1MRK 506 335-UUS A
13.1.7
Technical manual
routed. It has a single trip output (TRIP) for connection to one or more of the IEDs binary
outputs, as well as to other functions within the IED requiring this signal.
ANSI05000789 V2 EN
Figure 253:
Simplified logic diagram for three pole trip
In multi-breaker arrangements, one SMPPTRC (94) function block is used for each
breaker.
Lockout can be activated either by activating the input (SETLKOUT) or automatically
from the trip input by setting AutoLock to Enabled. A Lockout condition will be indicated
by activation of the output (CLLKOUT). If lockout has been activated it can be reset by
activating the input (RSTLKOUT) or via the HMI.
If TripLockout is set to Enabled an active Lockout will latch the three-phase trip output.
In this way if both AutoLock and TripLockout are set to Enabled the trip will always be
three-phase and sealed in.

Technical data

Table 366:
SMPPTRC (94) technical data
Function
Trip action
Timers
Range or value
3-ph
(0.000-60.000) s
Section 13
Logic
Accuracy
-
± 0.5% ± 10 ms
531