Section 8
Voltage protection
8.4.7
316

Technical data

Table 206:
LOVPTUV (27) technical data
Function
Operate voltage
Reset ratio
Pulse timer
Timers
Range or value
(0–100)% of VBase
<105%
(0.050–60.000) s
(0.000–60.000) s
1MRK 506 335-UUS A
Accuracy
± 0.5% of V
n
-
± 0.5% ± 25 ms
± 0.5% ± 25 ms