Signals - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
7.12.4
7.12.5
Table 147:
STBPTOC (50STB) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IPickup
1 - 2500
Table 148:
STBPTOC (50STB) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
7.12.6
Technical manual

Signals

Table 145:
STBPTOC (50STB) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
ENABLE
BOOLEAN
Table 146:
STBPTOC (50STB) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Settings
Unit
Step
-
-
%IB
1
Unit
Step
-
1
Monitored data
Table 149:
STBPTOC (50STB) Monitored data
Name
Type
I_A
REAL
I_B
REAL
I_C
REAL
Default
Description
-
Three phase group signal for current inputs
0
Block of function
0
Enable stub protection usually with open disconnect
switch (89b)
Description
Common trip signal
General pickup signal
Default
Description
Disabled
Disable/Enable Operation
200
Pickup current level in % of IBase
Default
Description
1
Selection of one of the Global Base Value
groups
Values (Range)
Unit
-
A
-
A
-
A
Section 7
Current protection
Description
Current in phase A
Current in phase B
Current in phase C
269

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents