Time Synchronization Via Irig-B - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 17
Basic IED functions
17.2.7
17.2.7.1
17.2.7.2
Table 579:
IRIG-B Non group settings (basic)
Name
Values (Range)
TimeDomain
LocalTime
UTC
Encoding
IRIG-B
1344
1344TZ
TimeZoneAs1344
MinusTZ
PlusTZ
17.2.8
17.2.8.1
750

Time synchronization via IRIG-B

Identification
Function description
Time synchronization via IRIG-B
Settings
Unit
Step
-
-
-
-
-
-
Operation principle
General concepts
Time definitions
The error of a clock is the difference between the actual time of the clock, and the time the
clock is intended to have. Clock accuracy indicates the increase in error, that is, the time
gained or lost by the clock. A disciplined clock knows its own faults and tries to
compensate for them.
IEC 61850
IEC 60617
identification
identification
IRIG-B
-
Default
Description
LocalTime
Time domain
IRIG-B
Type of encoding
PlusTZ
Time zone as in 1344 standard
1MRK 506 335-UUS A
ANSI/IEEE C37.2
device number
-
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents