Settings - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 11
Control
11.4.2.5
Table 255:
SCSWI Non group settings (basic)
Name
Values (Range)
CtlModel
Dir Norm
SBO Enh
PosDependent
Always permitted
Not perm at 00/11
tSelect
0.000 - 60.000
tSynchrocheck
0.00 - 600.00
tSynchronizing
0.00 - 600.00
tExecutionFB
0.00 - 600.00
11.4.3
11.4.3.1
392

Settings

Unit
Step
-
-
-
-
s
0.001
s
0.01
s
0.01
s
0.01
Circuit breaker SXCBR
Signals
Table 256:
SXCBR Input signals
Name
Type
BLOCK
BOOLEAN
LR_SWI
BOOLEAN
OPEN
BOOLEAN
CLOSE
BOOLEAN
BL_OPEN
BOOLEAN
BL_CLOSE
BOOLEAN
BL_UPD
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
TR_OPEN
BOOLEAN
TR_CLOSE
BOOLEAN
RS_CNT
BOOLEAN
XIN
BOOLEAN
Default
Description
SBO Enh
Specifies control model type
Always permitted
Permission to operate depending on the
position
30.000
Maximum time between select and execute
signals
10.00
Allowed time for synchronism-check to fulfil
close conditions
0.00
Supervision time to get the signal
synchronizing in progress
30.00
Maximum time from command execution to
termination
Default
Description
0
Block of function
0
Local/Remote switch indication from switchyard
0
Pulsed signal used to immediately open the switch
0
Pulsed signal used to immediately close the switch
0
Signal to block the open command
0
Signal to block the close command
0
Steady signal for block of the position updating
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
0
Signal for open position of truck from I/O
0
Signal for close position of truck from I/O
0
Resets the operation counter
0
Execution information from CSWI
1MRK 506 335-UUS A
Technical manual