ABB REL650 series Technical Manual page 298

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 7
Current protection
292
Function
Operate time, directional
Reset time, directional
Critical impulse time
Impulse margin time
Dynamic overreach
Range or value
30 ms typically at 0 to 2 x I
set
20 ms typically at 0 to 10 x I
set
40 ms typically at 2 to 0 x I
set
10 ms typically at 0 to 2 x I
set
2 ms typically at 0 to 10 x I
set
15 ms typically
< 10% at t = 300 ms
1MRK 506 335-UUS A
Accuracy
-
-
-
-
-
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents