Signals - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 10
Secondary system supervision
10.1.4
10.1.5
Table 223:
CCSRDIF (87) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IMinOp
5 - 200
Table 224:
CCSRDIF (87) Group settings (advanced)
Name
Values (Range)
Pickup_Block
5 - 500
Table 225:
CCSRDIF (87) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
330

Signals

Table 221:
CCSRDIF (87) Input signals
Name
Type
I3P
GROUP
SIGNAL
IREF
GROUP
SIGNAL
BLOCK
BOOLEAN
Table 222:
CCSRDIF (87) Output signals
Name
Type
FAIL
BOOLEAN
ALARM
BOOLEAN
Settings
Unit
Step
-
-
%IB
1
Unit
Step
%IB
1
Unit
Step
-
1
Default
Description
-
Three phase group signal for current inputs
-
Group signal for current reference
0
Block of function
Description
Detection of current circuit failure
Alarm for current circuit failure
Default
Description
Disabled
Disable/Enable Operation
20
Minimum operate current differential pickup in
% of IBase
Default
Description
150
Block of the function at high phase current, in %
of IBase
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 506 335-UUS A
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents