1MRK 506 335-UUS A
6.2.5
Table 33:
FDPSPDIS Group settings (basic)
Name
Values (Range)
21 enable
Disabled
Enabled
50/51 enable
Disabled
Enabled
3I0BLK_PP
10 - 100
3I0Enable_PG
10 - 100
RLdFwd
1.00 - 3000.00
RldRev
1.00 - 3000.00
LdAngle
5 - 70
X0
0.50 - 3000.00
Pickup Iph
10 - 2500
Pickup_N
10 - 2500
X1
0.50 - 3000.00
RFltFwdPP
0.50 - 3000.00
RFltRevPP
0.50 - 3000.00
RFltFwdPG
1.00 - 9000.00
RFltRevPG
1.00 - 9000.00
IMinPUPP
5 - 500
IMinPUPG
5 - 500
Table 34:
FDPSPDIS Group settings (advanced)
Name
Values (Range)
TimerPP
Disabled
Enabled
tPP
0.000 - 60.000
TimerPE
Disabled
Enabled
tPG
0.000 - 60.000
Technical manual

Settings

Unit
Step
-
-
-
-
%IPh
1
%IPh
1
ohm/p
0.01
ohm/p
0.01
Deg
1
-
0.01
%IB
1
%IB
1
-
0.01
ohm/l
0.01
ohm/l
0.01
ohm/l
0.01
ohm/l
0.01
%IB
1
%IB
1
Unit
Step
-
-
s
0.001
-
-
s
0.001
Default
Description
Enabled
Operation of impedance based measurement
Disabled
Operation of current based measurement
40
3I0 limit for blocking Phase-to-Phase
measuring loops
20
3I0 limit for releasing Phase-to-Ground
measuring loops
80.00
Forward resistive reach for the load impedance
area
80.00
Reverse resistive reach for the load impedance
area
30
Load angle determining the load impedance
area
120.00
Zero sequence reactance reach
120
Pick up value for phase selection by over-
current element
20
3I0 pickup
40.00
Positive sequence reactance reach
30.00
Fault resistance reach, Phase-Phase, forward
30.00
Fault resistance reach, Phase-Phase, reverse
100.00
Fault resistance reach, Phase-Ground,
forward
100.00
Fault resistance reach, Phase-Ground,
reverse
10
Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
5
Minimum pickup phase current for Phase-to-
ground loops
Default
Description
Disabled
Operation mode Off / On of zone timer, Phase-
Phase
3.000
Time delay to trip, Phase-Phase
Disabled
Operation mode Off / On of zone timer, Phase-
Ground
3.000
Time delay to trip, Ground-Earth
Section 6
Impedance protection
129