1MRK 506 335-UUS A
13.2.4
13.2.5
Table 369:
SPTPTRC (94) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Program
3 phase
1p/3p
tTripMin
0.000 - 60.000
Technical manual

Signals

Table 367:
SPTPTRC (94) Input signals
Name
Type
BLOCK
BOOLEAN
TRINP_3P
BOOLEAN
TRINP_A
BOOLEAN
TRINP_B
BOOLEAN
TRINP_C
BOOLEAN
PS_A
BOOLEAN
PS_B
BOOLEAN
PS_C
BOOLEAN
1PTRZ
BOOLEAN
1PTRGF
BOOLEAN
P3PTR
BOOLEAN
SETLKOUT
BOOLEAN
RSTLKOUT
BOOLEAN
Table 368:
SPTPTRC (94) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
TR1P
BOOLEAN
TR3P
BOOLEAN
CLLKOUT
BOOLEAN
Settings
Unit
Step
-
-
-
-
s
0.001
Default
Description
0
Block of function
0
Trip all phases
0
Trip phase A
0
Trip phase B
0
Trip phase C
0
Phase selection input for phase A
0
Phase selection input for phase B
0
Phase selection input for phase C
0
Zone trip with a separate phase selection
0
Single phase DEF trip for separate phase selection
0
Force all trips to be three-phase
0
Set circuit breaker lockout
0
Reset circuit breaker lockout
Description
Common trip signal
Trip signal from phase A
Trip signal from phase B
Trip signal from phase C
Tripping single-pole
Tripping three-pole
Circuit breaker lockout output (set until reset)
Default
Description
Enabled
Disable/Enable Operation
3 phase
Three phase / single or three phase
0.150
Minimum duration of trip output signal
Section 13
Logic
533