Signals - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
12.3.4
12.3.5
Table 344:
ZCWSPSCH (85) Group settings (basic)
Name
Values (Range)
CurrRev
Disabled
Enabled
tPickUpRev
0.000 - 60.000
tDelayRev
0.000 - 60.000
Table continues on next page
Technical manual

Signals

Table 342:
ZCWSPSCH (85) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
IFWD
BOOLEAN
IREV
BOOLEAN
WEIBLK1
BOOLEAN
WEIBLK2
BOOLEAN
BLKZ
BOOLEAN
CBOPEN
BOOLEAN
CRL
BOOLEAN
Table 343:
ZCWSPSCH (85) Output signals
Name
Type
IRVL
BOOLEAN
TRWEI
BOOLEAN
TRWEI_A
BOOLEAN
TRWEI_B
BOOLEAN
TRWEI_C
BOOLEAN
ECHO
BOOLEAN
Settings
Unit
Step
-
-
s
0.001
s
0.001
Scheme communication
Default
Description
-
Three phase group signal for voltage inputs
0
Block of function
0
A signal that indicates a forward fault has been detected
and will block tripping if there was a pre-existing reverse
fault condition (IREV)
0
A signal that indicates a reverse fault has been detected
and activates current reverasl logic
0
Block of WEI logic
0
Block of WEI logic due to operation of other protections
that would effect a pilot trip or the detection of reverse
faults that will be tripped by an external device
0
Block of trip from WEI logic through the loss of voltage
(fuse-failure) function
0
Block of trip from WEI logic by an open breaker
0
POTT or Unblock carrier receive for WEI logic
Description
Operation of current reversal logic
Trip of WEI logic
Trip of WEI logic in phase A
Trip of WEI logic in phase B
Trip of WEI logic in phase C
A signal that indicates channel start (CS) by WEI logic
Default
Description
Disabled
Operating mode of Current Reversal Logic
0.020
Pickup time for current reversal logic
0.060
Time Delay to prevent Carrier send and local
trip
Section 12
509