Function Block - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
14.13.3
14.13.4
14.13.5
14.13.6
Technical manual

Function block

MVEXP
RANGE*
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC09000215-1-en.vsd
IEC09000215 V1 EN
Figure 304:
MVEXP function block
Signals
Table 486:
MVEXP Input signals
Name
Type
RANGE
INTEGER
Table 487:
MVEXP Output signals
Name
Type
HIGHHIGH
BOOLEAN
HIGH
BOOLEAN
NORMAL
BOOLEAN
LOW
BOOLEAN
LOWLOW
BOOLEAN
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
GlobalBaseSel: Selects the global base value group used by the function to define (IBase),
(VBase) and (SBase).
Operation principle
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGGIO). The
function block converts the input integer value to five binary output signals according to
table
488.
Default
Description
0
Measured value range
Description
Measured value is above high-high limit
Measured value is between high and high-high limit
Measured value is between high and low limit
Measured value is between low and low-low limit
Measured value is below low-low limit
Section 14
Monitoring
661