ABB REL650 series Technical Manual page 119

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
Technical manual
The condition for operation at phase-to-phase fault is that the angle β between the two
compensated voltages Vcomp1 and Vcomp2 is greater than or equal to 90° (figure 42).
The angle will be 90° for fault location on the boundary of the circle.
The angle β for A-to-B fault can be defined according to equation 16.
V I
Z
AB
β =
Arg
(
)
V
− −
I
Z
v
Re
AB
EQUATION1792-ANSI-650 V1 EN
where
V
is the V
voltage
AB
EQUATION1801 V1 EN
ZRev
is the positive sequence impedance setting for phase-to-phase fault in reverse direction
I
·X
AB
I
·Z
AB
-
I
·ZRev
AB
ANSI09000117 V1 EN
Figure 42:
Simplified offset mho characteristic and voltage vectors for phase A-to-B
fault.
Operation occurs if 90≤β≤270.
Offset mho, forward direction
=
V
Vcomp1
AB
ß
V
Vcomp2=V
I
AB
Section 6
Impedance protection
-
I
·Z
AB
=
I
·Z
=V
F
F
AB
·R
ANSI09000117-1-en.vsd
(Equation 16)
113