Technical Data - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
11.3.7
11.4
11.4.1
Technical manual

Technical data

Table 252:
STBRREC (79) technical data
Function
Number of autoreclosing shots
Autoreclosing open time:
Shot 1 - t1 3Ph
Shot 1 - t1 1Ph
shot 2 - t2 3Ph
shot 3 - t3 3Ph
shot 4 - t4 3Ph
shot 5 - t5 3Ph
Autorecloser maximum wait time
for sync
Open time extension for long trip
time
Maximum trip pulse duration
Inhibit reset time
Reset time
Minimum time CB must be closed
before AR becomes ready for
autoreclosing cycle
CB check time before
unsuccessful
Wait for master release
Wait time after close command
before proceeding to next shot
Apparatus control
Functionality
The apparatus control function APC8 for up to 8 apparatuses is used for control and
supervision of circuit breakers, disconnectors and grounding switches within a bay.
Permission to operate is given after evaluation of conditions from other functions such as
interlocking, synchronism check, operator place selection and external or internal
blockings.
In normal security, the command is processed and the resulting position is not supervised.
However with enhanced security, the command is processed and the resulting position is
supervised.
Range or value
1-5
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
Section 11
Control
Accuracy
-
± 0.5% ± 25 ms
389