Monitored Data - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 7
Current protection
Name
Values (Range)
Power2
0.0 - 500.0
Angle2
-180.0 - 180.0
TripDelay2
0.010 - 6000.000
Table 172:
GUPPDUP (37) Group settings (advanced)
Name
Values (Range)
TD
0.00 - 0.99
Table 173:
GUPPDUP (37) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
7.15.3.5
7.15.4
284
Unit
Step
%
0.1
Deg
0.1
s
0.001
Unit
Step
-
0.01
Unit
Step
-
1
-
-

Monitored data

Table 174:
GUPPDUP (37) Monitored data
Name
Type
P
REAL
PPERCENT
REAL
Q
REAL
QPERCENT
REAL
Operation principle
A simplified scheme showing the principle of the power protection function is shown in
figure 134. The function has two stages with individual settings.
Default
Description
1.0
Power setting for stage 2 in % of calculated
power base value
0.0
Characteristic angle for stage 2
1.000
Trip delay for stage 2
Default
Description
0.00
Low pass filter coefficient for power
measurement, V and I
Default
Description
1
Selection of one of the Global Base Value
groups
Pos Seq
Mode of measurement for current and voltage
Values (Range)
Unit
-
MW
-
%
-
MVAr
-
%
1MRK 506 335-UUS A
Description
Active Power
Active power in % of
calculated power base value
Reactive power
Reactive power in % of
calculated power base value
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading