Section 11
Control
11.3.3
11.3.4
376
Up to five reclosing attempts can be included by parameter setting. The first attempt can
be single- and/or three phase for single-phase or multi-phase faults respectively.
Multiple autoreclosing functions are provided for multi-breaker arrangements. A priority
circuit allows one circuit breaker to close first and the second will only close if the fault
proved to be transient.
The autoreclosing function is configured to co-operate with the synchrocheck function.

Function block

STBRREC (79)
ON
BLOCKED
OFF
SETON
BLKON
READY
BLKOFF
ACTIVE
RESET
SUCCL
INHIBIT
UNSUCCL
PICKUP
INPROGR
TRSOTF
1PT1
ZONESTEP
3PT1
TR3P
3PT2
THOLHOLD
3PT3
CBREADY
3PT4
52A
3PT5
PLCLOST
PREP3P
SYNC
CLOSECMD
WAIT
WFMASTER
RSTCOUNT
COUNT1P
COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
ANSI10000218-1-en.vsd
ANSI10000218 V1 EN
Figure 177:
STBRREC (79) function block
Signals
Table 248:
STBRREC (79) Input signals
Name
Type
ON
BOOLEAN
OFF
BOOLEAN
BLKON
BOOLEAN
BLKOFF
BOOLEAN
RESET
BOOLEAN
INHIBIT
BOOLEAN
PICKUP
BOOLEAN
Table continues on next page
Default
Description
0
Enables AR when Operation = ExternalCtrl
0
Disables AR when Operation = ExternalCtrl
0
Sets AR in blocked state
0
Releases AR from blocked state
0
Resets AR to initial conditions
0
Interrupts and inhibits reclosing sequence
0
Reclosing sequence starts by a protection trip signal
1MRK 506 335-UUS A