Settings - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
7.6.5
Table 105:
EF4PTOC Group settings (basic)
Name
Values (Range)
Operation
Off
On
EnaDir
Disable
Enable
AngleRCA
-180 - 180
polMethod
Voltage
Current
Dual
UPolMin
1 - 100
Table continues on next page
Technical manual
Name
Type
I3PDIR
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKST1
BOOLEAN
BLKST2
BOOLEAN
BLKST3
BOOLEAN
BLKST4
BOOLEAN
Table 104:
EF4PTOC Output signals
Name
Type
TRIP
BOOLEAN
TR1
BOOLEAN
TR2
BOOLEAN
TR3
BOOLEAN
TR4
BOOLEAN
START
BOOLEAN
ST1
BOOLEAN
ST2
BOOLEAN
ST3
BOOLEAN
ST4
BOOLEAN
STFW
BOOLEAN
STRV
BOOLEAN
2NDHARMD
BOOLEAN

Settings

Unit
Step
-
-
-
-
Deg
1
-
-
%UB
1
Default
Description
-
Three phase group signal for operating directional
inputs
0
Block of function
0
Block of step 1 (start and trip)
0
Block of step 2 (start and trip)
0
Block of step 3 (start and trip)
0
Block of step 4 (start and trip)
Description
General trip signal
Trip signal from step 1
Trip signal from step 2
Trip signal from step 3
Trip signal from step 4
General start signal
Start signal step 1
Start signal step 2
Start signal step 3
Start signal step 4
Forward directional start signal
Reverse directional start signal
2nd harmonic block signal
Default
Description
Off
Operation Off / On
Enable
Enabling the Directional calculation
65
Relay characteristic angle (RCA)
Voltage
Type of polarization
1
Minimum voltage level for polarization (UN or
U2) in % of UBase
Section 7