Power swing detection ZMRPSB (68)

Identification
Function description
Power swing detection
Functionality
Power swings may occur after disconnection of heavy loads, upon severe fault clearing or
after tripping of big generation plants.
Power swing detection function ZMRPSB (68) is used to detect power swings and initiate
block of all distance protection zones. Occurrence of ground-fault currents during a power
swing inhibits the ZMRPSB (68) function to allow fault clearance.
Function block
ZMRPSB (68)
I3P*
PICKUP
V3P*
ZOUT
BLOCK
ZIN
BLK_SS
BLK_I0
I0CHECK
EXT_PSD
ANSI09000058-1-en.vsd
ANSI09000058 V1 EN
Figure 82:
ZMRPSB (78) function block
Signals
Table 60:
ZMRPSB (68) Input signals
Name
Type
I3P
GROUP
SIGNAL
U3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Table continues on next page
Impedance protection
IEC 61850
IEC 60617
identification
identification
ZMRPSB
Zpsb
SYMBOL-EE V1 EN
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
Section 6
ANSI/IEEE C37.2
device number
68