Underfrequency Protection Saptuf (81) - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
Section 9
9.1
9.1.1
9.1.2
9.1.3
Technical manual
Frequency protection

Underfrequency protection SAPTUF (81)

Identification
Function description
Underfrequency protection
Functionality
Underfrequency occurs as a result of a lack of sufficient generation in the network.
Underfrequency protection SAPTUF (81) measures frequency with high accuracy, and is
used for load shedding systems, remedial action schemes, gas turbine startup and so on.
Separate definite time delays are provided for operate and restore.
SAPTUF (81) is provided with undervoltage blocking.
Function block
SAPTUF (81)
V3P*
TRIP
BLOCK
PICKUP
RESTORE
BLKDMAGN
ANSI09000282-1-en.vsd
ANSI09000282 V1 EN
Figure 146:
SAPTUF (81) function block
Frequency protection
IEC 61850
IEC 60617
identification
identification
SAPTUF
f <
SYMBOL-P V1 EN
Section 9
ANSI/IEEE C37.2
device number
81
317