Function Block - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 16
Station communication
16.5.3
16.5.4
16.5.5
Table 553:
GOOSEDPRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
16.5.6
726

Function block

GOOSEDPRCV
BLOCK
^DPOUT
DATAVALID
COMMVALID
TEST
IEC10000249-1-en.vsd
IEC10000249 V1 EN
Figure 338:
GOOSEDPRCV function block
Signals
Table 551:
GOOSEDPRCV Input signals
Name
Type
BLOCK
BOOLEAN
Table 552:
GOOSEDPRCV Output signals
Name
Type
DPOUT
INTEGER
DATAVALID
BOOLEAN
COMMVALID
BOOLEAN
TEST
BOOLEAN
Settings
Unit
Step
-
-
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Default
Description
0
Block of function
Description
Double point output
Data valid for double point output
Communication valid for double point output
Test output
Default
Description
Disabled
Operation Enable/Disable
1MRK 506 335-UUS A
Technical manual