ABB REL650 series Technical Manual page 127

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
Technical manual
apparent impedances at phase-to-phase faults follow equation
to phase B fault).
V
- V
A
B
=
Z
app
I
- I
A
B
EQUATION1545 V1 EN
Here V and I represent the corresponding voltage and current phasors in the respective
phase Ln (n = 1, 2, 3)
The ground return compensation applies in a conventional manner to phase-to-ground
faults (example for a phase A to ground fault) according to equation 24.
V _ A
=
Z
app
+
×
I _ A
I
KN
N
EQUATION1546 V1 EN
Where:
V_A, I_A and IN
are the phase voltage, phase current and residual current present to the IED
KN is defined as:
-
Z0 Z1
=
KN
×
3 Z1
EQUATION-2105 V1 EN
=
+
Z
0
R
0
jX
0
EQUATION2106 V1 EN
=
+
Z
1
R
1
jX
1
EQUATION2107 V1 EN
Where
R0
is the resistive zero sequence reach
X0
is the reactive zero sequence reach
R1
is the resistive positive sequence reach
X1
is the reactive positive sequence reach
Here IN is a phasor of the residual current in IED point. This results in the same reach
along the line for all types of faults.
Section 6
Impedance protection
23
(example for a phase A
(Equation 23)
(Equation 24)
121