Technical Data - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
13.2.7
13.3
13.3.1
13.3.2
Technical manual
AND
ATRIP
AND
BTRIP
AND
CTRIP
RSTTRIP
ANSI10000269 V2 EN
Figure 258:
Final tripping circuits

Technical data

Table 371:
SPTPTRC (94) technical data
Function
Trip action
Timers
Trip matrix logic TMAGGIO
Identification
Function description
Trip matrix logic
Functionality
The 12 Trip matrix logic TMAGGIO function each with 32 inputs are used to route trip
signals and other logical output signals to the tripping logics SMPPTRC and SPTPTRC
or to different output contacts on the IED.
OR
AND
AND
OR
-loop
Range or value
3-Ph, 1/3-Ph
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
TMAGGIO
-
Section 13
Logic
TR_A
TR_B
TR_C
TRIP
TR3P
AND
TR1P
10 ms
0
ANSI10000269-2-en.vsd
Accuracy
-
± 0.5% ± 10 ms
ANSI/IEEE C37.2
device number
-
537