ABB REL650 series Technical Manual page 383

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
Technical manual
Name
Type
TRSOTF
BOOLEAN
ZONESTEP
BOOLEAN
TR3P
BOOLEAN
THOLHOLD
BOOLEAN
CBREADY
BOOLEAN
52a
BOOLEAN
PLCLOST
BOOLEAN
SYNC
BOOLEAN
WAIT
BOOLEAN
RSTCOUNT
BOOLEAN
Table 249:
STBRREC (79) Output signals
Name
Type
BLOCKED
BOOLEAN
SETON
BOOLEAN
READY
BOOLEAN
ACTIVE
BOOLEAN
SUCCL
BOOLEAN
UNSUCCL
BOOLEAN
INPROGR
BOOLEAN
1PT1
BOOLEAN
3PT1
BOOLEAN
3PT2
BOOLEAN
3PT3
BOOLEAN
3PT4
BOOLEAN
3PT5
BOOLEAN
PREP3P
BOOLEAN
CLOSECMD
BOOLEAN
WFMASTER
BOOLEAN
COUNT1P
INTEGER
COUNT3P1
INTEGER
COUNT3P2
INTEGER
COUNT3P3
INTEGER
Table continues on next page
Default
Description
0
Makes AR to continue to shots 2-5 at a trip from SOTF
0
Coordination between local AR and down stream
devices
1
Signal to AR that a three-phase tripping occurred
0
Holds AR in wait state
0
CB must be ready for CO/OCO operation to allow start /
close
0
Status of the circuit breaker Closed/Open
0
Power line carrier or other form of permissive signal lost
0
Synchronizing check fulfilled for 3Ph closing attempts
0
Wait for master in Multi-breaker arrangements
0
Resets all counters
Description
Wait for master in Multi-breaker arrangements
AR operation is switched on
Indicates that AR is ready for a new sequence
Reclosing sequence in progress
Activated if CB closes during the time tUnsucCl
Reclosing unsuccessful, signal resets after the reclaim
time
Reclosing shot in progress, activated during open reset
Single-phase reclosing in progress, shot 1
Three-phase reclosing in progress, shot 1
Three-phase reclosing in progress, shot 2
Three-phase reclosing in progress, shot 3
Three-phase reclosing in progress, shot 4
Three-phase reclosing in progress, shot 5
Prepare three-pole trip, control of the next trip operation
Closing command for CB
Signal to Slave issued by Master for sequential
reclosing
Counting the number of single-phase reclosing shots
Counting the number of three-phase reclosing shot 1
Counting the number of three-phase reclosing shot 2
Counting the number of three-phase reclosing shot 3
Section 11
Control