Technical Data - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 10
Secondary system supervision
10.2.8
10.3
10.3.1
10.3.2
344
Figure 161:
Simplified logic diagram for fuse failure supervision function, Main logic

Technical data

Table 232:
SDDRFUF technical data
Function
Operate voltage, zero sequence
Operate current, zero sequence
Operate voltage, negative sequence
Operate current, negative sequence
Operate voltage change pickup
Operate current change pickup
Operate phase voltage
Operate phase current
Operate phase dead line voltage
Operate phase dead line current
Breaker close/trip circuit monitoring TCSSCBR
Identification
Function description
Breaker close/trip circuit monitoring
Functionality
The trip circuit supervision function TCSSCBR is designed to supervise the control circuit
of the circuit breaker. The trip circuit supervision generates a current of approximately 1
mA through the supervised control circuit. The validity supervision of a control circuit is
provided for power output contacts T1, T2 and T3.
The function picks up and trips when TCSSCBR detects a trip circuit failure. The trip time
characteristic for the function is of definite time (DT) type. The function trips after a
predefined operating time and resets when the fault disappears.
Range or value
(1-100)% of VBase
(1–100)% of IBase
(1–100)% of VBase
(1–100)% of IBase
(1–100)% of VBase
(1–100)% of IBase
(1-100)% of VBase
(1-100)% of IBase
(1-100)% of VBase
(1-100)% of IBase
IEC 61850
IEC 60617
identification
identification
TCSSCBR
-
1MRK 506 335-UUS A
Accuracy
± 1.0% of V
n
± 1.0% of I
n
± 0.5% of V
n
± 1.0% of I
n
± 5.0% of V
n
± 5.0% of I
n
± 0.5% of V
n
± 1.0% of I
n
± 0.5% of V
n
± 1.0% of I
n
ANSI/IEEE C37.2
device number
-
Technical manual