12.4.5
Table 349:
ZCLCPLAL Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
LoadCurr
1 - 100
LossOfLoad
Disabled
Enabled
ZoneExtension
Disabled
Enabled
MinCurr
1 - 100
tLowCurr
0.000 - 60.000
tLoadOn
0.000 - 60.000
tLoadOff
0.000 - 60.000
Table 350:
ZCLCPLAL Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
514
Name
Type
EXACC
BOOLEAN
BC
BOOLEAN
LLACC
BOOLEAN
Table 348:
ZCLCPLAL Output signals
Name
Type
TRZE
BOOLEAN
TRLL
BOOLEAN

Settings

Unit
Step
-
-
%IB
1
-
-
-
-
%IB
1
s
0.001
s
0.001
s
0.001
Unit
Step
-
1
Default
Description
0
Connected to function used for tripping at zone
extension
0
Breaker Close
0
Connected to function used for tripping at loss of load
Description
Trip by zone extension
Trip by loss of load
Default
Description
Disabled
Disable/Enable Operation
10
Load current before disturbance in % of IBase
Disabled
Enable/Disable operation of Loss of load
Disabled
Enable/Disable operation of Zone extension
5
Level taken as current loss due to remote CB
trip in % of IBase
0.200
Time delay on pick-up for MINCURR value
0.000
Time delay on pick-up for load current release
0.300
Time delay on drop off for load current release
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 506 335-UUS A