Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Setting of the phase reference channel........66 Example................. 66 Setting of current channels............66 Example 1................67 Example 2................67 Example 3................68 Examples on how to connect, configure and set CT inputs for most commonly used CT connections....72 Line distance protection REL670 2.2 IEC Application manual...
Page 8
Short guidance for use of UDP..........107 Protocol reporting via IEEE 1344 and C37.118 PMUREPORT..109 Identification................109 Application................. 109 Operation principle..............112 Frequency reporting............. 113 Reporting filters..............115 Scaling Factors for ANALOGREPORT channels....116 Line distance protection REL670 2.2 IEC Application manual...
Page 9
Impact of series compensation on protective IED of adjacent lines............... 181 Distance protection...............182 Setting guidelines..............189 General.................189 Setting of zone1..............190 Setting of overreaching zone..........190 Setting of reverse zone............191 Line distance protection REL670 2.2 IEC Application manual...
Page 10
Load impedance limitation, without load encroachment function.................230 Load impedance limitation, with Phase selection with load encroachment, quadrilateral characteristic function activated ................232 Setting of minimum operating currents.........232 Directional impedance element for quadrilateral characteristics..............232 Line distance protection REL670 2.2 IEC Application manual...
Page 11
Fault infeed from remote end..........265 Load encroachment..............265 Short line application............266 Long transmission line application........267 Parallel line application with mutual coupling....... 267 Tapped line application............273 Setting guidelines..............276 General.................276 Setting of zone1..............276 Line distance protection REL670 2.2 IEC Application manual...
Page 12
Setting of zone 1..............306 Setting of overreaching zone..........306 Setting of reverse zone............307 Setting of zones for parallel line application......308 Setting of reach in resistive direction........309 Load impedance limitation, without load encroachment function.................310 Line distance protection REL670 2.2 IEC Application manual...
Page 13
Setting of zones for parallel line application......349 Setting the reach with respect to load........351 Zone reach setting lower than minimum load impedance..352 Zone reach setting higher than minimum load impedance...354 Line distance protection REL670 2.2 IEC Application manual...
Page 14
Zone reach setting higher than minimum load impedance...403 Parameter setting guidelines..........404 ZMMMXU settings..............406 Power swing detection ZMRPSB ...........407 Identification................407 Application................. 407 General.................407 Basic characteristics.............408 Setting guidelines..............409 Power swing logic PSLPSCH ............416 Identification................416 Application................. 416 Line distance protection REL670 2.2 IEC Application manual...
Page 15
Directional phase overcurrent protection, four steps OC4PTOC..460 Identification................460 Application................. 460 Setting guidelines..............461 Settings for each step............463 Setting example..............466 Instantaneous residual overcurrent protection EFPIOC ....471 Identification................471 Application................. 471 Setting guidelines..............471 Line distance protection REL670 2.2 IEC Application manual...
Page 17
Power supply quality............538 High impedance earthed systems........538 The following settings can be done for the two step overvoltage protection............538 Two step residual overvoltage protection ROV2PTOV ....541 Identification................541 Application................. 541 Line distance protection REL670 2.2 IEC Application manual...
Page 19
Application................. 588 Setting guidelines..............589 General.................589 Setting of common parameters..........589 Negative sequence based............590 Zero sequence based............591 Delta U and delta I ...............591 Dead line detection...............592 Fuse failure supervision VDSPVC..........592 Identification................592 Line distance protection REL670 2.2 IEC Application manual...
Page 20
ARMode = 1/2ph + 1*3ph, 1-phase, 2-phase or 3-phase reclosing in the first shot............620 ARMode = 1ph + 1*2/3ph, 1-phase, 2-phase or 3-phase reclosing in the first shot............621 External selection of auto reclosing mode......621 Auto reclosing reclaim timer..........622 Line distance protection REL670 2.2 IEC Application manual...
Page 21
Configuration setting............662 Interlocking for bus-coupler bay ABC_BC ........ 663 Application................664 Configuration................ 664 Signals from all feeders............664 Signals from bus-coupler............666 Configuration setting............668 Interlocking for transformer bay AB_TRAFO ......669 Application................669 Signals from bus-coupler............670 Line distance protection REL670 2.2 IEC Application manual...
Page 22
Single point generic control 8 signals SPC8GAPC......694 Identification................695 Application................. 695 Setting guidelines..............695 AutomationBits, command function for DNP3.0 AUTOBITS..695 Identification................696 Application................. 696 Setting guidelines..............696 Single command, 16 signals SINGLECMD........696 Line distance protection REL670 2.2 IEC Application manual...
Page 23
Current reversal logic............714 Weak-end infeed logic............715 Setting guidelines..............716 Current reversal logic............717 Weak-end infeed logic............717 Current reversal and weak-end infeed logic for phase segregated communication ZC1WPSCH ........717 Identification................717 Line distance protection REL670 2.2 IEC Application manual...
Page 28
IEC/UCA 61850-9-2LE communication protocol......813 Introduction................813 Setting guidelines..............816 Specific settings related to the IEC/UCA 61850-9-2LE communication..............817 Loss of communication when used with LDCM....817 Setting examples for IEC/UCA 61850-9-2LE and time synchronization..............822 Line distance protection REL670 2.2 IEC Application manual...
Page 29
Change lock CHNGLCK..............852 Application................. 852 Denial of service SCHLCCH/RCHLCCH ........853 Application................. 853 Setting guidelines..............853 Section 24 Basic IED functions............855 IED identifiers TERMINALID............855 Application................. 855 Product information PRODINF............855 Application................. 855 Line distance protection REL670 2.2 IEC Application manual...
Page 30
Test mode functionality TESTMODE..........868 Application................. 868 IEC 61850 protocol test mode..........868 Setting guidelines..............870 Time synchronization TIMESYNCHGEN........870 Application................. 870 Setting guidelines..............871 System time................871 Synchronization..............872 Process bus IEC/UCA 61850-9-2LE synchronization..874 Section 25 Requirements............... 877 Line distance protection REL670 2.2 IEC Application manual...
Page 31
SNTP server requirements............. 886 PTP requirements................887 Sample specification of communication requirements for the protection and control terminals in digital telecommunication networks..................887 IEC/UCA 61850-9-2LE Merging unit requirements ....... 888 Section 26 Glossary............... 891 Line distance protection REL670 2.2 IEC Application manual...
This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering. The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology, such as protection schemes and communication principles. Line distance protection REL670 2.2 IEC Application manual...
The manual provides procedures for the checking of external circuitry and energizing the IED, parameter setting and configuration as well as verifying settings by secondary injection. The manual Line distance protection REL670 2.2 IEC Application manual...
GUID-2945B229-DAB0-4F15-8A0E-B9CF0C2C7B15 v13 The electrical warning icon indicates the presence of a hazard which could result in electrical shock. The warning icon indicates the presence of a hazard which could result in personal injury. Line distance protection REL670 2.2 IEC Application manual...
For example, to save the changes in non-volatile memory, select Yes and press • Parameter names are shown in italics. For example, the function can be enabled and disabled with the Operation setting. • Each function block symbol shows the available input/output signal. Line distance protection REL670 2.2 IEC Application manual...
With the included remote communication, following the IEEE C37.94 standard, up to 192 channels for intertrip and binary signals are available per LDCM communication module in the communication between the IEDs. Line distance protection REL670 2.2 IEC Application manual...
Page 48
The following tables list all the functions available in the IED. Those functions that are not exposed to the user or do not need to be configured are not described in this manual. Line distance protection REL670 2.2 IEC Application manual...
Directional impedance element for mho characteristic ZDARDIR Additional distance protection directional function for earth faults ZSMGAPC Mho impedance supervision logic FMPSPDIS Faulty phase identification with load enchroachment Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
(1CB), including interlocking (see Table 4) APC15 Control 1-H38 functionality for a single bay, max 15 objects (2CB), including interlocking (see Table 5) QCBAY Bay control Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 53
DNP3.0 SINGLECMD Single command, 16 signals I103CMD Function commands for 60870-5-103 I103GENCMD Function commands generic for 60870-5-103 I103POSCMD commands with position and select for 60870-5-103 Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 54
INDCALH Logic for group indication AND, GATE, INV, Basic 40-420 40-42 40-42 40-42 40-42 LLD, OR, configurable PULSETIMER, logic blocks RSMEMORY, (see Table 3) SRMEMORY, TIMERSET, XOR Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 55
Boolean 16 conversion ITBGAPC Integer to Boolean 16 conversion with Logic Node representation TEIGAPC Elapsed time integrator with limit transgression and overflow supervision INTCOMP Comparator for integer inputs REALCOMP Comparator for real inputs Line distance protection REL670 2.2 IEC Application manual...
Page 56
Switch controller SXSWI Circuit switch QCRSV Apparatus control RESIN1 RESIN2 POS_EVAL Evaluation of position indication XLNPROXY Proxy for signals from switching device via GOOSE GOOSEXLNRCV GOOSE function block to receive a switching device Line distance protection REL670 2.2 IEC Application manual...
Page 57
Table 6: Total number of instances for configurable logic blocks Q/T Configurable logic blocks Q/T Total number of instances ANDQT INDCOMBSPQT INDEXTSPQT INVALIDQT INVERTERQT ORQT PULSETIMERQT RSMEMORYQT SRMEMORYQT TIMERSETQT XORQT Line distance protection REL670 2.2 IEC Application manual...
Page 58
VMMXU Voltage measurement phase-phase CMSQI Current sequence measurement VMSQI Voltage sequence measurement VNMMXU Voltage measurement phase-earth AISVBAS General service value presentation of analog inputs EVENT Event function Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 59
SSIML Insulation supervision for liquid medium SSCBR Circuit breaker condition monitoring LMBRFLO Fault locator I103MEAS Measurands for IEC 60870-5-103 I103MEASUSR Measurands user defined signals for 60870-5-103 Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 60
IEC 60870-5-103 I103USRDEF Status for user defined signals for 60870-5-103 L4UFCNT Event counter with limit supervision TEILGAPC Running hour meter Metering PCFCNT Pulse-counter logic ETPMMTR Function for energy calculation and demand handling Line distance protection REL670 2.2 IEC Application manual...
8 merging units ACTIVLOG Activity logging ALTRK Service tracking IEC 62439-3 Parallel redundancy 1-P23 1-P23 1-P23 1-P23 protocol IEC 62439-3 High-availability 1-P24 1-P24 1-P24 1-P24 seamless redundancy Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 62
Configuration parameters for C37.118 2011 and IEEE1344 protocol PMUREPORT Protocol reporting via IEEE 1344 and C37.118 PHASORREPORT1 Protocol reporting of phasor data via IEEE 1344 and C37.118, phasors 1-8 Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Summation block 3 phase ATHSTAT Authority status ATHCHCK Authority check AUTHMAN Authority management FTPACCS FTP access with password GBASVAL Global base values for settings ALTMS Time master supervision ALTIM Time management COMSTATUS Protocol diagnostic Line distance protection REL670 2.2 IEC Application manual...
Page 64
Parameter setting function for HMI in PCM600 FNKEYMD1– FNKEYMD5 LEDGEN General LED indication part for LHMI OPENCLOSE_LED LHMI LEDs for open and close keys GRP1_LED1– Basic part for CP HW LED indication module GRP1_LED15 GRP2_LED1– GRP2_LED15 GRP3_LED1– GRP3_LED15 Line distance protection REL670 2.2 IEC Application manual...
ZCRW PSCH Optional Functions Control Control Control Control Ud> PMU REP S CILO S CSWI S XSWI VD SPVC Q CRSV IEC16000195-1-en.vsd IEC16000195 V1 EN-US Figure 2: Configuration diagram for configuration A41 Line distance protection REL670 2.2 IEC Application manual...
If a second TRM is used, at least one TRM channel must be configured to get the service values. However, the MU physical channel must be configured to get service values from that channel. Line distance protection REL670 2.2 IEC Application manual...
Set parameter Set parameter CTStarPoint CTStarPoint Correct Setting is Correct Setting is "ToObject" "FromObject" en05000456.vsd IEC05000456 V1 EN-US Figure 6: Internal convention of the directionality in the IED Line distance protection REL670 2.2 IEC Application manual...
Forward. This means that the protection is looking towards the line. 4.2.2.2 Example 2 SEMOD55055-29 v7 Two IEDs used for protection of two objects and sharing a CT. Line distance protection REL670 2.2 IEC Application manual...
CT that is feeding the two IEDs. With these settings, the directional functions of the line protection shall be set to Forward to look towards the line. 4.2.2.3 Example 3 SEMOD55055-35 v7 One IED used to protect two objects. Line distance protection REL670 2.2 IEC Application manual...
Page 75
The CT direction for the current channels to the line protection is set with the line as reference object and the directional functions of the line protection shall be set to Forward to protect the line. Line distance protection REL670 2.2 IEC Application manual...
Page 76
CTStarPoint with Transformer as Transformer as reference object. reference object. Correct setting is Correct setting is "ToObject" "ToObject" IEC05000462 V2 EN-US Figure 10: Example how to set CTStarPoint parameters in the IED Line distance protection REL670 2.2 IEC Application manual...
Page 77
CT inputs marked with 1 in Figure 11, set CTStarPoint = FromObject, and for all CT inputs marked with 2 in Figure 11, set CTStarPoint = ToObject. Regardless which one of the above two options is selected, busbar differential protection will behave correctly. Line distance protection REL670 2.2 IEC Application manual...
CT polarity marking is correct! It shall be noted that depending on national standard and utility practices, the rated secondary current of a CT has typically one of the following values: • • Line distance protection REL670 2.2 IEC Application manual...
IED. It gives an overview of the actions which are needed to make this measurement available to the built-in protection and control functions within the IED as well. For correct terminal designations, see the connection diagrams valid for the delivered IED. Line distance protection REL670 2.2 IEC Application manual...
Page 80
Ratio of the first two parameters is only used inside the IED. The third parameter (CTStarPoint=ToObject) as set in this example causes no change on the measured currents. In other words, currents are already measured towards the protected object. Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 81
GRPL3. If GRP2N is connected, the data reflects the measured value of GRP2N. Another alternative is to have the star point of the three-phase CT set as shown in Figure 14: Line distance protection REL670 2.2 IEC Application manual...
Page 82
IED. A third alternative is to have the residual/neutral current from the three-phase CT set connected to the IED as shown in Figure 14. Line distance protection REL670 2.2 IEC Application manual...
Page 83
6). Depending on the type of functions, which need this current information, more than one preprocessing block might be connected in parallel to these three CT inputs. Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
IED. It gives an overview of the required actions by the user in order to make this measurement available to the built-in protection and control functions in the IED as well. For correct terminal designations, see the connection diagrams valid for the delivered IED. Line distance protection REL670 2.2 IEC Application manual...
Page 85
Section 4 1MRK 506 369-UEN B Analog inputs IL1-IL2 SMAI2 BLOCK AI3P IL2-IL3 REVROT ^GRP2L1 IL3-IL1 ^GRP2L2 ^GRP2L3 ^GRP2N IEC11000027-3-en.vsdx Protected Object IEC11000027 V3 EN-US Figure 16: Delta DAB connected three-phase CT set Line distance protection REL670 2.2 IEC Application manual...
Page 86
If frequency tracking and compensation is required (this feature is typically required only DFTReference for IEDs installed in the generating stations) then the setting parameters shall be set accordingly. Another alternative is to have the delta connected CT set as shown in figure 17: Line distance protection REL670 2.2 IEC Application manual...
CT to the IED. It gives an overview of the required actions by the user in order to make this measurement available to the built-in protection and control functions within the IED as well. Line distance protection REL670 2.2 IEC Application manual...
Page 88
IED, which are connected to this preprocessing function block. If frequency tracking and compensation is required (this feature is typically required DFTReference only for IEDs installed in the power plants) then the setting parameters shall be set accordingly. Line distance protection REL670 2.2 IEC Application manual...
The phase-to-phase value can be used even if each channel is connected to a phase-to-earth voltage from the VT. 4.2.4.1 Example SEMOD55055-47 v3 Consider a VT with the following data: Line distance protection REL670 2.2 IEC Application manual...
100 V • 110 V • 115 V • 120 V • 230 V The IED fully supports all of these values and most of them will be shown in the following examples. Line distance protection REL670 2.2 IEC Application manual...
For correct terminal designations, see the connection diagrams valid for the delivered IED. SMAI2 BLOCK AI3P REVROT ^GRP2L1 ^GRP2L2 ^GRP2L3 ^GRP2N #Not used IEC06000599-4-en.vsdx IEC06000599 V4 EN-US Figure 20: A Three phase-to-earth connected VT Line distance protection REL670 2.2 IEC Application manual...
Page 92
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio of the entered values exactly corresponds to ratio of one individual VT. (Equation 2) EQUATION1903 V1 EN-US Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
IED. It shall be noted that this VT connection is only used on lower voltage levels (that is, rated primary voltage below 40 kV). Line distance protection REL670 2.2 IEC Application manual...
Page 94
VTprim =13.8 kV VTsec =120 V Please note that inside the IED only ratio of these two parameters is used. Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
VT secondary voltage (110/3V in this particular example). Figure gives overview of required actions by the user in order to make this measurement available to the built-in protection and control functions within the IED as well. Line distance protection REL670 2.2 IEC Application manual...
Page 96
AI3P REVROT ^GRP2L1 # Not Used ^GRP2L2 # Not Used ^GRP2L3 # Not Used ^GRP2N +3Uo IEC06000601-4-en.vsdx IEC06000601 V4 EN-US Figure 23: Open delta connected VT in high impedance earthed power system Line distance protection REL670 2.2 IEC Application manual...
Page 97
If frequency tracking and compensation is required (this feature is typically required only for IEDs installed in the generating stations ) then the setting parameters DFTReference shall be set accordingly. Line distance protection REL670 2.2 IEC Application manual...
VT secondary voltage, that is, 115V or 115/√3V as in this particular example. Figure gives an overview of the actions which are needed to make this measurement available to the built-in protection and control functions within the IED. Line distance protection REL670 2.2 IEC Application manual...
Page 99
# Not Used ^GRP2L1 # Not Used ^GRP2L2 # Not Used ^GRP2L3 +3Uo ^GRP2N IEC06000602-4-en.vsdx IEC06000602 V4 EN-US Figure 24: Open delta connected VT in low impedance or solidly earthed power system Line distance protection REL670 2.2 IEC Application manual...
Page 100
If frequency tracking and compensation is required (this feature is typically required only for IEDs installed in the generating stations) then the setting parameters DFTReference shall be set accordingly. Line distance protection REL670 2.2 IEC Application manual...
AMU0600442 v15 IEC13000239-3-en.vsd IEC13000239 V3 EN-US Figure 25: Local human-machine interface The LHMI of the IED contains the following elements • Keypad • Display (LCD) • LED indicators • Communication port for PCM600 Line distance protection REL670 2.2 IEC Application manual...
4 Scroll bar (appears when needed) The function key button panel shows on request what actions are possible with the function buttons. Each function button has a LED indication that can be used as a Line distance protection REL670 2.2 IEC Application manual...
Page 103
Each panel is shown by pressing one of the function buttons or the Multipage button. Pressing the ESC button clears the panel from the display. Both panels have a dynamic width that depends on the label string length. Line distance protection REL670 2.2 IEC Application manual...
. These LEDs can indicate the status of two arbitrary binary signals by configuring the OPENCLOSE_LED function block. For instance, OPENCLOSE_LED can be connected to a circuit breaker to indicate the breaker open/close status on the LEDs. Line distance protection REL670 2.2 IEC Application manual...
The push-buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode. The keypad also contains programmable push-buttons that can be configured either as menu shortcut or control buttons. Line distance protection REL670 2.2 IEC Application manual...
Page 106
LHMI keypad with object control, navigation and command push- buttons and RJ-45 communication port 1...5 Function button Close Open Escape Left Down Right Enter Remote/Local Uplink LED Not in use Multipage Menu Line distance protection REL670 2.2 IEC Application manual...
The blocking of functions through the IEC61850 protocol can be reset in Main menu/Test/Reset IEC61850 Mod. The yellow LED changes to either On or Off state depending on the state of operation. Line distance protection REL670 2.2 IEC Application manual...
Numerical values are presented either in integer or in decimal format with minimum and maximum values. Character strings can be edited character by character. Enumerated values have a predefined set of selectable values. Line distance protection REL670 2.2 IEC Application manual...
Do not connect the IED front port to a LAN. Connect only a single local PC with PCM600 to the front port. It is only intended for temporary use, such as commissioning and testing. Line distance protection REL670 2.2 IEC Application manual...
Whereas, for UDP clients, the PMUREPORT instance for each UDP channel is defined by the user in the PMU and the client has to know the PMU ID corresponding to that instance in order to be able to communicate. More Line distance protection REL670 2.2 IEC Application manual...
IED over IEEE1344 protocol using the selected TCP port defined in 1344TCPport, and can communicate with the IED over IEEE C37.118 protocol using the selected TCP port number in C37.118TCPport. Line distance protection REL670 2.2 IEC Application manual...
PMUReportUDP[x] – Instance number of PMUREPORT function block that must send data on this UDP stream (UDP client group[x]) UDPDestAddres[x] – UDP destination address for UDP client group[x] (unicast / multicast address range) Line distance protection REL670 2.2 IEC Application manual...
Page 114
UDP data will be only sent to that specific unicast IP address. In addition to UDPDestAddress[x] parameter, UDPDestPort[x] parameter is used to define the UDP destination port number for UDP client group[x]. Line distance protection REL670 2.2 IEC Application manual...
The message generated by the PMUREPORT function block is set in accordance with the IEEE C37.118 and/or IEEE 1344 standards. Line distance protection REL670 2.2 IEC Application manual...
Page 116
PHASORREPORT blocks including 32 configurable phasor channels (8 phasor channels in each PHASORREPORT block). Each phasor channel can be configured as a 3-phase (symmetrical components positive/ negative/zero) or single-phase phasor (L1/L2/L3). Line distance protection REL670 2.2 IEC Application manual...
Page 117
BINARYREPORT blocks capable of reporting up to 24 Binary signals (8 Binary signals in each BINARYREPORT block). These binary signals can be for example dis-connector or breaker position indications or internal/ external protection alarm signals. Line distance protection REL670 2.2 IEC Application manual...
The IEEE C37.118 standard also imposes a variety of steady state and dynamic requirements which are fulfilled in the IED with the help of high accuracy measurements and advanced filtering techniques. Line distance protection REL670 2.2 IEC Application manual...
9 Hz to 95 Hz. In order to do that, the three-phase voltage signal shall be connected to the IED. Then IED can adapt its filtering algorithm in order to properly measure phasors of all current and voltage signals connected to the Line distance protection REL670 2.2 IEC Application manual...
Page 120
FREQREFCHERR output states if the reference frequency is good, or if there is an error or if the reference channel is unavailable. For more information refer to the table PMUREPORT monitored data. Line distance protection REL670 2.2 IEC Application manual...
This has to be considered in connection with C37.118, where the passband is defined relative to a fixed nominal frequency as shown in the equation 12. ± (Equation 12) IECEQUATION2418 V1 EN-US where, Line distance protection REL670 2.2 IEC Application manual...
CFG-3 in order to recalculate analog values, will get a better resolution than using the scale factors in CFG-2. The following examples show how the scale factor is calculated. Line distance protection REL670 2.2 IEC Application manual...
Page 123
The scale factor will be sent as 3051804 on configuration frame 2, and 305180.43 on configuration frame 3. The range of analog values that can be transmitted in this case is -305181 to -10000000000 and +305181 to +10000000000. Line distance protection REL670 2.2 IEC Application manual...
3 ms while the PHASORREPORT block is expecting input every 0.9 ms. The PHASORREPORT filtering window is designed to receive updated input every 0.9 ms and therefore the application will fail. Line distance protection REL670 2.2 IEC Application manual...
Page 125
PHASORREPORT blocks with different instance numbers. In this example, as the PHASORREPORT blocks have different instance numbers and different settings for SvcClass and ReportRate, a separate SMAI block is used for each PHASORREPORT block. Line distance protection REL670 2.2 IEC Application manual...
Page 126
In this example, SMAI1 will adapt its filtering according to PHASORREPORT instance 1 (because of higher priority) and therefore PHASORREPORT instance 2 will receive data which does not match its performance class and report rate. Line distance protection REL670 2.2 IEC Application manual...
Page 127
PHASORREPORT blocks in ACT where SMAI3 is configured as the reference block for DFT reference external out (DFTRefExtOut) and 3PHSUM uses external DFT reference (from SMAI3). Figures show the corresponding setting parameters. Line distance protection REL670 2.2 IEC Application manual...
Page 128
Figure 43: An example of correct connection of 3PHSUM and PHASORREPORT blocks in ACT IEC140000130-1-en.vsd IEC140000130 V1 EN-US Figure 44: SMAI1 setting parameters example-showing that SMAI3 is selected as the DFT reference (DFTRefGrp3) Line distance protection REL670 2.2 IEC Application manual...
Page 129
PHASORREPORT function block. On the other hand, when 3PHSUM uses external DFT reference, it also adapts its filtering according to the SMAI reference block. Therefore, in order to avoid two Line distance protection REL670 2.2 IEC Application manual...
Application Manual under section Basic IED functions. 6.2.4 Setting guidelines GUID-83969957-DABF-4B9B-95C7-B9F0AF6E647A v2 Based on the functionality and appearance in PCM600, the PMU reporting functionality is categorized into 4 different categories (function block) as follows: PMUREPORT PHASORREPORT ANALOGREPORT BINARYREPORT Line distance protection REL670 2.2 IEC Application manual...
Page 131
1, 2 and 3 organization defined in IEEE C37.118.2 message format. Here the user can select the data type of the calculated synchrophasors. The options are Integer or Float data. The Line distance protection REL670 2.2 IEC Application manual...
Page 132
IEEE floating-point format. The data sent via the DFREQ field is Rate Of Change Of Frequency (ROCOF), in Hertz per second times 100. It is ranged from –327.67 to Line distance protection REL670 2.2 IEC Application manual...
Page 133
PHASORREPORT is the function block responsible for reporting the synchrophasors. Each instance of PMUREPORT function block has 32 phasor channels with the following setting parameters; where X is a number from 1 to Line distance protection REL670 2.2 IEC Application manual...
Page 134
AnalogXUnitType: Unit type for analog signal X. It refers to the 4-byte ANUNIT field of the configuration frames 1, 2 organization defined in IEEE C37.118.2 message format. The options are Single point-on-wave, RMS of analog input and Peak of analog input. Line distance protection REL670 2.2 IEC Application manual...
Restricted earth fault protection for transformer, generator and shunt reactor windings • Restricted earth fault protection The application is dependent on the primary system arrangements and location of breakers, available CT cores and so on. Line distance protection REL670 2.2 IEC Application manual...
(that is, no operation) for external faults even in the presence of heavy CT saturation. The principle is based on the CT secondary current circulating between involved current transformers and not Line distance protection REL670 2.2 IEC Application manual...
Page 137
For such a case a voltage will be developed across the measuring branch. The calculations are made with the worst situations in mind and a minimum operating voltage U is calculated according to equation Line distance protection REL670 2.2 IEC Application manual...
Page 138
Adjust as required based on tables 16, or to values in between as required for the application. Minimum ohms can be difficult to adjust due to the small value compared to the total value. Line distance protection REL670 2.2 IEC Application manual...
Page 139
14. å = × n IR Ires lmag (Equation 14) EQUATION1747 V1 EN-US where: is the CT ratio primary current at IED pickup, Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 140
The series resistor is dimensioned for 200 W. Preferable the U>Trip SeriesResistor should always be lower than 200 W to allow continuous activation during testing. If this value is exceeded, testing should be done with a transient faults. Line distance protection REL670 2.2 IEC Application manual...
Page 141
I> Protected Object a) Through load situation b) Through fault situation c) Internal faults IEC05000427-2-en.vsd IEC05000427 V2 EN-US Figure 49: The high impedance principle for one phase with two current transformer inputs Line distance protection REL670 2.2 IEC Application manual...
3-Ph Plate with Metrosils and Resistors IEC07000193-5-en.vsdx IEC07000193 V5 EN-US Figure 50: CT connections for high impedance differential protection Description Scheme earthing point It is important to insure that only one earthing point exist in this scheme. Line distance protection REL670 2.2 IEC Application manual...
Measure the value achieved and set this value for this parameter. The value shall always be high impedance. This means for example, for 1A circuits say bigger than 400 ohms (400 VA) and Line distance protection REL670 2.2 IEC Application manual...
T-zone is protected with a separate differential protection scheme. The 1Ph high impedance differential HZPDIF function in the IED allows this to be done efficiently, see Figure 52. Line distance protection REL670 2.2 IEC Application manual...
Page 146
Line distance protection REL670 2.2 IEC Application manual...
Page 147
The current value at U>Trip is taken. For the voltage dependent resistor current the peak value of voltage 200 ˣ √2 is used. Then the RMS current is calculated by dividing obtained current value from Line distance protection REL670 2.2 IEC Application manual...
HZPDIF can be used to protect the tertiary reactor for phase faults as well as earth faults if the power system of the tertiary winding is direct or low impedance earthed. Line distance protection REL670 2.2 IEC Application manual...
Page 149
Line distance protection REL670 2.2 IEC Application manual...
Page 150
For the voltage dependent resistor current the peak value of voltage 30 ˣ √2 is used. Then the RMS current is calculated by dividing obtained current value from the metrosil curve with √2. Use the maximum value from the metrosil curve given in Figure 54. Line distance protection REL670 2.2 IEC Application manual...
The metrosil operating characteristic is given in the following figure. IEC05000749 V1 EN-US Figure 54: Current voltage characteristics for the non-linear resistors, in the range 10-200 V, the average range of current is: 0.01–10 mA Line distance protection REL670 2.2 IEC Application manual...
The distance protection function is designed to meet basic requirements for application on transmission and sub transmission lines (solid earthed systems) although it also can be used on distribution levels. Line distance protection REL670 2.2 IEC Application manual...
(Z0-Z1)/3 The voltage on the healthy phases is generally lower than 140% of the nominal phase-to-earth voltage. This corresponds to about 80% of the nominal phase-to- phase voltage. Line distance protection REL670 2.2 IEC Application manual...
The fault infeed may enlarge the fault impedance seen by the distance protection. This effect is very important to keep in mind when both planning the protection system and making the settings. Line distance protection REL670 2.2 IEC Application manual...
57. The load encroachment algorithm increases the possibility to detect high fault resistances, especially for line to earth faults at remote end. For example, for a given setting of the load angle ARGLd for the load encroachment function, the Line distance protection REL670 2.2 IEC Application manual...
Table 18: Definition of long lines Line category 110 kV 500 kV Long lines 77 km - 99 km 350 km - 450 km Very long lines > 99 km > 450 km Line distance protection REL670 2.2 IEC Application manual...
From an application point of view there exists three types of network configurations (classes) that must be considered when making the settings for the protection function. Those are: Line distance protection REL670 2.2 IEC Application manual...
Page 159
Here is the description of what happens when a fault occurs on the parallel line, as shown in figure 59. From symmetrical components, it is possible to derive the impedance Z at the IED point for normal lines without mutual coupling according to equation 27. Line distance protection REL670 2.2 IEC Application manual...
Page 160
Equivalent zero sequence impedance circuit of the double-circuit, parallel, operating line with a single phase-to-earth-fault at the remote busbar When mutual coupling is introduced, the voltage at the IED point A is changed, according to equation 28. Line distance protection REL670 2.2 IEC Application manual...
Page 161
Notice that the following relationship exists between the zero sequence currents: ⋅ ⋅ − (Equation 31) EQUATION1279 V3 EN-US Simplification of equation 31, solving it for 3I0p and substitution of the result into equation gives that the voltage can be drawn as: Line distance protection REL670 2.2 IEC Application manual...
Page 162
When the parallel line is out of service and earthed at both ends on the bus bar side of the line CT so that zero sequence current can flow on the parallel line, the equivalent zero sequence circuit of the parallel lines will be according to figure 61. Line distance protection REL670 2.2 IEC Application manual...
Page 164
(Equation 37) EQUATION1284 V1 EN-US This means that the reach is reduced in reactive and resistive directions. If the real and imaginary components of the constant A are equal to equation equation 39. Line distance protection REL670 2.2 IEC Application manual...
EQUATION1288 V2 EN-US Ensure that the underreaching zones from both line ends will overlap a sufficient amount (at least 10%) in the middle of the protected circuit. 8.1.2.7 Tapped line application SEMOD168232-266 v2 Line distance protection REL670 2.2 IEC Application manual...
Page 166
Transformation ratio for transformation of impedance at U1 side of the transformer to the measuring side U2 (it is assumed that current and voltage distance function is taken from U2 side of the transformer). Line distance protection REL670 2.2 IEC Application manual...
Page 167
A. In practice, the setting of fault resistance for both phase-to-earth (RFPE) and phase-to-phase (RFPP) must be as high as possible without interfering with the load impedance to obtain reliable fault detection. Line distance protection REL670 2.2 IEC Application manual...
45. The effect of series compensation is in this particular case obvious and self explanatory. Line (Equation 45) EQUATION1895 V1 EN-US A typical 500 km long 500 kV line is considered with source impedance (Equation 46) EQUATION1896 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 169
, because if it does, the system cannot get back to equilibrium and the synchronism is lost. The first swing stability and the stability margin can be evaluated by studying the different areas in figure Line distance protection REL670 2.2 IEC Application manual...
Page 170
The reactive power balance of a series compensated line is shown in figure as an example for 500 km long 500 kV transmission line with 50% compensation degree. Line distance protection REL670 2.2 IEC Application manual...
Page 171
The effect on the power transfer when considering a constant angle difference (δ) between the line ends is illustrated in figure 72. Practical compensation degree runs from 20 to 70 percent. Transmission capability increases of more than two times can be obtained in practice. Line distance protection REL670 2.2 IEC Application manual...
Page 172
The cost of series compensation is small compared to the cost of a transmission line. When evaluating the cost of a transmission system upgrade also the cost of secondary equipment such as eventual Line distance protection REL670 2.2 IEC Application manual...
Page 173
75. A TSSC typically consists of a few segments in series that can be inserted independently of each other in order to achieve different total series capacitor reactance. en06000595.vsd IEC06000595 V1 EN-US Figure 75: Thyristor switched series capacitor Line distance protection REL670 2.2 IEC Application manual...
Page 174
TCSC wave forms presented in capacitive boost mode for a typical 50Hz system The apparent impedance of the TCSC (the impedance seen by the power system) can typically be increased to up to 3 times the physical impedance of the capacitor, Line distance protection REL670 2.2 IEC Application manual...
The most important challenges, which influence the operation of different protection functions in the greatest extent, are described in this chapter. Line distance protection REL670 2.2 IEC Application manual...
Page 176
IED point is this way proportional to sum of voltage drops on partial impedances between the IED point and the fault position F, as presented by × (Equation 49) EQUATION1901 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 177
It is a common practice to call this phenomenon voltage inversion. Its consequences on operation of different protections in series compensated networks depend on their operating principle. The most known effect has voltage Line distance protection REL670 2.2 IEC Application manual...
Page 178
90 electrical degrees, which means that reactive current will flow from series compensated line to the system. The system conditions are in such case presented by equation Line distance protection REL670 2.2 IEC Application manual...
Page 179
IEDs. The most obvious difference is generally seen in fault currents. Figure presents a simplified picture of a series compensated network with basic Line distance protection REL670 2.2 IEC Application manual...
Page 180
• The transient DC component, which magnitude depends on the fault incident angle decays with the circuit time constant L R s (Equation 56) EQUATION1907 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 181
DC component, which diminishes completely in approximately 120ms. The final magnitude of the fault current on compensated line is higher due to the decreased apparent impedance of a line (60% Line distance protection REL670 2.2 IEC Application manual...
Page 182
- jX CT 1 CT 2 VT 2 en06000611.vsd IEC06000611 V1 EN-US Figure 85: Possible positions of instrument transformers relative to line end series capacitor Line distance protection REL670 2.2 IEC Application manual...
Page 183
IEDs on protected power lines. Figure presents typical locations of capacitor banks on power lines together with corresponding compensation degrees. Distance IED near the feeding bus will see in different cases fault on remote end Line distance protection REL670 2.2 IEC Application manual...
Page 184
LOC = 50% LOC = 33%, 66% LOC = 100% en06000613.vsd IEC06000613 V1 EN-US Figure 87: Apparent impedances seen by distance IED for different SC locations and spark gaps used for overvoltage protection Line distance protection REL670 2.2 IEC Application manual...
Page 185
D,L “A Linearized Model for MOV-Protected series capacitors” Paper 86SM357– 8 IEEE/PES summer meeting in Mexico City July 1986) have resulted in construction of a non-linear equivalent circuit with series connected capacitor and Line distance protection REL670 2.2 IEC Application manual...
Page 186
• Series capacitor becomes nearly completely bridged by MOV when the line current becomes higher than 10-times the protective current level (I £ 10· k · Line distance protection REL670 2.2 IEC Application manual...
D bus and the fault becomes equal to zero, if the capacitor is installed near the bus and the fault appears just behind the capacitor. This may cause the phenomenon of voltage inversion to be expanded very deep Line distance protection REL670 2.2 IEC Application manual...
This makes it necessary to install distance protection in combination with telecommunication. The most common is distance protection in Permissive Overreaching Transfer Trip mode (POTT). Line distance protection REL670 2.2 IEC Application manual...
Page 189
If the capacitor is out of service or bypassed, the reach with these settings can be less than 50% of protected line dependent on compensation degree and there will be a section, G in figure 91, of the power line where no tripping occurs from either end. Line distance protection REL670 2.2 IEC Application manual...
Page 190
Distance protections of adjacent power lines shown in figure are influenced by this negative impedance. If the intermediate infeed of short circuit power by other lines is taken into consideration, the negative voltage drop on X is amplified and a Line distance protection REL670 2.2 IEC Application manual...
Page 191
In such case the reactance of a short adjacent line may be lower than the capacitor reactance and voltage inversion phenomenon may occur also on remote end of Line distance protection REL670 2.2 IEC Application manual...
Page 192
The operating area for negative impedance depends upon the magnitude of the source impedance and calculations must be made on a case by Line distance protection REL670 2.2 IEC Application manual...
Page 193
The current reversal phenomenon also raises problems from the protection point of view, particularly when the power lines are short and when permissive overreach schemes are used. Line distance protection REL670 2.2 IEC Application manual...
Page 194
99, than also one distance IED (operating in POTT teleprotection scheme) on parallel, healthy circuit will send a carrier signal CSAB to the remote line end, where this signal will be received as a carrier receive signal CRBB. Line distance protection REL670 2.2 IEC Application manual...
The settings for the distance protection function are done in primary values. The instrument transformer ratio that has been set for the analog input card is used to automatically convert the measured secondary input signals to primary values used in the distance protection function. Line distance protection REL670 2.2 IEC Application manual...
If the requirements in the bullet—listed paragraphs above gives a zone2 reach less than 120%, the time delay of zone2 must be increased by approximately 200ms to Line distance protection REL670 2.2 IEC Application manual...
³ × Zrev Z rem (Equation 74) EQUATION1525 V5 EN-US Where: is the protected line impedance Z2rem is zone2 setting at remote end of protected line. Line distance protection REL670 2.2 IEC Application manual...
Due to the sub-harmonic oscillation swinging caused by the series capacitor at fault conditions the reach of the under-reaching zone 1 must be further reduced. Zone 1 can only be set with a percentage reach to the artificial fault according to the curve Line distance protection REL670 2.2 IEC Application manual...
Page 199
Different settings of the reach for the ph-ph faults and ph-E loops makes it possible to minimise the necessary decrease of the reach for different types of faults. Reactive Reach Compensated lines with the capacitor into the zone 1 reach : Line distance protection REL670 2.2 IEC Application manual...
Page 200
Section 8 1MRK 506 369-UEN B Impedance protection LLOC en07000063.vsd IEC07000063 V1 EN-US Figure 102: Simplified single line diagram of series capacitor located at X LLOC ohm from A station Line distance protection REL670 2.2 IEC Application manual...
Page 201
When the calculation of XFw gives a negative value the zone 1 must be permanently blocked. For protection on non compensated lines facing series capacitor on next line. The setting is thus: Line distance protection REL670 2.2 IEC Application manual...
Page 202
Settings of the resistive reaches are limited according to the minimum load impedance. Line distance protection REL670 2.2 IEC Application manual...
Check the reduction of a reach for the overreaching zones due to the effect of the zero sequence mutual coupling. The reach is reduced for a factor: × (Equation 78) EQUATION1426 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
MVA. The load impedance [Ω/phase] is a function of the minimum operation voltage and the maximum load current: --------------------- - load × (Equation 88) EQUATION574 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 206
More accurate calculations are necessary according to equation 92. R1PP £ × × × RFPP 1.6 Z cosJ – -------------- - sinJ loadmin X1PP (Equation 92) EQUATION580 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Operation parameter to Off. Different time delays are possible for the ph-E (tPE) and for the ph-ph (tPP) measuring loops in each distance protection zone separately, to further increase the total flexibility of a distance protection. Line distance protection REL670 2.2 IEC Application manual...
8.2.3.1 Load encroachment characteristics M13142-3 v6 The phase selector must at least cover the overreaching zone 2 in order to achieve correct phase selection for utilizing single-phase autoreclosing for faults on the Line distance protection REL670 2.2 IEC Application manual...
Page 209
With reference to figure 104, the following equations for the setting calculations can be obtained. Index PHS in images and equations reference settings for Phase selection with load encroachment function FDPSPDIS and index Zm reference settings for Distance protection function (ZMQPDIS). Line distance protection REL670 2.2 IEC Application manual...
Page 210
Relation between distance protection phase selection (FDPSPDIS) and impedance zone (ZMQPDIS) for phase-to-earth fault φloop>60° (setting parameters in italic) 1 FDPSPDIS (phase selection)(red line) 2 ZMQPDIS (Impedance protection zone) RFltRevPG +XN)/tan(60°) RFltFwdPG RFPG 8 φloop Line distance protection REL670 2.2 IEC Application manual...
Page 211
FDPSPDIS characteristic shall cut off some part of the zone measurement characteristic. Phase-to-earth fault in reverse direction M13142-151 v4 Reactive reach M13142-153 v2 The reactive reach in reverse direction is the same as for forward so no additional setting is required. Line distance protection REL670 2.2 IEC Application manual...
Page 212
FDPSPDIS characteristic angle is changed from 60 degrees to 90 degrees (rotated 30° anti-clock wise). Line distance protection REL670 2.2 IEC Application manual...
The resistive boundary RLdRv for load encroachment characteristic in reverse direction can be calculated in the same way as RLdFw, but use maximum importing power that might occur instead of maximum exporting power and the relevant Umin voltage for this condition. Line distance protection REL670 2.2 IEC Application manual...
The distance protection function in the IED is designed to meet basic requirements for application on transmission and sub-transmission lines (solid earthed systems) although it also can be used on distribution levels. Line distance protection REL670 2.2 IEC Application manual...
(kV) in the faulty phase before fault is the positive sequence impedance (Ω/phase) is the negative sequence impedance (Ω/phase), is considered to be equal to Z Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 217
EQUATION2122 V1 EN-US £ (Equation 104) EQUATION2123 V1 EN-US Where is the zero sequence source resistance is the zero sequence source reactance is the positive sequence source resistance is the positive sequence source reactance Line distance protection REL670 2.2 IEC Application manual...
Page 218
The neutral point reactor is normally designed so that it can be tuned to a position where the reactive current balances the capacitive current from the network that is: × × (Equation 106) EQUATION1272 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
⋅ ⋅ ⋅ (Equation 107) EQUATION1273-IEC-650 V2 EN-US If we divide U by I we get Z present to the IED at A side. = p ·Z ·R (Equation 108) EQUATION1274-IEC-650 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
This is valid in both directions. The use of the load encroachment feature is essential for long heavily loaded lines, where there might be a conflict between the necessary emergency load transfer and Line distance protection REL670 2.2 IEC Application manual...
The different network configuration classes are: Parallel line with common positive and zero sequence network Parallel circuits with common positive but isolated zero sequence network Parallel circuits with positive and zero sequence sources isolated. Line distance protection REL670 2.2 IEC Application manual...
Page 224
From symmetrical components, we can derive the impedance Z at the relay point for normal lines without mutual coupling according to equation 109. − ⋅ ⋅ ⋅ (Equation 109) IECEQUATION1275 V2 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 225
A side as: æ ö × ç ÷ × I ph è ø (Equation 111) EQUATION1277 V3 EN-US Where: = Z0m/(3 · Z1L) Line distance protection REL670 2.2 IEC Application manual...
Page 226
90% of the line reactance p=71% that is, the protection is underreaching with approximately 20%. The zero sequence mutual coupling can reduce the reach of distance protection on the protected circuit when the parallel line is in normal operation. The reduction of Line distance protection REL670 2.2 IEC Application manual...
Page 227
R equals to zero. They consider only the zero sequence, mutual reactance X . Calculate the equivalent X and R zero sequence parameters according to equation and equation for each Line distance protection REL670 2.2 IEC Application manual...
Page 228
IEC09000255_1_en.vsd IEC09000255 V1 EN-US Figure 117: Equivalent zero-sequence impedance circuit for a double-circuit line with one circuit disconnected and not earthed The reduction of the reach is equal to equation 119. Line distance protection REL670 2.2 IEC Application manual...
EQUATION1288 V2 EN-US Ensure that the underreaching zones from both line ends will overlap a sufficient amount (at least 10%) in the middle of the protected circuit. 8.3.2.7 Tapped line application M17048-243 v3 Line distance protection REL670 2.2 IEC Application manual...
Page 230
U2 (it is assumed that current and voltage distance function is taken from U2 side of the transformer). is the line impedance from the T point to the fault (F). Transformer impedance Line distance protection REL670 2.2 IEC Application manual...
Page 231
RFPP should be as high as possible without interfering with the load impedance in order to obtain reliable fault detection. However for zone1 it is necessary to limit the reach according to setting instructions in order to avoid overreach. Line distance protection REL670 2.2 IEC Application manual...
120% of the protected line. The zone 2 reach can be even higher if the fault infeed from adjacent lines at remote end is considerable higher than the fault current at the IED location. Line distance protection REL670 2.2 IEC Application manual...
The same applies to the back-up protection of the bus bar or power transformers. It is necessary to secure, that it always covers the overreaching zone, used at the remote line IED for the telecommunication purposes. Line distance protection REL670 2.2 IEC Application manual...
(Equation 130) EQUATION554 V1 EN-US Check the reduction of a reach for the overreaching zones due to the effect of the zero sequence mutual coupling. The reach is reduced for a factor: Line distance protection REL670 2.2 IEC Application manual...
The final reach in resistive direction for phase-to-earth fault loop measurement automatically follows the values of the line-positive and zero-sequence resistance, and at the end of the protected zone is equal to equation 136. Line distance protection REL670 2.2 IEC Application manual...
Where: is the minimum phase-to-phase voltage in kV is the maximum apparent power in MVA. The load impedance [Ω/phase] is a function of the minimum operation voltage and the maximum load current: Line distance protection REL670 2.2 IEC Application manual...
Page 237
More accurate calculations are necessary according to equation 145. Line distance protection REL670 2.2 IEC Application manual...
The evaluation of the directionality takes place in Directional impedance quadrilateral function ZDRDIR. Equation and equation are used to classify that the fault is in forward direction for phase-to-earth fault and phase-to-phase fault. Line distance protection REL670 2.2 IEC Application manual...
Page 239
(as shown in figure 120). It should not be changed unless system studies have shown the necessity. ZDRDIR gives binary coded directional information per measuring loop on the output STDIRCND. STDIR= STFWL1*1+STFWL2*2+STFWL3*4+STFWL1L2*8+ +STFWL2L3*16+STFWL3L1*32+STRVL1*64+STRVL2*128+ +STRVL3*256+STRVL1L2*512+STRVL2L3*1024+STRVL3L1*2048 Line distance protection REL670 2.2 IEC Application manual...
Page 240
If the fault was detected in the reverse direction, the measuring element in the reverse direction remains in operation. • If the current decreases below the minimum operating value, the memory resets until the positive sequence voltage exceeds 10% of its rated value. Line distance protection REL670 2.2 IEC Application manual...
Full-scheme distance measuring, mho characteristic function (ZMHPDIS) in the IED is designed to meet basic requirements for application on transmission and sub-transmission lines (solid earthed systems) although it also can be used on distribution levels. Line distance protection REL670 2.2 IEC Application manual...
(Z The voltage on the healthy phases is generally lower than 140% of the nominal phase-to-earth voltage. This corresponds to about 80% of the nominal phase-to- phase voltage. Line distance protection REL670 2.2 IEC Application manual...
Page 243
Line distance protection REL670 2.2 IEC Application manual...
Page 244
The neutral point reactor is normally designed so that it can be tuned to a position where the inductive current balances the capacitive current from the network that × × (Equation 153) EQUATION1272 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
⋅ ⋅ ⋅ (Equation 154) EQUATION1273-IEC-650 V2 EN-US If we divide V by IA we get Z present to the IED at A side = p ·Z ·R (Equation 155) EQUATION1274-IEC-650 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
This has the drawback that it will reduce the sensitivity of the protection, that is, the ability to detect resistive faults. Load Load Load Load Load Load Load Load operation en06000403.vsd IEC06000403 V1 EN-US Figure 124: Load encroachment phenomena and shaped load encroachment characteristic Line distance protection REL670 2.2 IEC Application manual...
Page 247
So, for short lines, the load encroachment function could preferably be switched off. The main settings of the parameters for load encroachment are done in Faulty phase identification with load encroachment for mho function FMPSPDIS. The Line distance protection REL670 2.2 IEC Application manual...
What can be recognized as long lines with respect to the performance of distance protection is noted in table 22. Line distance protection REL670 2.2 IEC Application manual...
Mutual coupling effect The mutual coupling is based on the known induction law, that a current induces a longitudinal voltage in the parallel circuit. The induced voltage is: × (Equation 156) IECEQUATION14002 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 250
It can be shown from analytical calculations of line impedances that the mutual impedances for positive and negative sequence are very small (< 1-2% of the self impedance) and it is a practice to neglect them. Line distance protection REL670 2.2 IEC Application manual...
Page 251
IECEQUATION14004 V1 EN-US Where: is phase to earth short circuit voltage at the relay location in the faulted phase is short circuit current in the faulted phase Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 252
ê ú ë û (Equation 163) IECEQUATION14010 V1 EN-US Where: earth current of faulty line is earth current of the parallel line is line positive sequence impedance Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 253
Different setting values that influence the earth -return compensation for different distance zones within the same group of setting parameters. • Different groups of setting parameters for different operating conditions of a protected multi circuit line. Line distance protection REL670 2.2 IEC Application manual...
Transformation ratio for transformation of impedance at U1 side of the transformer to the measuring side U2 (it is assumed that current and voltage distance function is taken from U2 side of the transformer). Line distance protection REL670 2.2 IEC Application manual...
• The effect of a load transfer between the terminals of the protected line, the fault resistance is considerable and the effect must be recognized. • Zero-sequence mutual coupling from parallel lines. Line distance protection REL670 2.2 IEC Application manual...
8.4.3.3 Setting of overreaching zone 8.4.3.4 Setting of zone 2 GUID-5A41709F-8AB2-4A4B-9B3E-3B48EBD0DE0D v1 Zone 2 distance elements must be set according to the following criteria: Line distance protection REL670 2.2 IEC Application manual...
In these equations, x stands for ratio of distance to fault and length of the line, and Z stands for the impedance seen by the relay. Line distance protection REL670 2.2 IEC Application manual...
Page 258
× (Equation 169) IECEQUATION14005 V1 EN-US ⋅ (Equation 170) IEC13000297 V1 EN-US Case 2: Parallel line switched off and not earthed or earthed at one line end Line distance protection REL670 2.2 IEC Application manual...
Page 259
In case 3, the highest impedance is measured, which corresponds to the shortest reach. The mutual impedance will influence the distance measurement of ground faults and cause either an extension or a reduction of the reach relative to the set reach. Line distance protection REL670 2.2 IEC Application manual...
Page 260
To eliminate the overreach caused by the earthed parallel line, set the K for the zone 1 as: (Equation 173) IECEQUATION14018 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 261
The earth-fault compensation factor must be adjusted to the case of parallel line in service (case 3) where the highest earth-fault impedance occurs. (Equation 176) IECEQUATION14019 V1 EN-US For case 1, the measured impedance can be calculated by the following expression: Line distance protection REL670 2.2 IEC Application manual...
Page 262
With this method of setting the zero sequence compensation factor K can for zone 1 and zone 2 be even better adapted for the real system conditions. The table describes earth-fault compensation settings to be adopted for different groups. Line distance protection REL670 2.2 IEC Application manual...
The minimum load impedance (Ω/phase) is calculated as: ------ - loadmin (Equation 180) EQUATION571 V1 EN-US Where: is the minimum phase-to-phase voltage in kV is the maximum apparent power in MVA. Line distance protection REL670 2.2 IEC Application manual...
Page 264
The result gives the maximum diameter (RFPE) for which the load impedance touch the circle with the given load condition. Use an extra margin of 20% to give sufficient distance between the calculated minimum load impedance and relay boundary. Line distance protection REL670 2.2 IEC Application manual...
SEMOD154469-129 v3 The parameters for load encroachment shaping of the characteristic are found in the description of Faulty phase identification with load encroachment for mho (FMPSPDIS), refer to section "Load encroachment characteristics". Line distance protection REL670 2.2 IEC Application manual...
In the case of evolving faults or momentary current transformer saturation conditions, the pick up of the zones may get delayed. Zone timer logic improves the operating time in such conditions. The zone timer logic can be set using the Line distance protection REL670 2.2 IEC Application manual...
In the following some hints with respect to distance protection are highlighted. Solid earthed networks SEMOD154680-14 v3 In solid earthed systems the transformer neutrals are connected solidly to earth without any impedance between the transformer neutral and earth. Line distance protection REL670 2.2 IEC Application manual...
Page 268
Effectively earthed networks SEMOD154680-40 v4 A network is defined as effectively earthed if the earth fault factor fe is less than 1.4. The earth fault factor is defined according to equation 185. Line distance protection REL670 2.2 IEC Application manual...
Page 269
(3U0) will have the same magnitude in different places in the network due to low voltage drop distribution. The magnitude of the total fault current can be calculated according to the formula below: Line distance protection REL670 2.2 IEC Application manual...
Page 270
For this reason a separate high sensitive earth-fault protection is necessary to carry out the fault clearance for single phase- to-earth fault. Line distance protection REL670 2.2 IEC Application manual...
The effect of load encroachment is illustrated to the left in figure 136. The entrance of the load impedance inside the characteristic is of cause not allowed and the way to handle this with conventional distance Line distance protection REL670 2.2 IEC Application manual...
Load encroachment is not so common. The line length that can be recognized as a short line is not a fixed length; it depends on system parameters such as voltage and source impedance, see table "Short line application". Line distance protection REL670 2.2 IEC Application manual...
(risk for unwanted trip due to load encroachment is eliminated). 8.5.2.7 Parallel line application with mutual coupling SEMOD154680-148 v1 Line distance protection REL670 2.2 IEC Application manual...
Page 274
Most multi circuit lines have two parallel operating circuits. The application guide mentioned below recommends in more detail the setting practice for this particular type of line. The basic principles also apply to other multi circuit lines. Line distance protection REL670 2.2 IEC Application manual...
Page 275
Z< Z< en05000221.vsd IEC05000221 V1 EN-US Figure 137: Class 1, parallel line in service. The equivalent circuit of the lines can be simplified, see figure 138. Line distance protection REL670 2.2 IEC Application manual...
Page 276
When the parallel line is out of service and earthed at both ends on the bus bar side of the line CT so that zero sequence current can flow on the parallel line, the Line distance protection REL670 2.2 IEC Application manual...
Page 278
(Equation 196) EQUATION1284 V1 EN-US This means that the reach is reduced in reactive and resistive directions. If the real and imaginary components of the constant A are equal to equation equation 198. Line distance protection REL670 2.2 IEC Application manual...
EQUATION1288 V2 EN-US Ensure that the underreaching zones from both line ends will overlap a sufficient amount (at least 10%) in the middle of the protected circuit. 8.5.2.8 Tapped line application SEMOD154680-265 v1 Line distance protection REL670 2.2 IEC Application manual...
Page 280
Transformation ratio for transformation of impedance at U1 side of the transformer to the measuring side U2 (it is assumed that current and voltage distance function is taken from U2 side of the transformer). Line distance protection REL670 2.2 IEC Application manual...
Page 281
In practice, the setting of fault resistance for both phase-to-earth (RFPE) and phase-to-phase (RFPP) should be as high as possible without interfering with the load impedance in order to obtain reliable fault detection. Line distance protection REL670 2.2 IEC Application manual...
Consider the possible enlarging factor that might exist due to fault infeed from adjacent lines. Equation can be used to calculate the reach in reverse direction when the zone is used for blocking scheme, weak-end infeed and so on. Line distance protection REL670 2.2 IEC Application manual...
If the denominator in equation is called B and Z0m is simplified to X0m, then the real and imaginary part of the reach reduction factor for the overreaching zones can be written as: Line distance protection REL670 2.2 IEC Application manual...
To avoid load encroachment for the phase-to-earth measuring elements, the set resistive reach of any distance protection zone must be less than 80% of the minimum load impedance. Line distance protection REL670 2.2 IEC Application manual...
If the load current compensation is activated, there is an additional criteria IMinOpIN that will block the phase-earth loop if the 3I0<IMinOpIN. The default setting of IMinOpIN is 5% of the IED base current IBase. Line distance protection REL670 2.2 IEC Application manual...
The sector is mirror-symmetric along the MTA (Maximum Torque Axis). Directional elements for earth-faults must operate at fault current values below the magnitude of load currents. As phase quantities are adversely affected by load, the Line distance protection REL670 2.2 IEC Application manual...
Page 289
0 degrees. Care must be taken to ensure that neutral current direction remains unchanged during all network configurations and faults, and therefore all transformer configurations/constructions are not suitable for polarization. Line distance protection REL670 2.2 IEC Application manual...
Page 290
(see equation 221), and similarly it must be ensured that |U | >> |k · I | for reverse faults. + × × AngleRCA k I e (Equation 221) EQUATION1639 V2 EN-US Line distance protection REL670 2.2 IEC Application manual...
PilotMode: Set PilotMode to On when pilot scheme is to be used. In this mode fault inception function will send a block signal to remote end to block the overreaching zones, when operated. Line distance protection REL670 2.2 IEC Application manual...
The ability to accurately and reliably classifying different types of fault so that single pole tripping and autoreclosing can be used which plays an important roll in this matter. Line distance protection REL670 2.2 IEC Application manual...
IMaxLoad: The setting IMaxLoad must be set higher than the maximum load current transfer during emergency conditions including a safety margin of at least 20%. The setting is proposed to be according to equation 222: Line distance protection REL670 2.2 IEC Application manual...
ARGLd RLdRv en05000226.vsd IEC05000226 V1 EN-US Figure 145: Load encroachment characteristic The calculation of the apparent load impedance Z and minimum load load impedance Z can be done according to equations: loadmin Line distance protection REL670 2.2 IEC Application manual...
The setting of RLd and ArgLd is by default set to 80 ohm/phase and 20 degrees. Those values must be adapted to the specific application. Distance protection zone, quadrilateral characteristic, separate settings ZMRPDIS, ZMRAPDIS and ZDRDIR GUID-7308DB86-32CE-4615-95DC-92BEEF69E184 v1 Line distance protection REL670 2.2 IEC Application manual...
Some hints with respect to distance protection are highlighted below. Solid earthed networks GUID-02632014-090D-4D95-B678-6DFC7DE998A7 v1 In solidly earthed systems, the transformer neutrals are connected solidly to earth without any impedance between the transformer neutral and earth. Line distance protection REL670 2.2 IEC Application manual...
Page 297
Effectively earthed networks GUID-5F4CCC18-2BAC-4140-B56C-B9002CD36318 v1 A network is defined as effectively earthed if the earth-fault factor f is less than 1.4. The earth-fault factor is defined according to equation 229. Line distance protection REL670 2.2 IEC Application manual...
Page 298
What is typical for this type of network is that the magnitude of the earth fault current is very low compared to the short circuit current. The voltage on the healthy phases will get a magnitude of √3 times the phase voltage during the fault. Line distance protection REL670 2.2 IEC Application manual...
Page 299
Phase preference logic (PPLPHIZ) is needed, which is not common to be used in transmission applications. In this type of network, it is mostly not possible to use distance protection for detection and clearance of earth-faults. The low magnitude of the earth-fault Line distance protection REL670 2.2 IEC Application manual...
When the line is heavily loaded, the distance protection at the exporting end will have a tendency to overreach. To handle this phenomenon, the IED has an adaptive Line distance protection REL670 2.2 IEC Application manual...
So, for short lines, the load encroachment function could preferably be switched off. See section "Load impedance limitation, without load encroachment function". The settings of the parameters for load encroachment are done in , FRPSPDIS function. Line distance protection REL670 2.2 IEC Application manual...
GUID-40F06841-F192-4159-87BA-7BC7E4B014AA v1 For long transmission lines, the margin to the load impedance, that is, to avoid load encroachment, will normally be a major concern. It is well known that it is difficult Line distance protection REL670 2.2 IEC Application manual...
The different network configuration classes are: Parallel line with common positive and zero sequence network Parallel circuits with common positive but isolated zero sequence network Parallel circuits with positive and zero sequence sources isolated. Line distance protection REL670 2.2 IEC Application manual...
Page 304
Let us analyze what happens when a fault occurs on the parallel line see figure 150. From symmetrical components, we can derive the impedance Z at the relay point for normal lines without mutual coupling according to equation 236. Line distance protection REL670 2.2 IEC Application manual...
Page 305
Equivalent zero sequence impedance circuit of the double-circuit, parallel, operating line with a single phase-to-earth fault at the remote busbar. When mutual coupling is introduced, the voltage at the relay point A will be changed according to equation 237. Line distance protection REL670 2.2 IEC Application manual...
Page 306
⋅ ⋅ − (Equation 240) EQUATION1279 V3 EN-US Simplification of equation 240, solving it for 3I0p and substitution of the result into equation gives that the voltage can be drawn as: Line distance protection REL670 2.2 IEC Application manual...
Page 307
When the parallel line is out of service and earthed at both line ends on the bus bar side of the line CTs so that zero sequence current can flow on the parallel line, the equivalent zero sequence circuit of the parallel lines will be according to figure 153. Line distance protection REL670 2.2 IEC Application manual...
Page 309
The line zero sequence mutual impedance does not influence the measurement of the distance protection in a faulty circuit. IEC09000255_1_en.vsd IEC09000255 V1 EN-US Figure 155: Equivalent zero sequence impedance circuit for a double-circuit line with one circuit disconnected and not earthed. Line distance protection REL670 2.2 IEC Application manual...
U2 (it is assumed that current and voltage distance function is taken from U2 side of the transformer). is the line impedance from the T point to the fault (F). Transformer impedance Line distance protection REL670 2.2 IEC Application manual...
Page 311
In practice, the setting of fault resistance for both phase-to-earth RFPE and phase- to-phase RFPP should be as high as possible without interfering with the load impedance in order to obtain reliable fault detection. Line distance protection REL670 2.2 IEC Application manual...
Consider the possible enlarging factor that might exist due to fault infeed from adjacent lines. Equation can be used to calculate the reach in reverse direction when the zone is used for blocking scheme, weak-end infeed etc. Line distance protection REL670 2.2 IEC Application manual...
Check the reduction of a reach for the overreaching zones due to the effect of the zero sequence mutual coupling. The reach is reduced for a factor: × (Equation 253) EQUATION1426 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
MVA. The load impedance [Ω/phase] is a function of the minimum operation voltage and the maximum load current: --------------------- - load × (Equation 263) EQUATION574 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 317
More accurate calculations are necessary according to equation 267. R1Zx RFPPZx 1.6 Z load min X1Zx (Equation 267) IECEQUATION2307 V2 EN-US Line distance protection REL670 2.2 IEC Application manual...
Operation parameter to Off. Different time delays are possible for the phase-to-earthtPE and for the phase-to-phase tPP measuring loops in each distance protection zone separately, to further increase the total flexibility of a distance protection. Line distance protection REL670 2.2 IEC Application manual...
The outline of the characteristic is presented in figure 158. As illustrated, the resistive blinders are set individually in forward and reverse direction while the angle of the sector is the same in all four quadrants. Line distance protection REL670 2.2 IEC Application manual...
Page 320
FRPSPDIS function. When output signal STCNDZis selected, the characteristic for the FRPSPDIS (and also zone measurement depending on settings) can be reduced by the load encroachment characteristic (as shown in figure 159). Line distance protection REL670 2.2 IEC Application manual...
Page 321
160. The figure shows a distance measuring zone operating in forward direction. Thus, the operating area of the zone together with the load encroachment area is highlighted in black. Line distance protection REL670 2.2 IEC Application manual...
Page 322
R-axis. Consequently, it will be more or less necessary to use the load encroachment characteristic in order to secure a margin to the load impedance. Line distance protection REL670 2.2 IEC Application manual...
Page 323
30 degrees when subject to a pure phase-to-phase fault. At the same time, the characteristic "shrinks" by 2/√3, from the full RLdFw/RLdRv reach, which is valid at load or three-phase fault. Line distance protection REL670 2.2 IEC Application manual...
STCNDZ or STCNDLE must be connected to input STCND on distance zones. For normal overhead lines, the angle for the loop impedance φ for phase-to-earth fault defined according to equation 268. Line distance protection REL670 2.2 IEC Application manual...
With reference to figure 163, the following equations for the setting calculations can be obtained. Index PHS in images and equations reference settings for Phase selection with load encroachment function (FRPSPDIS) and index Zm reference settings for Distance protection function (ZMRPDIS). Line distance protection REL670 2.2 IEC Application manual...
Page 326
Teleprotection schemes, mostly zone 2. Equation and equation gives the minimum recommended reactive reach. These recommendations are valid for both 60 and 90 deg. characteristic angle. ³ × 1.44 X1 (Equation 269) EQUATION1309 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Resistive reach M13142-156 v4 The resistive reach in reverse direction must be set longer than the longest reverse zones. In blocking schemes it must be set longer than the overreaching zone at Line distance protection REL670 2.2 IEC Application manual...
0.91 RFPP > × RFFwPP 1.82 R PP (Equation 275) EQUATION2226 V1 EN-US where: RFPP is the setting of the longest reach of the overreaching zones that must be covered by FRPSPDIS. Line distance protection REL670 2.2 IEC Application manual...
Page 329
0.5*RFPP 0.5*RFPP 0.5*RFPP 0.5*RFPP 0 × RFRvPP R1PP= tan 70° en08000249.vsd IEC08000249 V1 EN-US Figure 164: Relation between measuring zone and FRPSPDIS characteristic for phase-to-phase fault for φline>70° (setting parameters in italic) Line distance protection REL670 2.2 IEC Application manual...
The resistive boundary RLdRv for load encroachment characteristic in reverse direction can be calculated in the same way as RLdFw, but use maximum Line distance protection REL670 2.2 IEC Application manual...
The heavy load transfer that is common in many transmission networks may in some cases be in opposite to the wanted fault resistance coverage. Therefore, the function has a built in algorithm for load encroachment, which gives the possibility Line distance protection REL670 2.2 IEC Application manual...
With reference to figure 166, the following equations for the setting calculations can be obtained. Index PHS in images and equations reference settings for Phase selection with load encroachment function FDPSPDIS and index Zm reference settings for Distance protection function (ZMQPDIS). Line distance protection REL670 2.2 IEC Application manual...
Page 333
Relation between distance protection phase selection (FDPSPDIS) and impedance zone (ZMQPDIS) for phase-to-earth fault φloop>60° (setting parameters in italic) 1 FDPSPDIS (phase selection)(red line) 2 ZMQPDIS (Impedance protection zone) RFltRevPG +XN)/tan(60°) RFltFwdPG RFPG 8 φloop Line distance protection REL670 2.2 IEC Application manual...
Page 334
FDPSPDIS characteristic shall cut off some part of the zone measurement characteristic. Phase-to-earth fault in reverse direction M13142-151 v4 Reactive reach M13142-153 v2 The reactive reach in reverse direction is the same as for forward so no additional setting is required. Line distance protection REL670 2.2 IEC Application manual...
Page 335
FDPSPDIS characteristic angle is changed from 60 degrees to 90 degrees (rotated 30° anti-clock wise). Line distance protection REL670 2.2 IEC Application manual...
The resistive boundary RLdRv for load encroachment characteristic in reverse direction can be calculated in the same way as RLdFw, but use maximum importing power that might occur instead of maximum exporting power and the relevant Umin voltage for this condition. Line distance protection REL670 2.2 IEC Application manual...
Some hints with respect to distance protection are highlighted below. Solidly earthed networks GUID-6B0F02F4-18ED-415E-8D48-0A1648F7CE00 v2 In solidly earthed systems, the transformer neutrals are connected directly to earth without any impedance between the transformer neutral and earth. Line distance protection REL670 2.2 IEC Application manual...
Page 339
GUID-39CAF169-315E-4E3E-9EE6-28CBF624B90E v5 A network is defined as effectively earthed if the earth-fault factor f is less than 1.4. The earth-fault factor is defined according to equation 287. (Equation 287) EQUATION1268 V4 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 340
The zero sequence voltage (3U ) will have the same magnitude in different places in the network due to low voltage drop distribution. The magnitude of the total fault current can be calculated according to equation290. Line distance protection REL670 2.2 IEC Application manual...
Page 341
For cross-country faults and when using phase preference, it is necessary to make sure that the distance protection is operating in the phase-to- earth loops independently, whenever possible. See guidelines for setting INReleasePE. Line distance protection REL670 2.2 IEC Application manual...
To handle this phenomenon, the IED has an adaptive built-in algorithm, which compensates the overreach tendency of zone 1 at the exporting end. No settings are required for this feature. Line distance protection REL670 2.2 IEC Application manual...
The possibility of different setting values that influence the earth-return compensation for different distance zones within the same group of setting parameters. • Different groups of setting parameters for different operating conditions of a protected multi circuit line. Line distance protection REL670 2.2 IEC Application manual...
Page 346
Z< Z< IEC09000250_1_en.vsd IEC09000250 V1 EN-US Figure 173: Class 1, parallel line in service The equivalent circuit of the lines can be simplified, see figure 174. Line distance protection REL670 2.2 IEC Application manual...
Page 347
A to B on the parallel line for the case when the fault current infeed from remote line end is zero, the voltage U in the faulty phase at A side as in equation 297. = ⋅ p ZI ⋅ ⋅ (Equation 297) IECEQUATION1278 V2 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 348
Parallel line out of service and earthed GUID-574F8EE5-EAEC-40B8-A615-FDAD2808CD6D v1 GUID-8EB3A8EF-119D-4530-8F01-0879A7478E1F v1 Z< Z< IEC09000251_1_en.vsd IEC09000251 V1 EN-US Figure 175: The parallel line is out of service and earthed Line distance protection REL670 2.2 IEC Application manual...
(at least 10%) in the middle of the protected circuit. 8.12.2.7 Tapped line application GUID-740E8C46-45EE-4CE8-8718-9FAE658E9FCE v1 GUID-7AA566A4-B6E9-41A7-9927-4DAB50BE8D1A v1 IEC09000160-3-en.vsd IEC09000160 V3 EN-US Figure 179: Example of tapped line with Auto transformer Line distance protection REL670 2.2 IEC Application manual...
Page 352
1 settings, that is, without selectivity conflicts. Careful fault calculations are necessary to determine suitable settings and selection of proper scheme communication. Line distance protection REL670 2.2 IEC Application manual...
5-10% of the total line impedance. • The effect of a load transfer between the IEDs of the protected fault resistance is considerable, the effect must be recognized. • Zero-sequence mutual coupling from parallel lines. Line distance protection REL670 2.2 IEC Application manual...
If a fault occurs at point F see figure 180, the IED at point A senses the impedance: ⋅ ⋅ ⋅ ⋅ (Equation 312) EQUATION302 V5 EN-US Line distance protection REL670 2.2 IEC Application manual...
GUID-8A62367C-2636-4EC1-90FF-397A51F586F7 v1 With reference to section "Parallel line applications", the zone reach can be set to 85% of the protected line. However, influence of mutual impedance has to be taken into account. Line distance protection REL670 2.2 IEC Application manual...
Page 356
Set the values of the corresponding zone (zero-sequence resistance and reactance) equal to: Line distance protection REL670 2.2 IEC Application manual...
See figure In this context, the main examples of normal operation are reactive load from reactive power compensation equipment or the capacitive charging of a long high-voltage power line. XLd needs Line distance protection REL670 2.2 IEC Application manual...
As a safety margin, it is required to avoid load encroachment under three-phase conditions. To guarantee correct, healthy phase IED operation under combined heavy three-phase load and earth faults, [2] RLdRv=RLdRvFactor*RLdFw [3] RLdRv=RLdRvFactor*RLdFw Line distance protection REL670 2.2 IEC Application manual...
Page 359
ZMRPSB is activated in the IED. Use an additional safety margin of approximately 20% in cases when a ZMRPSB function is activated in the IED, refer to the description of Power swing detection function ZMRPSB. Line distance protection REL670 2.2 IEC Application manual...
Should one phase of a parallel circuit open a single pole, even though there is no fault, and the load current of that phase increase, there is actually no way of distinguish this from a real fault with similar characteristics. Should this [4] RLdRv=RLdRvFactor*RLdFw Line distance protection REL670 2.2 IEC Application manual...
Z1, Z2 and ZRV is fixed). The options are Non-directional, Forward or Reverse. The result from respective set value is illustrated in figure182, where the positive impedance corresponds to the direction out on the protected line. Line distance protection REL670 2.2 IEC Application manual...
Page 362
TimerModeZx, ZoneLinkStart and TimerLinksZx The logic for the linking of the timer settings can be described with a module diagram. The figure shows only the case when TimerModeZx is selected to Ph- Ph and Ph-E. Line distance protection REL670 2.2 IEC Application manual...
Page 363
CVTs with power electronic damping devices, or if the type cannot be identified at all. None This option should be selected if the voltage transformer is fully magnetic. (Magnetic) INReleasePE Line distance protection REL670 2.2 IEC Application manual...
ENUMERATED (normal, high, low, high-high and low-low) in ZMFPDIS.ZMMMXU. ZLimHys Hysteresis value in % of range (ZMax-ZMin), common for all limits. It is used to avoid the frequent update of the value for the attribute “range”. Line distance protection REL670 2.2 IEC Application manual...
Some hints with respect to distance protection are highlighted below. Solidly earthed networks GUID-6870F6A8-EB28-47CF-AF26-7CE758BF934E v1 In solidly earthed systems, the transformer neutrals are connected directly to earth without any impedance between the transformer neutral and earth. Line distance protection REL670 2.2 IEC Application manual...
Page 366
Effectively earthed networks GUID-613296E6-A612-4B8B-9F23-311D07CFDB0E v2 A network is defined as effectively earthed if the earth-fault factor f is less than 1.4. The earth-fault factor is defined according to equation 335: Line distance protection REL670 2.2 IEC Application manual...
Page 367
For this reason a separate high sensitive earth-fault protection is necessary to carry out the fault clearance for single phase- to-earth fault. Line distance protection REL670 2.2 IEC Application manual...
To handle this phenomenon, the IED has an adaptive built-in algorithm, which compensates the overreach tendency of zone 1 at the exporting end and reduces the underreach at the importing end. No settings are required for this function. Line distance protection REL670 2.2 IEC Application manual...
The different network configuration classes are: Parallel line with common positive and zero sequence network Parallel circuits with common positive but separated zero sequence network Parallel circuits with positive and zero sequence sources separated. [6] RLdRv=RLdRvFactor*RLdFw. Line distance protection REL670 2.2 IEC Application manual...
Page 372
From symmetrical components, we can derive the impedance Z at the relay point for normal lines without mutual coupling according to equation 340. − ⋅ ⋅ ⋅ (Equation 340) IECEQUATION1275 V2 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 373
A side as: æ ö × ç ÷ × I ph è ø (Equation 342) EQUATION1277 V3 EN-US Where: = Z0m/(3 · Z1L) Line distance protection REL670 2.2 IEC Application manual...
Page 374
The zero sequence mutual coupling can reduce the reach of distance protection on the protected circuit when the parallel line is in normal operation. The reduction of the reach is most pronounced with no current infeed in the IED closest to the fault. Line distance protection REL670 2.2 IEC Application manual...
Page 375
All expressions below are proposed for practical use. They assume the value of zero sequence, mutual resistance R equals to zero. They consider only the zero sequence, mutual reactance X . Calculate the equivalent X and R zero Line distance protection REL670 2.2 IEC Application manual...
Page 376
IEC09000255_1_en.vsd IEC09000255 V1 EN-US Figure 193: Equivalent zero-sequence impedance circuit for a double-circuit line with one circuit disconnected and not earthed The reduction of the reach is equal to equation 350. Line distance protection REL670 2.2 IEC Application manual...
EQUATION1288 V2 EN-US Ensure that the underreaching zones from both line ends will overlap a sufficient amount (at least 10%) in the middle of the protected circuit. 8.13.2.7 Tapped line application GUID-4DFD6015-E97C-4F7E-84CA-C7CD2438C55A v1 Line distance protection REL670 2.2 IEC Application manual...
Page 378
U2 (it is assumed that current and voltage distance function is taken from U2 side of the transformer). is the line impedance from the T point to the fault (F). is transformer impedance. Line distance protection REL670 2.2 IEC Application manual...
Series compensation in power systems GUID-7F3BBF91-4A17-4B31-9828-F2757672C440 v2 The main purpose of series compensation in power systems is virtual reduction of line reactance in order to enhance the power system stability and increase Line distance protection REL670 2.2 IEC Application manual...
358. The effect of series compensation is in this particular case obvious and self explanatory. Line (Equation 358) EQUATION1895 V1 EN-US A typical 500 km long 500 kV line is considered with source impedance (Equation 359) EQUATION1896 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
The effect on the power transfer when considering a constant angle difference (δ) between the line ends is illustrated in figure 198. Practical compensation degree runs from 20 to 70 percent. Transmission capability increases of more than two times can be obtained in practice. Line distance protection REL670 2.2 IEC Application manual...
The resulting voltage U in IED point is this way proportional to sum of voltage drops on partial impedances between the IED point and the fault position F, as presented by Line distance protection REL670 2.2 IEC Application manual...
Page 383
Voltage U in IED point will lag the fault current I in case when: < < (Equation 362) EQUATION1902 V1 EN-US Where is the source impedance behind the IED Line distance protection REL670 2.2 IEC Application manual...
Page 384
202. The resultant reactance is in this case of inductive nature and the fault currents lags source voltage by 90 electrical degrees. Line distance protection REL670 2.2 IEC Application manual...
Page 385
Current inversion in zero sequence systems with low zero sequence source impedance (a number of power transformers connected in parallel) must be considered as practical possibility in many modern networks. Line distance protection REL670 2.2 IEC Application manual...
Page 386
It is for this reason absolutely necessary to study the possible effect on operation of zero sequence directional earth-fault overcurrent protection before its installation. Line distance protection REL670 2.2 IEC Application manual...
Page 387
LOC = 50% LOC = 33%, 66% LOC = 100% en06000613.vsd IEC06000613 V1 EN-US Figure 205: Apparent impedances seen by distance IED for different SC locations and spark gaps used for overvoltage protection Line distance protection REL670 2.2 IEC Application manual...
Page 388
Extensive studies at Bonneville Power Administration in USA ( ref. Goldsworthy, D,L “A Linearized Model for MOV-Protected series capacitors” Paper 86SM357– 8 IEEE/PES summer meeting in Mexico City July 1986) have resulted in Line distance protection REL670 2.2 IEC Application manual...
Page 389
• Series capacitor becomes nearly completely bridged by MOV when the line current becomes higher than 10-times the protective current level (I £ 10· k · Line distance protection REL670 2.2 IEC Application manual...
D bus and the fault becomes equal to zero, if the capacitor is installed near the bus and the fault appears just behind the capacitor. This may cause the phenomenon of voltage inversion to be expanded very deep Line distance protection REL670 2.2 IEC Application manual...
This makes it necessary to install distance protection in combination with telecommunication. The most common is distance protection in Permissive Overreaching Transfer Trip mode (POTT). Line distance protection REL670 2.2 IEC Application manual...
If the capacitor is out of service or bypassed, the reach with these settings can be less than 50% of protected line dependent on compensation degree and there will be a section, G in figure 209, of the power line where no tripping occurs from either end. Line distance protection REL670 2.2 IEC Application manual...
Page 393
Distance protections of adjacent power lines shown in figure are influenced by this negative impedance. If the intermediate infeed of short circuit power by other lines is taken into consideration, the negative voltage drop on X is amplified and a Line distance protection REL670 2.2 IEC Application manual...
Page 394
In such case the reactance of a short adjacent line may be lower than the capacitor reactance and voltage inversion phenomenon may occur also on remote end of Line distance protection REL670 2.2 IEC Application manual...
Page 395
The operating area for negative impedance depends upon the magnitude of the source impedance and calculations must be made on a case by Line distance protection REL670 2.2 IEC Application manual...
Page 396
The current reversal phenomenon also raises problems from the protection point of view, particularly when the power lines are short and when permissive overreach schemes are used. m0AC m0CB en06000627.vsd IEC06000627 V1 EN-US Figure 215: Double circuit, parallel operating line Line distance protection REL670 2.2 IEC Application manual...
Page 397
IED RAB and especially telecommunication equipment, trip its related circuit breaker, since all conditions for POTT have been fulfilled. Zero sequence mutual impedance will additionally influence this process, Line distance protection REL670 2.2 IEC Application manual...
Inaccuracies in the line zero-sequence impedance data, and their effect on the calculated value of the earth-return compensation factor. • The effect of infeed between the IED and the fault location, including the influence of different Z ratios of the various sources. Line distance protection REL670 2.2 IEC Application manual...
The zone 2 must not be reduced below 120% of the protected line section. The whole line must be covered under all conditions. Line distance protection REL670 2.2 IEC Application manual...
In many applications it might be necessary to consider the enlarging factor due to the fault current infeed from adjacent lines in the reverse direction in order to obtain certain sensitivity. Line distance protection REL670 2.2 IEC Application manual...
Figure 219: Reduced reach due to the expected sub-harmonic oscillations at different degrees of compensation æ ö c degree of compensation ç ÷ ç ÷ è ø (Equation 381) EQUATION1894 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 402
Different settings of the reach for the ph-ph faults and ph-E loops makes it possible to minimise the necessary decrease of the reach for different types of faults. Line distance protection REL670 2.2 IEC Application manual...
Page 403
When the calculation of X1Fwgives a negative value the zone 1 must be permanently blocked. For protection on non compensated lines facing series capacitor on next line. The setting is thus: • X1Fw is set to (XLine-XC · K) · p/100. Line distance protection REL670 2.2 IEC Application manual...
Page 404
Settings of the resistive reaches are limited according to the minimum load impedance. Line distance protection REL670 2.2 IEC Application manual...
(Equation 383) EQUATION554 V1 EN-US Check the reduction of a reach for the overreaching zones due to the effect of the zero sequence mutual coupling. The reach is reduced for a factor: Line distance protection REL670 2.2 IEC Application manual...
The final reach in resistive direction for phase-to-earth fault loop measurement automatically follows the values of the line-positive and zero-sequence resistance, and at the end of the protected zone is equal to equation 389. Line distance protection REL670 2.2 IEC Application manual...
Check the maximum permissible resistive reach for any zone to ensure that there is a sufficient setting margin between the boundary and the minimum load impedance. The minimum load impedance (Ω/phase) is calculated as: [7] RLdRv=RLdRvFactor*RLdFw. [8] RLdRv=RLdRvFactor*RLdFw. Line distance protection REL670 2.2 IEC Application manual...
Page 408
To avoid load encroachment for the phase-to-phase measuring elements, the set resistive reach of any distance protection zone must be less than 160% of the minimum load impedance. Line distance protection REL670 2.2 IEC Application manual...
For symmetrical load or three-phase and phase-to-phase faults, this corresponds to the per-phase, or positive-sequence, impedance. For a phase-to-earth fault, it corresponds to the per-loop impedance, including the earth return impedance. [9] RLdRv=RLdRvFactor*RLdFw Line distance protection REL670 2.2 IEC Application manual...
ILmLn is the RMS value of the vector difference between phase currents Lm and Both current limits IMinOpPEZx and IMinOpPPZx are automatically reduced to 75% of regular set values if the zone is set to operate in reverse direction, that is, OperationDir=Reverse. Line distance protection REL670 2.2 IEC Application manual...
Page 411
Refer to chapter Simplified logic schemes in Technical Manual for the application of these settings. OperationSC Choose the setting value SeriesComp if the protected line or adjacent lines are compensated with series capacitors. Otherwise maintain the NoSeriesComp setting value. CVTtype Line distance protection REL670 2.2 IEC Application manual...
As the rotating masses strive to find a stable operate condition, they oscillate with damped oscillations until they reach the final stability. Line distance protection REL670 2.2 IEC Application manual...
Rated secondary voltage of voltage (or potential) transformers 0.11 used EQUATION1325 V1 EN-US Rated primary current of current transformers used 1200 EQUATION1326 V1 EN-US Rated secondary current of current transformers used EQUATION1327 V1 EN-US Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 416
The calculated value of the system impedance is of informative nature and helps in determining the position of the oscillation center, see figure 225, which is for a general case calculated according to equation 405. Line distance protection REL670 2.2 IEC Application manual...
Page 417
EQUATION1340 V1 EN-US In particular cases, when (Equation 406) EQUATION1342 V1 EN-US The center of oscillation resides on the impedance point according to equation 407. 7.43 33.9 (Equation 407) EQUATION1341 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 418
400 kV: • = 0.9 for lines longer than 150 km • = 0.85 for lines between 80 and 150 km • = 0.8 for lines shorter than 80 km Line distance protection REL670 2.2 IEC Application manual...
Page 419
Since it is not possible to further increase the external load angle δ , it is necessary to reduce the inner boundary of the oscillation detection characteristic. The minimum required value is calculated according to the procedure listed in equation 413, 414, and 416. Line distance protection REL670 2.2 IEC Application manual...
Page 420
FRPSPDIS) to the value equal to or less than the calculated value RLdInFw. It is at the same time necessary to adjust the load angle in FDPSPDIS or FRPSPDIS to follow the condition presented in equation 418. Line distance protection REL670 2.2 IEC Application manual...
Page 421
The tR2 inhibit timer disables the output START signal from ZMRPSB function, if the measured impedance remains within ZMRPSB operating area for a time longer than the set tR2 value. This time delay was usually set to approximately two seconds in older power-swing devices. Line distance protection REL670 2.2 IEC Application manual...
1 operating characteristic and causes its unwanted operation, if no preventive measures have been taken, see figure 227. Line distance protection REL670 2.2 IEC Application manual...
Page 423
ZMRPSB operating characteristic IEC99000181_2_en.vsd IEC99000181 V2 EN-US Figure 227: Impedance trajectory within the distance protection zones 1 and 2 during and after the fault on line B – D Line distance protection REL670 2.2 IEC Application manual...
3) is in many cases not blocked by the power swing detection elements. This allows in such cases the distance protection zone 3 (together with the full-scheme design of the distance protection function) to be used at the same time as the overreaching power-swing zone. Line distance protection REL670 2.2 IEC Application manual...
Page 425
Connect the CACC functional input to start output signal of the local overreaching power swing distance protection zone, which serves as a local criteria at receiving of carrier signal during the power swing cycle. Line distance protection REL670 2.2 IEC Application manual...
Page 426
(swing) frequency in smin Calculate the maximum permissible resistive reach for each power swing zone separately according to the following equations. × × RFPP v tnPP (Equation 422) EQUATION1538 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 427
O/C EF protection to eliminate the initial fault and still make possible for the power swing zones to operate for possible consecutive faults. A time delay between 150 and 300 ms is generally sufficient. Line distance protection REL670 2.2 IEC Application manual...
(usually zone 2). Configure for this reason the functional output signal STZMURPS to the start output of the overreaching distance protection zone (usually START of distance protection zone 2). Line distance protection REL670 2.2 IEC Application manual...
The situation with pole slip of a generator can be caused by different reasons. A short circuit occurs in the external power grid, close to the generator. If the fault clearance time is too long, the generator will accelerate so much, so the Line distance protection REL670 2.2 IEC Application manual...
Page 430
This split can be made at predefined locations (trip of predefined lines) after function from pole slip protection (PSPPPAM) in the line protection IED. Line distance protection REL670 2.2 IEC Application manual...
Page 431
The consequence can be damages on insulation and stator/rotor iron. • At asynchronous operation the generator will absorb a significant amount of reactive power, thus risking overload of the windings. Line distance protection REL670 2.2 IEC Application manual...
MeasureMode. The setting possibilities are: PosSeq, L1-L2, L2- L3, or L3-L1. If all phase voltages and phase currents are fed to the IED the PosSeq alternative is recommended (default). Further settings can be illustrated in figure 232. Line distance protection REL670 2.2 IEC Application manual...
Page 433
The ImpedanceZB is the reverse impedance as show in figure 232. ZB should be equal to the generator transient reactance X'd. The impedance is given in % of the base impedance, see equation 425. Line distance protection REL670 2.2 IEC Application manual...
Figure 233: Line application of pole slip protection If the apparent impedance crosses the impedance line ZB – ZA this is the detection criterion of out of step conditions, see figure 234. Line distance protection REL670 2.2 IEC Application manual...
Page 435
With all phase voltages and phase currents available and fed to the protection IED, it is recommended to set the MeasureMode to positive sequence. The impedance settings are set in pu with ZBase as reference: Line distance protection REL670 2.2 IEC Application manual...
Page 436
The warning angle (StartAngle) should be chosen not to cross into normal operating area. The maximum line power is assumed to be 2000 MVA. This corresponds to apparent impedance: 2000 (Equation 432) EQUATION1967 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 437
Normally the N1Limit is set to 1 so that the line will be tripped at the first pole slip. If the line shall be tripped at all pole slip situations also the parameter N2Limit is set to 1. In other cases a larger number is recommended. Line distance protection REL670 2.2 IEC Application manual...
Figure 236: Generator application of pole slip protection If the apparent impedance crosses the impedance line ZB – ZA this is the detected criterion of out of step conditions, see figure 237. Line distance protection REL670 2.2 IEC Application manual...
Page 439
Use the following generator data: UBase : 20 kV SBase set to 200 MVA ': 25% Use the following block transformer data: UBase : 20 kV (low voltage side) SBase set to 200 MVA : 15% Line distance protection REL670 2.2 IEC Application manual...
Page 440
Ð ° 0.25 0.25 90 (Equation 438) EQUATION1973 V1 EN-US Set ZB to 0.25 × 0.15 (Equation 439) EQUATION1974 V1 EN-US This corresponds to: Ð 0.15 0.15 90 (Equation 440) EQUATION1975 V2 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 441
EQUATION1977 V2 EN-US In case of minor damped oscillations at normal operation we do not want the protection to start. Therefore we set the start angle with large margin. Set StartAngle to 110°. Line distance protection REL670 2.2 IEC Application manual...
This is often shown in a simplified way as two equivalent generators connected to each other via an equivalent transmission line and the phase difference between the equivalent generators is 180 electrical degrees. Line distance protection REL670 2.2 IEC Application manual...
Page 443
The out-of-step condition of a generator can be caused by different reasons. Sudden events in an electrical power system such as large changes in load, fault occurrence or slow fault clearance, can cause power oscillations, that are called power swings. Line distance protection REL670 2.2 IEC Application manual...
Page 444
In asynchronous operation there is induction of currents in parts of the generator normally not carrying current, thus resulting in increased heating. The consequence can be damages on insulation and iron core of both rotor and stator. Line distance protection REL670 2.2 IEC Application manual...
ForwardX = 0.565/0.9522 · 100 = 59.33 in % ZBase; ReverseX = 0.282/0.9522 · 100 = 29.6 in % ZBase (all referred to 13.8 kV) resulted ForwardR = 0.078/0.9522 · 100 = 8.19 in % ZBase; ReverseR = 0.003/0.9522 · 100 = 0.29 in % ZBase (all referred to 13.8 kV) settings Line distance protection REL670 2.2 IEC Application manual...
Page 446
11.32 % of the total ForwardX, the setting ReachZ1 should be set to ReachZ1 = 12 %. This means that the generator – step-up transformer unit would be in the zone 1. In other words, if the centre of Line distance protection REL670 2.2 IEC Application manual...
Page 447
2 can be the same as in zone 1. Recommended value: NoOfSlipsZ2 = 2 or 3. • Operation: With the setting Operation OOSPPAM function can be set On/Off. Line distance protection REL670 2.2 IEC Application manual...
(LV-side) then inversion is not necessary (InvertCTCurr = Off), provided that the CT’s star point earthing complies with ABB recommendations, as it is shown in Table 32. If the currents fed to the Out-of-step protection are measured on the protected generator terminals side, then invertion is necessary (InvertCTCurr = On), provided that the CT’s star...
IPh< is used to set the current level for the detection of a dead line. IPh< is, by default, set to 20% of IBase. It shall be set with a sufficient margin (15–20%) below the minimum expected load current. In many cases, the minimum load Line distance protection REL670 2.2 IEC Application manual...
Page 450
The selection of the Impedance mode gives increased security. When Mode is set to UILvl&Imp, the condition for tripping is an ORed between UILevel and Impedance. Line distance protection REL670 2.2 IEC Application manual...
Figure shows an occurring cross-country fault. Figure shows the achievement of line voltage on healthy phases and an occurring cross-country fault. Line distance protection REL670 2.2 IEC Application manual...
Page 452
243. The integer from the phase selection function, which gives the type of fault undergoes a check and will release the distance protection zones as decided by the logic. The logic includes a check of the fault loops given by the phase selection Line distance protection REL670 2.2 IEC Application manual...
Page 453
It is limited by the impedance to below the typical, say 25 to 40 A. Occurring neutral current is thus a sign of a cross-country fault (a double earth- fault) Line distance protection REL670 2.2 IEC Application manual...
Normally in a high impedance earthed system, the voltage drop is big and the setting can typically be set to 70% of base voltage (UBase) Line distance protection REL670 2.2 IEC Application manual...
High speed distance protection ZMFPDIS. The application is for resonance (Petersen coil) or high resistive earthed systems where phase preference based tripping is required for so-called cross-country faults, two simultaneous single phase-to-earth-faults in different phases and on different line sections. Line distance protection REL670 2.2 IEC Application manual...
Page 456
Figure shows a typical cross-country fault situation. Figure shows phase voltage relations before and during a single phase-to-earth fault. Load Load en06000550.vsd IEC06000550 V1 EN-US Figure 245: A typical cross-country fault situation Line distance protection REL670 2.2 IEC Application manual...
Page 457
This residual current may be used as an indication of a cross-country fault. IL3=IN IL1=IN en06000553.vsd IEC06000553 V1 EN-US Figure 247: The currents in the phases at a double earth fault Line distance protection REL670 2.2 IEC Application manual...
Page 458
AND condition with the corresponding signals of the phase selection, loop by loop. In other words, the phase selection inside the distance protection has to detect the fault as well before a trip from the distance zones can be achieved. Line distance protection REL670 2.2 IEC Application manual...
3U0>: The setting of the residual voltage level (neutral voltage) which is used by the evaluation logic to verify that an earth-fault exists. The setting can typically be 20% of base voltage (UBase). Line distance protection REL670 2.2 IEC Application manual...
Page 460
In the High speed distance protection ZMFPDIS, setting INReleasePE needs to be set lower than the expected residual current during a cross-country fault. Otherwise the distance protection might operate in the phase-to-phase loops which will bypass the Phase preference logic. Line distance protection REL670 2.2 IEC Application manual...
(and relay) point, for which very high fault currents are characteristic. The instantaneous phase overcurrent protection PHPIOC can operate in 10 ms for faults characterized by very high currents. Line distance protection REL670 2.2 IEC Application manual...
The following fault calculations have to be done for three-phase, single-phase-to- earth and two-phase-to-earth faults. With reference to Figure 249, apply a fault in B and then calculate the current through-fault phase current I . The calculation Line distance protection REL670 2.2 IEC Application manual...
Page 463
5% for the maximum possible transient overreach have to be introduced. An additional 20% is suggested due to the inaccuracy of the instrument transformers under transient conditions and inaccuracy in the system data. Line distance protection REL670 2.2 IEC Application manual...
A fault in C has to be applied, and then the maximum current seen from the IED ) on the healthy line (this applies for single-phase-to-earth and two-phase-to- earth faults) is calculated. Line distance protection REL670 2.2 IEC Application manual...
Page 465
The IED setting value IP>> is given in percentage of the primary base current value, IBase. The value for IP>> is given from this formula: >>= × IBase (Equation 448) EQUATION1147 V3 EN-US Line distance protection REL670 2.2 IEC Application manual...
The selectivity between different overcurrent protections is normally enabled by co-ordination between the function time delays of the different protections. To enable optimal co-ordination between all overcurrent Line distance protection REL670 2.2 IEC Application manual...
The parameters for the directional phase overcurrent protection, four steps OC4PTOC are set via the local HMI or PCM600. The following settings can be done for OC4PTOC. Line distance protection REL670 2.2 IEC Application manual...
Page 468
7% of IB. 2ndHarmStab: Operate level of 2nd harmonic current restrain set in % of the fundamental current. The setting range is 5 - 100% in steps of 1%. The default setting is 20%. Line distance protection REL670 2.2 IEC Application manual...
DirModex: The directional mode of step x. Possible settings are Off/Non- directional/Forward/Reverse. Characteristx: Selection of time characteristic for step x. Definite time delay and different types of inverse time characteristics are available according to Table 33. Line distance protection REL670 2.2 IEC Application manual...
Page 470
ANSI reset characteristic according to standard. If IMinx is set above Ix> for any step the ANSI reset works as if current is zero when current drops below IMinx. Line distance protection REL670 2.2 IEC Application manual...
Page 471
The delay characteristics are described in Technical manual. There are some restrictions regarding the choice of the reset delay. For the definite time delay characteristics, the possible delay time setting instantaneous (1) and IEC (2 = set constant time reset). Line distance protection REL670 2.2 IEC Application manual...
The protection reset current must also be considered so that a short peak of overcurrent does not cause the operation of a protection even when the overcurrent has ceased. This phenomenon is described in Figure 255. Line distance protection REL670 2.2 IEC Application manual...
Page 473
The maximum load current on the line has to be estimated. There is also a demand that all faults within the zone that the protection shall cover must be detected by the phase overcurrent protection. The minimum fault current Iscmin to be detected by Line distance protection REL670 2.2 IEC Application manual...
Page 474
This is mostly used in the case of inverse time overcurrent protection. Figure shows how the time-versus-current curves are plotted in a diagram. The time setting is chosen to get the shortest fault time with maintained selectivity. Line distance protection REL670 2.2 IEC Application manual...
Page 475
These time delays can vary significantly between different protective equipment. The following time delays can be estimated: Protection operation 15-60 ms time: Protection resetting time: 15-60 ms Breaker opening time: 20-120 ms Line distance protection REL670 2.2 IEC Application manual...
Page 476
There are uncertainties in the values of protection operation time, breaker opening time and protection resetting time. Therefore a safety margin has to be included. With normal values the needed time difference can be calculated according to Equation 454. Line distance protection REL670 2.2 IEC Application manual...
Some guidelines for the choice of setting parameter for EFPIOC is given. M12762-6 v8 Common base IED values for primary current (IBase), primary voltage (UBase) and primary power (SBase) are set in the global base values for settings function GBASVAL. Line distance protection REL670 2.2 IEC Application manual...
Page 478
The function shall not operate for any of the calculated currents to the protection. The minimum theoretical current setting (Imin) will be: in MAX I (Equation 455) EQUATION284 V2 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 479
= 1.3 × I (Equation 458) EQUATION288 V3 EN-US The IED setting value IN>> is given in percent of the primary base current value, IBase. The value for IN>> is given by the formula: Line distance protection REL670 2.2 IEC Application manual...
51N_67N 4(IN>) protection, four steps TEF-REVA V2 EN-US 9.4.2 Application M12509-12 v10 The directional residual overcurrent protection, four steps EF4PTOC is used in several applications in the power system. Some applications are: Line distance protection REL670 2.2 IEC Application manual...
Page 481
Curve name ANSI Extremely Inverse ANSI Very Inverse ANSI Normal Inverse ANSI Moderately Inverse ANSI/IEEE Definite time ANSI Long Time Extremely Inverse ANSI Long Time Very Inverse Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Thus, if only the inverse time delay is required, it is important to set the definite time delay for that stage to zero. Line distance protection REL670 2.2 IEC Application manual...
IEC05000135-5-en.vsdx IEC05000135 V5 EN-US Figure 261: Relay characteristic angle given in degree In a normal transmission network a normal value of RCA is about 65°. The setting range is -180° to +180°. Line distance protection REL670 2.2 IEC Application manual...
This will give a declining residual current in the network, as the inrush current is deviating between the phases. There is a risk that the residual overcurrent function will give an unwanted trip. The inrush current has a relatively large ratio of 2nd Line distance protection REL670 2.2 IEC Application manual...
Also the same current setting as this step is chosen for the blocking at parallel transformer energizing. The settings for the parallel transformer logic are described below. BlkParTransf: This is used to On blocking at energising of parallel transformers. Line distance protection REL670 2.2 IEC Application manual...
The function can be activated by Circuit breaker position (change) or Circuit breaker command. tUnderTime: Time delay for operation of the sensitive undertime function. The setting range is 0.000 - 60.000 s in step of 0.001 s. The default setting is 0.300 s Line distance protection REL670 2.2 IEC Application manual...
IMinx: Minimum operate current for step x in % of IB. Set IMinx below INx> for every step to achieve ANSI reset characteristic according to standard. If IMinx is set above INx> for any step, signal will reset at current equals to zero. Line distance protection REL670 2.2 IEC Application manual...
Page 488
HarmBlockx: This is used to enable block of step x from 2 harmonic restrain function. tPCrvx, tACrvx, tBCrvx, tCCrvx: Parameters for user programmable of inverse time characteristic curve. The time characteristic equation is according to equation 460: Line distance protection REL670 2.2 IEC Application manual...
The polarizing voltage and current can be internally generated when a three-phase set of voltage transformers and current transformers are used. IN> IEC05000149-2-en.vsdx IEC05000149 V2 EN-US Figure 264: Connection of polarizing voltage from an open delta Line distance protection REL670 2.2 IEC Application manual...
Page 490
As a consequence of the distribution of zero sequence current in the power system, the current to the protection might be larger if one line out from the remote busbar is taken out of service, see Figure 266. Line distance protection REL670 2.2 IEC Application manual...
Page 491
IEC05000152 V2 EN-US Figure 267: Step 1, third calculation In this case the residual current out on the line can be larger than in the case of earth fault on the remote busbar. Line distance protection REL670 2.2 IEC Application manual...
Page 492
To assure selectivity the current setting must be chosen so that step 2 does not operate at step 2 for faults on the next line from the remote substation. Consider a fault as shown in Figure 269. Line distance protection REL670 2.2 IEC Application manual...
Page 493
IEC05000156 V3 EN-US Figure 270: Step 3, Selectivity calculation ³ × × step3 step2 (Equation 466) EQUATION1204 V4 EN-US where: is the chosen current setting for step 2 on the faulted line. step2 Line distance protection REL670 2.2 IEC Application manual...
Four step negative sequence NS4PTOC 46I2 overcurrent protection IEC10000053 V1 EN-US 9.5.2 Application GUID-343023F8-AFE3-41C2-8440-1779DD7F5621 v2 Four step negative sequence overcurrent protection NS4PTOC is used in several applications in the power system. Some applications are: Line distance protection REL670 2.2 IEC Application manual...
Page 495
Table 36: Inverse time characteristics Curve name ANSI Extremely Inverse ANSI Very Inverse ANSI Normal Inverse ANSI Moderately Inverse ANSI/IEEE Definite time ANSI Long Time Extremely Inverse Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
GlobalBaseSel: Selects the global base value group used by the function to define IBase, UBase and SBase as applicable. GUID-F7AA2194-4D1C-4475-8853-C7D064912614 v4 When inverse time overcurrent characteristic is selected, the operate time of the stage will be the sum of the inverse time delay Line distance protection REL670 2.2 IEC Application manual...
IEC Definite Time User Programmable ASEA RI RXIDG (logarithmic) The different characteristics are described in the Technical Reference Manual (TRM). Ix>: Operation negative sequence current level for step x given in % of IBase. Line distance protection REL670 2.2 IEC Application manual...
Page 498
Curve name Instantaneous IEC Reset (constant time) ANSI Reset (inverse time) The different reset characteristics are described in the Technical Reference Manual (TRM). There are some restrictions regarding the choice of reset delay. Line distance protection REL670 2.2 IEC Application manual...
AngleRCA: Relay characteristic angle given in degrees. This angle is defined as shown in figure 272. The angle is defined positive when the residual current lags the reference voltage (Upol = -U2) Line distance protection REL670 2.2 IEC Application manual...
% of IBase. The start forward or start reverse signals can be used in a communication scheme. The appropriate signal must be configured to the communication scheme block. Sensitive directional residual overcurrent and power protection SDEPSDE SEMOD171436-1 v4 Line distance protection REL670 2.2 IEC Application manual...
When should the sensitive directional residual overcurrent protection be used and when should the sensitive directional residual power protection be used? Consider the following: Line distance protection REL670 2.2 IEC Application manual...
Line distance protection REL670 2.2 IEC Application manual...
Page 503
In a system with a neutral point resistor (resistance earthed system) the impedance can be calculated as: Line distance protection REL670 2.2 IEC Application manual...
Page 504
The series impedances in the system can no longer be neglected. The system with a single phase to earth fault can be described as in Figure 274. Line distance protection REL670 2.2 IEC Application manual...
Page 505
The residual voltages in stations A and B can be written: × T ,0 (Equation 474) EQUATION1949 V1 EN-US × 3I (Z T ,0 lineAB,0 (Equation 475) EQUATION1950 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 506
). Since the reference voltage is used as the polarizing quantity for directionality, it is important to set this parameter correctly. With the setting OpMode the principle of directional function is chosen. Line distance protection REL670 2.2 IEC Application manual...
Page 507
When OpMode is set to 3I0 and fi the function will operate if the residual current is larger than the setting INDir> and the residual current angle is within the sector RCADir ± ROADir. Line distance protection REL670 2.2 IEC Application manual...
Page 508
The characteristic angle of the directional functions RCADir is set in degrees. RCADir is normally set equal to 0° in a high impedance earthed network with a neutral point resistor as the active current component is appearing out on the Line distance protection REL670 2.2 IEC Application manual...
Page 509
TimeChar is the selection of time delay characteristic for the non-directional residual current protection. Definite time delay and different types of inverse time characteristics are available: Line distance protection REL670 2.2 IEC Application manual...
Page 510
OpUN> is set On to activate the trip function of the residual over voltage protection. tUN is the definite time delay for the trip function of the residual voltage protection, given in s. Line distance protection REL670 2.2 IEC Application manual...
If the temperature of the protected object reaches a set warning level AlarmTemp, a signal ALARM can be given to the operator. This enables actions in the power system to be taken before dangerous temperatures are reached. If the temperature Line distance protection REL670 2.2 IEC Application manual...
When the thermal overload protection trips, a lock-out signal is activated. This signal is intended to block switch in of the protected circuit as long as the conductor temperature is high. The signal is released when the estimated Line distance protection REL670 2.2 IEC Application manual...
CCRBRF are set via the local HMI or PCM600. The following settings can be done for the breaker failure protection. GlobalBaseSel: Selects the global base value group used by the function to define IBase, UBase and SBase as applicable. Line distance protection REL670 2.2 IEC Application manual...
Page 514
In most applications 1 out of 3 is sufficient. For Contact operation means back-up trip is done when circuit breaker is closed (breaker position is used). Line distance protection REL670 2.2 IEC Application manual...
Page 515
It is often required that the total fault clearance time shall be less than a given critical time. This time is often dependent of the ability to maintain transient stability in case of a fault close to a power plant. Line distance protection REL670 2.2 IEC Application manual...
Page 516
CBFLT is active. Typical setting is 2.0 seconds. tPulse: Trip pulse duration. This setting must be larger than the critical impulse time of circuit breakers to be tripped from the breaker failure protection. Typical setting is 200 ms. Line distance protection REL670 2.2 IEC Application manual...
The stub protection is only activated when the disconnector of the object is open. STBPTOCenables fast fault clearance of faults at the section between the CTs and the open disconnector. Line distance protection REL670 2.2 IEC Application manual...
This signal is normally taken from an auxiliary contact (normally closed) of the line disconnector and connected to a binary input RELEASE of the IED. With the settingContinuous the function is activated independent of presence of any external release signal. Line distance protection REL670 2.2 IEC Application manual...
Each phase current through the circuit breaker is measured. If the difference between the phase currents is larger than a CurrUnsymLevel this is an indication of pole discordance, and the protection will operate. Line distance protection REL670 2.2 IEC Application manual...
Power to the power plant auxiliaries may come from a station service transformer connected to the secondary side of the step-up transformer. Power may also come from a start-up service transformer connected to the external network. One has to Line distance protection REL670 2.2 IEC Application manual...
Page 522
Overpower protection Operate Operate Line Line Margin Margin Operating point Operating point without without turbine torque turbine torque IEC09000019-2-en.vsd IEC09000019 V2 EN-US Figure 280: Reverse power protection with underpower or overpower protection Line distance protection REL670 2.2 IEC Application manual...
With the parameter OpMode1(2) the function can be set On/Off. The function gives trip if the power component in the direction defined by the setting Angle1(2) is smaller than the set pick up power value Power1(2) Line distance protection REL670 2.2 IEC Application manual...
Page 524
The setting is given in degrees. For active power the set angle should be 0° or 180°. 0° should be used for generator low forward active power protection. Line distance protection REL670 2.2 IEC Application manual...
Page 525
Calculated is settable parameter Line distance protection REL670 2.2 IEC Application manual...
Often, the motoring condition may imply that the turbine is in a very dangerous state. The task of the reverse power protection is to protect the turbine and not to protect the generator itself. Line distance protection REL670 2.2 IEC Application manual...
Page 527
This power will be about 10% of the rated power. If there is only air in the hydro turbine, the power demand will fall to about 3%. Line distance protection REL670 2.2 IEC Application manual...
IBase, UBase and SBase as applicable. Operation: With the parameter Operation the function can be set On/Off. Mode: The voltage and current used for the power measurement. The setting possibilities are shown in table 41. Line distance protection REL670 2.2 IEC Application manual...
Page 529
With the parameter OpMode1(2) the function can be set On/Off. The function gives trip if the power component in the direction defined by the setting Angle1(2) is larger than the set pick up power value Power1(2) Line distance protection REL670 2.2 IEC Application manual...
Page 530
The setting Angle1(2) gives the characteristic angle giving maximum sensitivity of the power protection function. The setting is given in degrees. For active power the set angle should be 0° or 180°. 180° should be used for generator reverse power protection. Line distance protection REL670 2.2 IEC Application manual...
Page 531
Calculated is settable parameter Line distance protection REL670 2.2 IEC Application manual...
All settings are in primary values or percentage. Set IBase (given in GlobalBaseSel) to power line rated current or CT rated current. Set minimum operating level per phase IP> to typically 10-20% of rated current. Line distance protection REL670 2.2 IEC Application manual...
VRPVOC function module has two independent protection each consisting of: • One overcurrent step with the following built-in features: Line distance protection REL670 2.2 IEC Application manual...
The short-circuit current may drop below the generator rated current after 0.5...1 s. Also, for generators with an excitation system not fed from the generator terminals, a fault can occur when the automatic voltage Line distance protection REL670 2.2 IEC Application manual...
Technical Manual for details. tDef_OC: Definite time delay. It is used if definite time characteristic is chosen; it shall be set to 0 s if the inverse time characteristic is chosen and no additional delay Line distance protection REL670 2.2 IEC Application manual...
An example of how to use VRPVOC function to provide voltage restrained overcurrent protection for a generator is given below. Let us assume that the time coordination study gives the following required settings: Line distance protection REL670 2.2 IEC Application manual...
Set GlobalBaseSel to the right value in order to select the Global Base Values Group with UBase and IBase equal to the rated phase-to-phase voltage and the rated phase current of the generator. Set StartCurr to the value 150%. Line distance protection REL670 2.2 IEC Application manual...
Page 538
Set tDef_UV to 3.0 s. 10. Set EnBlkLowV to Off (default value) to disable the cut-off level for low- voltage of the undervoltage stage. The other parameters may be left at their default value. Line distance protection REL670 2.2 IEC Application manual...
Disconnect apparatuses, like electric motors, which will be damaged when subject to service under low voltage conditions. The function has a high measuring accuracy and a settable hysteresis to allow applications to control reactive load. Line distance protection REL670 2.2 IEC Application manual...
10.1.3.5 Backup protection for power system faults M13851-62 v3 The setting must be below the lowest occurring "normal" voltage and above the highest occurring voltage during the fault conditions under consideration. Line distance protection REL670 2.2 IEC Application manual...
When using inverse time characteristic for the undervoltage function during very low voltages can give a short operation time. This might lead to unselective tripping. By setting t1Min longer than the operation time for other protections, such unselective tripping can be avoided. Line distance protection REL670 2.2 IEC Application manual...
The same also applies to the associated equipment, its voltage and time characteristic. There are wide applications where general overvoltage functions are used. All voltage related settings are made as a percentage of a settable base primary voltage, Line distance protection REL670 2.2 IEC Application manual...
The following settings can be done for the two step overvoltage protection M13852-22 v10 ConnType: Sets whether the measurement shall be phase-to-earth fundamental value, phase-to-phase fundamental value, phase-to-earth RMS value or phase-to- phase RMS value. Line distance protection REL670 2.2 IEC Application manual...
Page 545
The speed might be important for example in case of protection of transformer that might be overexcited. The time delay must be co- ordinated with other automated actions in the system. Line distance protection REL670 2.2 IEC Application manual...
Page 546
If the function is used as control for automatic switching of reactive compensation devices the hysteresis must be set smaller than the voltage change after switching of the compensation device. Line distance protection REL670 2.2 IEC Application manual...
The time delay for ROV2PTOV is seldom critical, since residual voltage is related to earth faults in a high-impedance earthed system, and enough time must normally be given for the primary protection to clear the fault. In some more specific Line distance protection REL670 2.2 IEC Application manual...
The two healthy phases will measure full phase-to- phase voltage, as the faulty phase will be connected to earth. The residual overvoltage will be three times the phase-to-earth voltage. See figure 287. Line distance protection REL670 2.2 IEC Application manual...
The residual sum will have the same value as the remaining phase-to-earth voltage, which is shown in Figure 288. IEC07000189-2-en.vsd IEC07000189 V2 EN-US Figure 288: Earth fault in Direct earthed system Line distance protection REL670 2.2 IEC Application manual...
The setting is highly dependent on the protection application. In many applications, the protection function has the task to prevent damage to the protected object. The speed might be important, for Line distance protection REL670 2.2 IEC Application manual...
Page 551
Make sure that the set value for parameter HystABSn is somewhat smaller than the set pickup value. Otherwise there is a risk that step n will not reset properly. Line distance protection REL670 2.2 IEC Application manual...
The capability of a transformer (or generator) to withstand overexcitation can be illustrated in the form of a thermal capability curve, that is, a diagram which shows Line distance protection REL670 2.2 IEC Application manual...
Page 553
It then uses the positive sequence quantities of voltages and currents. Analog measurements shall not be taken from any winding where a load tap changer is located. Some different connection alternatives are shown in figure 289. Line distance protection REL670 2.2 IEC Application manual...
TRIP: The TRIP output is activated after the operate time for the U/f level has expired. TRIP signal is used to trip the circuit breaker(s). Line distance protection REL670 2.2 IEC Application manual...
The default value is recommended to be used if the constant is not known. tMin: The operating times at voltages higher than the set V/Hz>>. The setting shall match capabilities on these high voltages. Typical setting can be 1-10 second. Line distance protection REL670 2.2 IEC Application manual...
In this example, each step will be (140-105) /5 = 7%. The setting of time delays t1 to t6 are listed in table 42. Line distance protection REL670 2.2 IEC Application manual...
Page 557
V/Hz transformer capability curve relay operate characteristic Continous 0.05 Time (minutes) en01000377.vsd IEC01000377 V1 EN-US Figure 290: Example on overexcitation capability curve and V/Hz protection settings for power transformer Line distance protection REL670 2.2 IEC Application manual...
The function requires voltage transformers in all phases of the capacitor bank. Figure shows some different alternative connections of this function. Line distance protection REL670 2.2 IEC Application manual...
Page 559
It will be an alternative for example, generator units where often two voltage transformers are supplied for measurement and excitation equipment. The application to supervise the voltage on two voltage transformers in the generator circuit is shown in figure 292. Line distance protection REL670 2.2 IEC Application manual...
The factor is defined as U2 · RFLx and shall be equal to the U1 voltage. Each phase has its own ratio factor. Line distance protection REL670 2.2 IEC Application manual...
(SDDRFUF) the alarm delay can be set to zero. 10.6 Loss of voltage check LOVPTUV SEMOD171868-1 v2 10.6.1 Identification SEMOD171954-2 v2 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Loss of voltage check LOVPTUV Line distance protection REL670 2.2 IEC Application manual...
The most common application of the PAPGAPC function is to provide tripping at the remote end of lines with passive load or with weak end infeed. The function must be included in the terminal at the weak infeed end of the feeder. Line distance protection REL670 2.2 IEC Application manual...
Del1PhOp: Enabling of delayed single phase operation. t1Ph: Time delay for single phase operation. Del3PhOp: Enabling of delayed three phase operation. ResCurrOper: Enabling of residual current operation. tResCurr: Time delay for residual current indication. Line distance protection REL670 2.2 IEC Application manual...
M13355-3 v8 All the frequency and voltage magnitude conditions in the system where SAPTUF performs its functions should be considered. The same also applies to the associated equipment, its frequency and time characteristic. Line distance protection REL670 2.2 IEC Application manual...
In smaller systems the frequency START level has to be set at a higher value, and the time delay must be rather short. Line distance protection REL670 2.2 IEC Application manual...
SAPFRC is normally used together with an overfrequency or underfrequency function, in small power systems, where a single event can cause a large imbalance Line distance protection REL670 2.2 IEC Application manual...
Page 569
- up to 3 Hz/s has been experienced when a small island was isolated from a large system. For more "normal" severe disturbances in large power systems, rate-of-change of frequency is much less, most often just a fraction of 1.0 Hz/s. Line distance protection REL670 2.2 IEC Application manual...
Each CVGAPC function module has got four independent protection elements built into it. Two overcurrent steps with the following built-in features: Line distance protection REL670 2.2 IEC Application manual...
The user can select a current input, by a setting parameter CurrentInput, to measure one of the current quantities shown in table 43. Line distance protection REL670 2.2 IEC Application manual...
Page 573
CVGAPC function will measure the phase L1 voltage phasor phase2 CVGAPC function will measure the phase L2 voltage phasor phase3 CVGAPC function will measure the phase L3 voltage phasor Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 574
U and U . This information about actual VT L1L2 L2L3 L3L1 connection is entered as a setting parameter for the pre-processing block, which will then be taken care automatically. Line distance protection REL670 2.2 IEC Application manual...
The reverse power protection might detect the situation but the operation time of this protection is normally too long. For big and important machines, fast protection against inadvertent energizing should, therefore, be included in the protective scheme. Line distance protection REL670 2.2 IEC Application manual...
OC element offers protection against all unbalance faults (phase-to-phase faults as well). Care shall be taken that the minimum pickup of such protection function shall be set above natural system unbalance level. Line distance protection REL670 2.2 IEC Application manual...
Page 578
In that case typically two NegSeq overcurrent steps are required. One for forward and one for reverse direction. As Line distance protection REL670 2.2 IEC Application manual...
By defining parameter x equal to maximum continuous negative sequence rating of the generator in accordance with the following formula Line distance protection REL670 2.2 IEC Application manual...
Page 580
B_OC1 = 0.0, C_OC1=0.0 and P_OC1=2.0 set StartCurr_OC1 equal to the value x then the OC1 step of the CVGAPC function can be used for generator negative sequence inverse overcurrent protection. Line distance protection REL670 2.2 IEC Application manual...
(k = 37.5 for the IEC standard or k = 41.4 for the ANSI standard) is the magnitude of the measured current is the generator rated current Line distance protection REL670 2.2 IEC Application manual...
Page 582
A, B, C and P are user settable coefficients which determine the curve used for Inverse Time Overcurrent TOC/IDMT calculation When the equation is compared with the equation for the inverse time characteristic of the OC1 step in it is obvious that if the following rules are followed: Line distance protection REL670 2.2 IEC Application manual...
Connect three-phase currents from the protected object to one CVGAPC instance (for example, GF03) Set CurrentInput to value UnbalancePh Set EnRestrainCurr to On Set RestrCurrInput to MaxPh Set RestrCurrCoeff to value 0.97 Line distance protection REL670 2.2 IEC Application manual...
Select CurveType_OC1 to value ANSI Very inv If required set minimum operating time for this curve by using parameter tMin_OC1 (default value 0.05s) Set StartCurr_OC1 to value 185% 10. Set VCntrlMode_OC1 to On 11. Set VDepMode_OC1 to Slope Line distance protection REL670 2.2 IEC Application manual...
RCA & ROA angles will be applicable for OC2 step if directional feature is enabled for this step as well. Figure shows overall protection characteristic Line distance protection REL670 2.2 IEC Application manual...
Page 586
Furthermore the other build-in protection elements can be used for other protection and alarming purposes. Q [pu] Operating region ILowSet [pu] -rca -0.2 -0.4 ILowSet Operating Region -0.6 -0.8 en05000535.vsd IEC05000535 V2 EN-US Figure 293: Loss of excitation Line distance protection REL670 2.2 IEC Application manual...
Sub-synchronous resonance protection for turbo generators • Sub-synchronous protection for wind turbines/wind farms • Detection of sub-synchronous oscillation between HVDC links and synchronous generators • Super-synchronous protection • Detection of presence of the geo-magnetic induced currents Line distance protection REL670 2.2 IEC Application manual...
GUID-5A3F67BD-7D48-4734-948C-01DAF9470EF8 v2 A relay type used for generator subsynchronous resonance overcurrent protection shall be replaced. The relay had inverse time operating characteristic as given with the following formula: (Equation 523) EQUATION13000029 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 589
IDMT characteristic is used which for multi-purpose overcurrent stage one, which has the following equation (for more information see Section “Inverse time characteristics” in the TRM). Line distance protection REL670 2.2 IEC Application manual...
14.1.3 Setting guidelines M12397-17 v8 GlobalBaseSel: Selects the global base value group used by the function to define IBase, UBase and SBase as applicable. Line distance protection REL670 2.2 IEC Application manual...
These solutions are combined to get the best possible effect in the fuse failure supervision function (FUFSPVC). FUFSPVC function built into the IED products can operate on the basis of external binary signals from the miniature circuit breaker or from the line disconnector. The Line distance protection REL670 2.2 IEC Application manual...
We propose a setting of approximately 70% of UBase. The drop off time of 200 ms for dead phase detection makes it recommended to always set SealIn to On since this will secure a fuse failure indication at persistent Line distance protection REL670 2.2 IEC Application manual...
The setting of the current limit 3I2< is in percentage of parameter IBase. The setting of 3I2< must be higher than the normal unbalance current that might exist in the system and can be calculated according to equation 528. Line distance protection REL670 2.2 IEC Application manual...
14.2.3.5 Delta U and delta I GUID-02336F26-98C0-419D-8759-45F5F12580DE v7 Set the operation mode selector OpDUDI to On if the delta function shall be in operation. Line distance protection REL670 2.2 IEC Application manual...
VDSPVC output can be configured to block voltage dependent protection functions such as high-speed distance protection, undervoltage relays, underimpedance relays and so on. Main Vt circuit FuseFailSupvn IEC12000143-1-en.vsd IEC12000143 V1 EN-US Figure 295: Application of VDSPVC Line distance protection REL670 2.2 IEC Application manual...
When SealIn is set to On and the fuse failure has last for more than 5 seconds, the blocked protection functions will remain blocked until normal voltage conditions are restored above the USealIn setting. The fuse failure outputs are deactivated when the normal voltage conditions are restored. Line distance protection REL670 2.2 IEC Application manual...
FreqDiffMin. If the frequency is less than FreqDiffMin the synchrocheck is used and the value of FreqDiffMin must thus be identical to the value FreqDiffM resp FreqDiffA for synchrocheck function. Line distance protection REL670 2.2 IEC Application manual...
Page 602
If needed an additional phase angle adjustment can be done for selected line voltage with the PhaseShift setting. Line distance protection REL670 2.2 IEC Application manual...
In steady conditions a bigger phase angle difference can be allowed as this is sometimes the case in a long and loaded parallel power line. For this application we accept a synchrocheck Line distance protection REL670 2.2 IEC Application manual...
The output is given only when the actual measured conditions match the set conditions. Figure shows two substations, where one (1) is energized and the other (2) is not energized. The line Line distance protection REL670 2.2 IEC Application manual...
The voltage selection function is used for the connection of appropriate voltages to the synchrocheck, synchronizing and energizing check functions. For example, when the IED is used in a double bus arrangement, the voltage that should be Line distance protection REL670 2.2 IEC Application manual...
(B16I). If the PSTO input is used, connected to the Local-Remote switch on the local HMI, the choice can also be from the station HMI system, typically ABB Microscada through IEC 61850–8–1 communication. The connection example for selection of the manual energizing mode is shown in figure 299.
The input used below in example are typical and can be changed by use of configuration and signal matrix tools. The SESRSYN and connected SMAI function block instances must have the same cycle time in the application configuration. Line distance protection REL670 2.2 IEC Application manual...
The voltage from busbar VT is connected to U3PBB1 and the voltage from the line VT is connected to U3PLN1. The conditions of the VT fuses shall also be connected as shown above. The voltage selection parameter CBConfig is set to No voltage sel. Line distance protection REL670 2.2 IEC Application manual...
LINE_MCB UB2OK WA2_MCB UB2FF ULN1OK LINE_MCB ULN1FF LINE_VT LINE IEC10000095-6-en.vsd IEC10000095 V4 EN-US Figure 302: Connection of the SESRSYN function block in a single breaker, double busbar arrangement with internal voltage selection Line distance protection REL670 2.2 IEC Application manual...
U3PBB1 on all three function blocks and the voltage from busbar 2 VT is connected to U3PBB2 on all three function blocks. The voltage from line1 VT is connected to U3PLN1 on all three function blocks and the voltage from line2 VT is Line distance protection REL670 2.2 IEC Application manual...
Page 611
Section 15 1MRK 506 369-UEN B Control connected to U3PLN2 on all three function blocks. The positions of the disconnectors and VT fuses shall be connected as shown in Figure 304. Line distance protection REL670 2.2 IEC Application manual...
Page 612
UB1FF WA2_MCB UB2OK UB2FF LINE1_MCB ULN1OK ULN1FF LINE2_MCB ULN2OK ULN2FF IEC10000097-4-en.vsd IEC10000097 V4 EN-US Figure 304: Connections of the SESRSYN function block in a 1 ½ breaker arrangement with internal voltage selection Line distance protection REL670 2.2 IEC Application manual...
Page 613
UB1OK/FF = Supervision of WA1_MCB fuse • UB2OK/FF = Supervision of WA2_MCB fuse • ULN1OK/FF = Supervision of LINE1_MCB fuse • ULN2OK/FF = Supervision of LINE2_MCB fuse • Setting CBConfig = 1 1/2 bus alt. CB Line distance protection REL670 2.2 IEC Application manual...
1 and 2 respectively, which can be a single-phase (phase-neutral), two-phase (phase-phase) or a positive sequence voltage. CBConfig This configuration setting is used to define type of voltage selection. Type of voltage selection can be selected as: Line distance protection REL670 2.2 IEC Application manual...
Page 615
A typical value for FreqDiffMin is 10 mHz. Generally, the value should be low if both synchronizing and synchrocheck functions are provided, and it is better to let the synchronizing function close, as it Line distance protection REL670 2.2 IEC Application manual...
Page 616
100 seconds. If the network frequencies are expected to be outside the limits from the start, a margin needs to be added. A typical setting is 600 seconds. Line distance protection REL670 2.2 IEC Application manual...
Page 617
PhaseDiffA setting. tSCM and tSCA The purpose of the timer delay settings, tSCM and tSCA, is to ensure that the synchrocheck conditions remains constant and that the situation is not due to a Line distance protection REL670 2.2 IEC Application manual...
Page 618
This voltage can be as high as 30% or more of the base line voltage. Because the setting ranges of the threshold voltages UHighBusEnerg/ UHighLineEnerg and ULowBusEnerg/ULowLineEnerg partly overlap each other, Line distance protection REL670 2.2 IEC Application manual...
“dead time” setting value. When simultaneous tripping and reclosing at the two line ends occurs, line dead time is approximately equal to the auto recloser “dead time”. If the auto reclosing dead time and line Line distance protection REL670 2.2 IEC Application manual...
Page 620
During the single-phase dead time there is an equivalent "series"-fault in the system resulting in a flow of zero sequence current. It is therefore necessary to Line distance protection REL670 2.2 IEC Application manual...
Page 621
The auto recloser can be inhibited (blocked) when certain protection functions detecting permanent faults, such as shunt reactor, cable or busbar protection are in operation. Back-up protection zones Line distance protection REL670 2.2 IEC Application manual...
Page 622
A permanent fault will cause the line protection to trip again when it recloses in an attempt to energize the line. The auto reclosing function allows a number of parameters to be adjusted. Examples: Line distance protection REL670 2.2 IEC Application manual...
No signal at INHIBIT input that is, no blocking or inhibit signal present. After the start has been accepted, it is latched in and an internal signal “start” is set. It can be interrupted by certain events, like an “inhibit” signal. Line distance protection REL670 2.2 IEC Application manual...
This time extension is controlled by the setting Extended t1 = On and the PLCLOST input. If this functionality is used the auto recloser start must also be allowed from distance protection zone 2 time delayed trip. Time Line distance protection REL670 2.2 IEC Application manual...
If TR2P and TR3P inputs are low (i.e. single-phase trip): The timer for single- phase auto reclosing dead time is started and the 1PT1 output (single-phase reclosing in progress) is activated. It can be used to suppress pole Line distance protection REL670 2.2 IEC Application manual...
1/2/3ph. If the first reclosing shot fails, a three-phase trip will be issued and three-phase reclosing will follow, if selected. At three-phase trip, a failure of a three-phase auto reclosing attempt will inhibit the auto recloser. No Line distance protection REL670 2.2 IEC Application manual...
External selection of auto reclosing mode M12391-241 v5 The auto reclosing mode can be selected by use of available logic function blocks. Below is an example where the choice of mode, ARMode=3ph or Line distance protection REL670 2.2 IEC Application manual...
If a new start occurs, and the number of auto reclosing shots is set to 1, and a new START or TRSOTF input signal appears, after the circuit breaker closing command, the UNSUCCL output (unsuccessful reclosing) is set high. The timer for the first Line distance protection REL670 2.2 IEC Application manual...
The sequence will continue as a three-phase auto reclosing sequence, if it is a selected alternative reclosing mode. The second fault which can be single-phase is tripped three-phase because the trip function Line distance protection REL670 2.2 IEC Application manual...
BLKON input or by an unsuccessful auto reclosing attempt if the BlockByUnsucCl setting is set to On. BLKON Used to block the auto recloser, for example, when certain special service conditions arise. When used, blocking must be reset with BLKOFF. Line distance protection REL670 2.2 IEC Application manual...
Page 632
Used to reset the auto recloser to start conditions. Possible hold by thermal overload protection will be reset. Circuit breaker position will be checked and time settings will be restarted with their set times. Line distance protection REL670 2.2 IEC Application manual...
Page 633
Signals for two-phase and three-phase trip. They are usually connected to the corresponding output of the trip function block. They control the choice of dead time and the auto reclosing cycle according to the selected program. Signal TR2P Line distance protection REL670 2.2 IEC Application manual...
Page 634
• wait: an auto recloser, acting as slave, is waiting for a release from the master to proceed with its own reclosing sequence Line distance protection REL670 2.2 IEC Application manual...
Page 635
Indicates that the auto recloser is ready for a new and complete auto reclosing sequence. It can be connected to the zone extension if a line protection should have extended zone reach before auto reclosing. Line distance protection REL670 2.2 IEC Application manual...
Page 636
Figure is showing an example of how to connect the auto recloser when used for single-phase, two-phase or three-phase auto reclosing. Line distance protection REL670 2.2 IEC Application manual...
Page 637
3PT1 ZCVPSOF-TRIP TRSOTF 3PT2 3PT3 THOLHOLD 3PT4 TR2P 3PT5 TRUE TR3P SESRSYN-AUTOOK SYNC WAIT RSTCOUNT WFMASTER =IEC04000135=5=en=Original.vsd IEC04000135 V5 EN-US Figure 309: Example of I/O-signal connections at a three-phase auto reclosing sequence Line distance protection REL670 2.2 IEC Application manual...
Page 638
WAIT input resets. The mimimum settable time for tSlaveDeadTime is 0.1sec because both master and slave should not send the breaker closing command at the same time. The slave Line distance protection REL670 2.2 IEC Application manual...
Page 639
If the High priority circuit breaker is not closed the High priority moves to the low priority circuit breaker. Line distance protection REL670 2.2 IEC Application manual...
Page 640
IEC04000137 V4 EN-US Figure 311: Additional input and output signals at multi-breaker arrangement. The connections can be made "symmetrical" to make it possible to control the priority by the settings, Priority: High/Low Line distance protection REL670 2.2 IEC Application manual...
INHIBIT input. tLongStartInh: The user can set a maximum start pulse duration time tLongStartInh. At a set time somewhat longer than the auto reclosing dead time, Line distance protection REL670 2.2 IEC Application manual...
Page 642
BlockByUnsucCl: Setting of whether an unsuccessful auto reclosing attempt shall set the auto recloser in blocked status. If used the BLKOFF input must be configured to unblock the function after an unsuccessful auto reclosing attempt. Normal setting is Off. Line distance protection REL670 2.2 IEC Application manual...
Page 643
NoOfShots: In power transmission one shot is mostly used. In most cases one auto reclosing shot is sufficient as the majority of arcing faults will cease after the first auto reclosing shot. In power systems with many other types of faults caused by Line distance protection REL670 2.2 IEC Application manual...
Page 644
The maximum wait time, tWaitForMaster for the second circuit breaker is set longer than the auto reclosing dead time plus a margin for synchrocheck conditions to be fulfilled for the first circuit breaker. Typical setting is 2sec. Line distance protection REL670 2.2 IEC Application manual...
The commands to an apparatus can be initiated from the Control Centre (CC), the station HMI or the local HMI on the IED front. Line distance protection REL670 2.2 IEC Application manual...
Page 646
The apparatus control function is realized by means of a number of function blocks designated: • Switch controller SCSWI • Circuit breaker SXCBR • Circuit switch SXSWI • Bay control QCBAY • Bay reserve QCRSV Line distance protection REL670 2.2 IEC Application manual...
Page 647
The extension of the signal flow and the usage of the GOOSE communication are shown in Figure 314. IEC 61850 en05000116.vsd IEC05000116 V2 EN-US Figure 313: Signal flow between apparatus control function blocks when all functions are situated within the IED Line distance protection REL670 2.2 IEC Application manual...
Page 648
IED, then the local/remote switch is under authority control, otherwise the default user can perform control operations from the local IED HMI without logging in. The default position of the local/remote switch is on remote. Line distance protection REL670 2.2 IEC Application manual...
The Bay control (QCBAY) is used to handle the selection of the operator place per bay. The function gives permission to operate from two main types of locations either from Remote (for example, control centre or station HMI) or from Local Line distance protection REL670 2.2 IEC Application manual...
SCSWI may handle and operate on one three-phase device or three one-phase switching devices. After the selection of an apparatus and before the execution, the switch controller performs the following checks and actions: Line distance protection REL670 2.2 IEC Application manual...
Substitution of position indication • Supervision timer that the primary device starts moving after a command • Supervision of allowed time for intermediate position • Definition of pulse duration for open/close command respectively Line distance protection REL670 2.2 IEC Application manual...
XLNPROXY function, their usage is controlled by the connection of each data’s signal input and valid input. These connections are usually from the GOOSEXLNRCV function (see Figure and Figure 317). Line distance protection REL670 2.2 IEC Application manual...
Page 653
Section 15 1MRK 506 369-UEN B Control IEC16000071 V1 EN-US Figure 316: Configuration with XLNPROXY and GOOSEXLNRCV where all the IEC 61850 modelled data is used, including selection Line distance protection REL670 2.2 IEC Application manual...
Page 654
SCSWI function. This cause is also shown on the output L_CAUSE as indicated in the following table: Line distance protection REL670 2.2 IEC Application manual...
IEDs. With this reservation method, the bay that wants the reservation sends a reservation request to other bays and then waits for a reservation granted signal from the other bays. Actual position Line distance protection REL670 2.2 IEC Application manual...
Page 656
The reservation can also be realized with external wiring according to the application example in Figure 319. This solution is realized with external auxiliary relays and extra binary inputs and outputs in each IED, but without use of function blocks QCRSV and RESIN. Line distance protection REL670 2.2 IEC Application manual...
Application principle for an alternative reservation solution 15.3.7 Interaction between modules M16626-3 v9 A typical bay with apparatus control function consists of a combination of logical nodes or functions that are described here: Line distance protection REL670 2.2 IEC Application manual...
Page 658
(energizing-check) is included. • The Generic Automatic Process Control function, GAPC, handles generic commands from the operator to the system. The overview of the interaction between these functions is shown in Figure below. Line distance protection REL670 2.2 IEC Application manual...
Figure 321: Example overview of the interactions between functions in a typical 15.3.8 Setting guidelines M16669-3 v5 The setting parameters for the apparatus control function are set via the local HMI or PCM600. Line distance protection REL670 2.2 IEC Application manual...
When the time has expired, the control function is reset, and a cause-code is given. tSynchrocheck is the allowed time for the synchrocheck function to fulfill the close conditions. When the time has expired, the function tries to start the synchronizing Line distance protection REL670 2.2 IEC Application manual...
The default length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI). tClosePulse is the output pulse length for a close command. If AdaptivePulse is set to Adaptive, it is the maximum length of the output pulse for an open command. Line distance protection REL670 2.2 IEC Application manual...
(x) in the bay, only the own bay is reserved, that is, the output for reservation request of other bays (RES_BAYS) will not be activated at selection of apparatus x. Line distance protection REL670 2.2 IEC Application manual...
As an option, a voltage indication can be used for interlocking. Take care to avoid a dangerous enable condition at the loss of a VT secondary voltage, for example, because of a blown fuse. Line distance protection REL670 2.2 IEC Application manual...
322. The function can also be used for a double busbar arrangement without transfer busbar or a single busbar arrangement with/without transfer busbar. Line distance protection REL670 2.2 IEC Application manual...
Signal QB7OPTR Q7 is open VPQB7TR The switch status for QB7 is valid. EXDU_BPB No transmission error from the bay that contains the above information. For bay n, these conditions are valid: Line distance protection REL670 2.2 IEC Application manual...
The switch status of BC_12 is valid. VP_BC_17 The switch status of BC_17 is valid. VP_BC_27 The switch status of BC_27 is valid. EXDU_BC No transmission error from any bus-coupler bay (BC). Line distance protection REL670 2.2 IEC Application manual...
Page 667
The switch status of bus-section coupler BS is valid. EXDU_BS No transmission error from the bay that contains the above information. For a line bay in section 1, these conditions are valid: Line distance protection REL670 2.2 IEC Application manual...
1 to section 2 and vice versa. 15.4.2.4 Configuration setting M13560-108 v4 If there is no bypass busbar and therefore no QB7 disconnector, then the interlocking for QB7 is not used. The states for QB7, QC71, BB7_D, BC_17, Line distance protection REL670 2.2 IEC Application manual...
Signal QQB12OPTR QB1 or QB2 or both are open. VPQB12TR The switch status of QB1 and QB2 are valid. EXDU_12 No transmission error from the bay that contains the above information. Line distance protection REL670 2.2 IEC Application manual...
Page 671
If the busbar is divided by bus-section circuit breakers, the signals from the bus- section coupler bay (A1A2_BS), rather than the bus-section disconnector bay (A1A2_DC), have to be used. For B1B2_BS, corresponding signals from busbar B Line distance protection REL670 2.2 IEC Application manual...
Section 1 Section 2 (WA1)A1 (WA2)B1 (WA7)C A1A2_DC(BS) B1B2_DC(BS) ABC_BC ABC_BC en04000484.vsd IEC04000484 V1 EN-US Figure 330: Busbars divided by bus-section disconnectors (circuit breakers) To derive the signals: Line distance protection REL670 2.2 IEC Application manual...
Page 673
VPS1S2TR The switch status of bus-section coupler BS is valid. EXDU_BS No transmission error from the bay containing the above information. For a bus-coupler bay in section 1, these conditions are valid: Line distance protection REL670 2.2 IEC Application manual...
QA2 and QC4 are not used in this interlocking en04000515.vsd IEC04000515 V1 EN-US Figure 332: Switchyard layout AB_TRAFO M13566-4 v4 The signals from other bays connected to the module AB_TRAFO are described below. Line distance protection REL670 2.2 IEC Application manual...
Line distance protection REL670 2.2 IEC Application manual...
Page 678
The switch status of bus-section coupler BS is valid. EXDU_BS No transmission error from the bay that contains the above information. For a bus-section circuit breaker between A1 and A2 section busbars, these conditions are valid: Line distance protection REL670 2.2 IEC Application manual...
Page 679
IEC04000490 V1 EN-US Figure 336: Signals from any bays for a bus-section circuit breaker between sections A1 and A2 For a bus-section circuit breaker between B1 and B2 section busbars, these conditions are valid: Line distance protection REL670 2.2 IEC Application manual...
QA1 open circuit breaker is not used or the state for BBTR is set to open. That is, no busbar transfer is in progress in this bus-section: • BBTR_OP = 1 • VP_BBTR = 1 Line distance protection REL670 2.2 IEC Application manual...
B are used. Section 1 Section 2 (WA1)A1 (WA2)B1 (WA7)C A1A2_DC(BS) B1B2_DC(BS) ABC_BC AB_TRAFO ABC_LINE ABC_LINE AB_TRAFO en04000493.vsd IEC04000493 V1 EN-US Figure 339: Busbars divided by bus-section disconnectors (circuit breakers) To derive the signals: Line distance protection REL670 2.2 IEC Application manual...
Page 682
The switch status of QB2 is valid. EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains the above information. For a bus-section disconnector, these conditions from the A1 busbar section are valid: Line distance protection REL670 2.2 IEC Application manual...
Page 683
EXDU_DC (A2/A3) en04000495.vsd IEC04000495 V1 EN-US Figure 341: Signals from any bays in section A2 to a bus-section disconnector For a bus-section disconnector, these conditions from the B1 busbar section are valid: Line distance protection REL670 2.2 IEC Application manual...
The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC, corresponding signals from busbar B are used. Line distance protection REL670 2.2 IEC Application manual...
Page 685
No transmission error from the bay that contains the above information. The logic is identical to the double busbar configuration “Signals in single breaker arrangement”. For a bus-section disconnector, these conditions from the A1 busbar section are valid: Line distance protection REL670 2.2 IEC Application manual...
Page 686
EXDU_DB (bay n/sect.A2) en04000500.vsd IEC04000500 V1 EN-US Figure 346: Signals from double-breaker bays in section A2 to a bus-section disconnector For a bus-section disconnector, these conditions from the B1 busbar section are valid: Line distance protection REL670 2.2 IEC Application manual...
The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC, corresponding signals from busbar B are used. Line distance protection REL670 2.2 IEC Application manual...
The signals from other bays connected to the module BB_ES are described below. 15.4.7.2 Signals in single breaker arrangement M15053-6 v5 The busbar earthing switch is only allowed to operate if all disconnectors of the bus-section are open. Line distance protection REL670 2.2 IEC Application manual...
Page 689
The switch status of bus-section disconnector DC is valid. EXDU_DC No transmission error from the bay that contains the above information. If no bus-section disconnector exists, the signal DCOPTR, VPDCTR and EXDU_DC are set to 1 (TRUE). Line distance protection REL670 2.2 IEC Application manual...
Page 690
Figure 352: Signals from any bays in section A1 to a busbar earthing switch in the same section For a busbar earthing switch, these conditions from the A2 busbar section are valid: Line distance protection REL670 2.2 IEC Application manual...
Page 691
Figure 354: Signals from any bays in section B1 to a busbar earthing switch in the same section For a busbar earthing switch, these conditions from the B2 busbar section are valid: Line distance protection REL670 2.2 IEC Application manual...
Signals from bypass busbar to busbar earthing switch 15.4.7.3 Signals in double-breaker arrangement M15053-83 v4 The busbar earthing switch is only allowed to operate if all disconnectors of the bus section are open. Line distance protection REL670 2.2 IEC Application manual...
The logic is identical to the double busbar configuration described in section “Signals in single breaker arrangement”. 15.4.7.4 Signals in 1 1/2 breaker arrangement M15053-123 v4 The busbar earthing switch is only allowed to operate if all disconnectors of the bus-section are open. Line distance protection REL670 2.2 IEC Application manual...
M13585-3 v10 The interlocking for a double busbar double circuit breaker bay including DB_BUS_A, DB_BUS_B and DB_LINE functions are used for a line connected to a double busbar arrangement according to figure 359. Line distance protection REL670 2.2 IEC Application manual...
• QB9_OP = VOLT_OFF • QB9_CL = VOLT_ON If there is no voltage supervision, then set the corresponding inputs as follows: • VOLT_OFF = 1 • VOLT_ON = 0 Line distance protection REL670 2.2 IEC Application manual...
M13569-6 v5 For application without QB9 and QC9, just set the appropriate inputs to open state and disregard the outputs. In the functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE: Line distance protection REL670 2.2 IEC Application manual...
(BLOCK) and one operator position input (PSTO). SLGAPC can be activated both from the local HMI and from external sources (switches) via the IED binary inputs. It also allows the operation from remote (like Line distance protection REL670 2.2 IEC Application manual...
PCM600 for a variety of applications, as a general purpose switch. VSGAPC can be used for both acquiring an external switch position (through the IPOS1 and the IPOS2 inputs) and represent it through the single line Line distance protection REL670 2.2 IEC Application manual...
Generic communication function for Double Point indication DPGAPC SEMOD55384-1 v4 15.7.1 Identification GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Generic communication function for DPGAPC Double Point indication Line distance protection REL670 2.2 IEC Application manual...
Closed Bad State 15.7.3 Setting guidelines SEMOD55398-5 v5 The function does not have any parameters available in the local HMI or PCM600. 15.8 Single point generic control 8 signals SPC8GAPC SEMOD176448-1 v3 Line distance protection REL670 2.2 IEC Application manual...
PulseModex: decides if the command signal for output x is Latched (steady) or Pulsed. tPulsex: if PulseModex is set to Pulsed, then tPulsex will set the length of the pulse (in seconds). 15.9 AutomationBits, command function for DNP3.0 AUTOBITS SEMOD158589-1 v3 Line distance protection REL670 2.2 IEC Application manual...
IEC 60617 ANSI/IEEE C37.2 identification identification device number Single command, 16 signals SINGLECMD 15.10.2 Application M12445-3 v3 Single command, 16 signals (SINGLECMD) is a common function and always included in the IED. Line distance protection REL670 2.2 IEC Application manual...
Page 703
Application example showing a logic diagram for control of a circuit breaker via configuration logic circuits Figure and figure show other ways to control functions, which require steady On/Off signals. Here, the output is used to control built-in functions or external devices. Line distance protection REL670 2.2 IEC Application manual...
Application example showing a logic diagram for control of external devices via configuration logic circuits 15.10.3 Setting guidelines M12448-3 v2 The parameters for Single command, 16 signals (SINGLECMD) are set via the local HMI or PCM600. Line distance protection REL670 2.2 IEC Application manual...
Page 705
0 to 1. That means the configured logic connected to the command function block may not have a cycle time longer than the cycle time for the command function block. Line distance protection REL670 2.2 IEC Application manual...
(overreaching and underreaching) • unblocking scheme and direct intertrip A permissive scheme is inherently faster and has better security against false tripping than a blocking scheme. On the other hand, a permissive scheme depend Line distance protection REL670 2.2 IEC Application manual...
Z rev TRIP = OR + tCoord+ CR Z rev IEC09000015_2_en.vsd IEC09000015 V2 EN-US Figure 365: Principle of blocking scheme Overreaching Communication signal received Communication signal send Z rev : Reverse zone Line distance protection REL670 2.2 IEC Application manual...
IEC11000252 V1 EN-US Figure 366: Principle of delta blocking scheme Overreaching Communication signal received Communication signal send deltaA: Delta based fault inception detection on A side that gets inhibited for forward faults Line distance protection REL670 2.2 IEC Application manual...
Therefore set the timer tCoord to zero. Failure of the communication channel does not affect the selectivity, but delays tripping at one end(s) for certain fault locations. Line distance protection REL670 2.2 IEC Application manual...
Page 711
The send signal (CS) might be issued in parallel both from an overreaching zone and an underreaching, independent tripping zone. The CS signal from the overreaching zone must not be prolonged while the CS signal from zone 1 can be prolonged. Line distance protection REL670 2.2 IEC Application manual...
In some power system applications, there is a need to trip the remote end breaker immediately from local protections. This applies for instance when transformers or reactors are connected to the system without circuit-breakers or for remote tripping following operation of breaker failure protection. Line distance protection REL670 2.2 IEC Application manual...
Restart if Unblocking scheme with alarm for loss of guard is to be used) Set to tSecurity = 0.035 s 16.1.3.2 Delta blocking scheme GUID-F4359690-F433-46CB-A173-8C14559E3FCF v1 Operation SchemeType DeltaBlocking tCoord = 0 s tSendMin = 0 s Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
NoRestart if only trip is required) tSecurity = 0.035 s 16.1.3.6 Intertrip scheme M13869-62 v5 Operation SchemeType Intertrip tCoord = 50 ms (10 ms + maximal transmission time) Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
The logic supports the following communications schemes: • blocking scheme • permissive schemes (overreach and underreach) • direct intertrip Line distance protection REL670 2.2 IEC Application manual...
Page 716
In case of single-phase faults, only one channel is activated at a time. But in case of multi-phase faults, two or three channels are activated simultaneously. The following descriptions of the schemes generally presents one of the three identical phases. Line distance protection REL670 2.2 IEC Application manual...
SEMOD141790-35 v2 Permissive underreach scheme is not suitable to use on short line length due to difficulties for distance protection measurement in general to distinguish between internal and external faults in those applications. Line distance protection REL670 2.2 IEC Application manual...
Page 718
CS signal from zone1 can be prolonged. To secure correct operations of current reversal logic in case of parallel lines, when applied, the carrier send signal CS shall not be prolonged. So Line distance protection REL670 2.2 IEC Application manual...
IEC 60834-1. It is recommended to coordinate the proposed settings with actual performance for the teleprotection equipment to get optimized settings. 16.2.3.1 Permissive underreache scheme SEMOD141800-6 v1 Operation Scheme Permissive UR type tCoord 0 ms tSendMin 0.1 s Line distance protection REL670 2.2 IEC Application manual...
3-phase 16.3.2 Application IP15023-1 v1 16.3.2.1 Current reversal logic M13895-4 v6 To avoid this kind of disturbances, a fault current reversal logic (transient blocking logic) can be used. Line distance protection REL670 2.2 IEC Application manual...
(WEI) echo logic is used. The fault current can also be initially too low due to the fault current distribution. Here, the fault current increases when the breaker opens at the strong terminal, and a sequential tripping is achieved. This Line distance protection REL670 2.2 IEC Application manual...
(SBase) are set in global base values for settings function GBASVAL. GlobalBaseSel: Selects the global base value group used by the function to define IBase, UBase and SBase as applicable. Line distance protection REL670 2.2 IEC Application manual...
IRVLx has reset and the tDelayRev time has elapsed. To achieve this, the reverse zone on the distance protection shall be connected to input IRVLx and the output IRVOPLx shall be connected to input BLKCS on the communication function block ZCPSCH. Line distance protection REL670 2.2 IEC Application manual...
(SBase) are set in Global base values for settings function GBASVAL. GlobalBaseSel: It is used to select a GBASVAL function for reference of base values. Current reversal logic Set OperCurrRev to On to activate the function. Line distance protection REL670 2.2 IEC Application manual...
The local acceleration logic (ZCLCPSCH) is used in applications where a conventional teleprotection scheme is not available (no communication channel), but where the user still requires fast clearance for faults on the whole line. Line distance protection REL670 2.2 IEC Application manual...
At the same time it should be set below the minimum load current transfer during normal operations that the line can be subjected to. By default, MinCurr is set to 5% of IBase. Line distance protection REL670 2.2 IEC Application manual...
With power line carrier, for example, the communication signal may be attenuated by the fault, especially when the fault is close to the line end, thereby disabling the communication channel. Line distance protection REL670 2.2 IEC Application manual...
B2. The delayed reset of output signal IRVL also ensures the send signal from IED B2 is held back till the forward direction element is reset in IED A2. Line distance protection REL670 2.2 IEC Application manual...
In communication networks small additional time delays are added in multiplexers and repeaters. Theses delays are less than 1 ms per process. It is often stated that the total propagation time is less than 5 ms. Line distance protection REL670 2.2 IEC Application manual...
(3U0) higher than the maximum false network frequency residual voltage that can occur during normal service conditions. The recommended minimum setting is two times the false zero-sequence voltage during normal service conditions. Line distance protection REL670 2.2 IEC Application manual...
The trip signal from local criterion will ensure the fault at the remote end and release the trip signal to the local side circuit breaker. The local criterion must detect the abnormal conditions and permit the CR signal to trip the circuit breaker. Line distance protection REL670 2.2 IEC Application manual...
Figure 379: DTT scheme 16.8.2 Setting guidelines GUID-9E9CD5E0-1556-4E56-8A5D-5ACC17DAA00F v2 Setting guidelines for Direct transfer trip functions are outlined in the following sections. 16.8.3 Low active power and power factor protection LAPPGAPC GUID-585236C8-583C-4415-9820-A1DD038EA995 v1 Line distance protection REL670 2.2 IEC Application manual...
However, when fault current is fed to the fault point the power loss in the fault will be detected. For operation for all unsymmetrical faults 1 out of 3 should be selected. Line distance protection REL670 2.2 IEC Application manual...
The capacitance (and charging current) is negligible in short line but significant in medium line and appreciable in long line. The percentage voltage rise due to the Ferranti effect between local end and remote end voltage is proportional Line distance protection REL670 2.2 IEC Application manual...
Page 737
The definite delay time for compensated over and under voltage can be shorter than that at remote end, but not too short. A short delay time would result in frequent Line distance protection REL670 2.2 IEC Application manual...
Setting guidelines GUID-DE3963D6-016E-41AD-832F-1D10DD26AABA v2 GlobalBaseSel: Selects the global base value group used by the function to define IBase, UBase and SBase as applicable. OperationUV: Used to set the under-voltage function On or Off. Line distance protection REL670 2.2 IEC Application manual...
The Sudden change in current variation (SCCVPTOC) function is fast way of finding any abnormality in line currents. When there is a fault in the system then current changes faster than the voltage. SCCVPTOC finds abnormal condition Line distance protection REL670 2.2 IEC Application manual...
2' mode if any one of the two CR is received then the trip signal coming from the local criterion is released, and in case of '2 out of 2' mode both the CR’s Line distance protection REL670 2.2 IEC Application manual...
Negative sequence voltage is also available as service value output U2. 16.8.7.3 Setting guidelines GUID-CB454AA3-ED5F-4D8A-9568-B6A167301B1E v2 GlobalBaseSel: Selects the global base value group used by the function to define IBase, UBase and SBase as applicable. Line distance protection REL670 2.2 IEC Application manual...
BLKTR will block the trip output. Negative sequence current is available as service value output I2. 16.8.9.3 Setting guideline GUID-377FEADE-375F-4B2D-ADDE-D92C59BDBD41 v2 GlobalBaseSel: Selects the global base value group used by the function to define IBase, UBase and SBase as applicable. Line distance protection REL670 2.2 IEC Application manual...
The choice of time delay is depending on the application of the protection as well as network topology. 16.8.12 Three phase undercurrent LCP3PTUC GUID-E8EAE24D-4B69-43DC-BCFC-C4AC63AA66AB v1 Line distance protection REL670 2.2 IEC Application manual...
The choice of time delay is depending on the application of the protection as well as network topology. Line distance protection REL670 2.2 IEC Application manual...
1/3-phase tripping and 1/3-phase autoreclosing. Alternatively, the breaker chosen as master can have single-phase tripping, while the slave Line distance protection REL670 2.2 IEC Application manual...
OR conditions from both line protections. Other back-up functions are connected to the input TRIN as described above for three-phase tripping. A typical connection for a single-phase tripping scheme is shown in figure 383. Line distance protection REL670 2.2 IEC Application manual...
The SMPPTRC function block is provided with possibilities to initiate lock-out. The lock-out can be set to only activate the block closing output CLLKOUT or initiate the block closing output and also maintain the trip signal output TR3P (latched trip). Line distance protection REL670 2.2 IEC Application manual...
SETLKOUT. 17.1.2.5 Example of directional data GUID-08AC09AB-2B2F-4095-B06E-1171CF225869 v2 An example how to connect the directional data from different application functions to the trip function is given below, see Figure 384: Line distance protection REL670 2.2 IEC Application manual...
Page 752
SMPPTRC, or directly to SMAGAPC and then to the SMPPTRC. The trip function (SMPPTRC) splits up the directional data as general output data for START, STL1, STL2, STL3, STN, FW and REV. Line distance protection REL670 2.2 IEC Application manual...
LEDs and/or output contacts on the IED. ALMCALH output signal and the physical outputs allows the user to adapt the alarm signal to physical tripping outputs according to the specific application needs. Line distance protection REL670 2.2 IEC Application manual...
LEDs and/or output contacts on the IED. INDCALH output signal IND and the physical outputs allows the user to adapt the indication signal to physical outputs according to the specific application needs. Line distance protection REL670 2.2 IEC Application manual...
GUID-D93E383C-1655-46A3-A540-657141F77CF0 v4 Logic is configured using the ACT configuration tool in PCM600. Execution of functions as defined by the configurable logic blocks runs according to a fixed sequence with different cycle times. Line distance protection REL670 2.2 IEC Application manual...
Page 757
Remember to design the logic circuits carefully and always check the execution sequence for different functions. In other cases, additional time delays must be introduced into the logic schemes to prevent errors, for example, race between functions. Line distance protection REL670 2.2 IEC Application manual...
Since all group connections are mandatory to be connected, the third input needs to be connected to something, which is the GRP_OFF signal in FXDSIGN function block. Line distance protection REL670 2.2 IEC Application manual...
Values of each of the different OUTx from function block B16I for 1≤x≤16. The sum of the value on each INx corresponds to the integer presented on the output OUT on the function block B16I. Line distance protection REL670 2.2 IEC Application manual...
Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC) is used to transform a set of 16 binary (logical) signals into an integer. BTIGAPC has a logical node mapping in IEC 61850. Line distance protection REL670 2.2 IEC Application manual...
1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an integer by the BTIGAPC function block. 17.10 Integer to Boolean 16 conversion IB16 SEMOD158367-1 v2 Line distance protection REL670 2.2 IEC Application manual...
OUTx where 1≤x≤16. The values of the different OUTx are according to the Table 53. If the BLOCK input is activated, it freezes the logical outputs at the last value. Line distance protection REL670 2.2 IEC Application manual...
The function TEIGAPC is used for user-defined logics and it can also be used for different purposes internally in the IED. An application example is the integration of elapsed time during the measurement of neutral point voltage or neutral current at earth-fault conditions. Line distance protection REL670 2.2 IEC Application manual...
The function gives the possibility to monitor the level of integer values in the system relative to each other or to a fixed value. It is a basic arithmetic function that can be used for monitoring, supervision, interlocking and other logics. Line distance protection REL670 2.2 IEC Application manual...
For absolute comparison between input and setting Set the EnaAbs = Absolute Set the RefSource = Set Value SetValue shall be set between -2000000000 to 2000000000 Similarly for signed comparison between input and setting Line distance protection REL670 2.2 IEC Application manual...
RefPrefix: This setting is used to set the unit of the reference value for comparison when setting RefSource is selected as SetValue. It has 5 unit selections and they are Milli, Unity, Kilo, Mega and Giga. Line distance protection REL670 2.2 IEC Application manual...
INPUT and REF. Then the settings should be adjusted as below, EnaAbs = Absolute RefSource = Input REF EqualBandHigh = 5.0 % of reference value EqualBandLow = 5.0 % of reference value. Line distance protection REL670 2.2 IEC Application manual...
IEC 61850. The possibility to continuously monitor measured values of active power, reactive power, currents, voltages, frequency, power factor etc. is vital for efficient production, transmission and distribution of electrical energy. It Line distance protection REL670 2.2 IEC Application manual...
Page 770
(DFT values) of the measured current and voltage signals. The measured power quantities are available either, as instantaneously calculated quantities or, averaged values over a period of time (low pass filtered) depending on the selected settings. Line distance protection REL670 2.2 IEC Application manual...
I leading U System mean voltage, calculated according to selected mode System mean current, calculated according to selected mode Frequency Relevant settings and their values on the local HMI under Main menu/ Settings/IED settings/Monitoring/Servicevalues(P_Q)/CVMMXN(P_Q): Line distance protection REL670 2.2 IEC Application manual...
UAmpCompY: Amplitude compensation to calibrate voltage measurements at Y% of Ur, where Y is equal to 5, 30 or 100. IAmpCompY: Amplitude compensation to calibrate current measurements at Y% of Ir, where Y is equal to 5, 30 or 100. Line distance protection REL670 2.2 IEC Application manual...
Page 773
XHiHiLim: High-high limit. Set as % of YBase (Y is SBase for S,P,Q UBase for Voltage measurement and IBase for current measurement). Line distance protection REL670 2.2 IEC Application manual...
Page 774
The first phase will be used as reference channel and compared with the curve for calculation of factors. The factors will then be used for all related channels. IEC05000652 V2 EN-US Figure 389: Calibration curves Line distance protection REL670 2.2 IEC Application manual...
“Setting of the phase reference channel”) using PCM600 for analog input channels Connect, in PCM600, measurement function to three-phase CT and VT inputs Set under General settings parameters for the Measurement function: Line distance protection REL670 2.2 IEC Application manual...
Page 776
Cycl: Report interval (s), Db: In 2000 Set ±Δdb=40 MW that is, 2% 0.001% of range, Int Db: In (larger changes than 40 MW will 0.001%s be reported) Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 777
30% of Ir IAngComp100 Angle pre-calibration for current 0.00 at 100% of Ir Measurement function application for a power transformer SEMOD54481-61 v9 Single line diagram for this application is given in figure 391. Line distance protection REL670 2.2 IEC Application manual...
Page 778
PCM600 for analog input channels Connect, in PCM600, measurement function to LV side CT & VT inputs Set the setting parameters for relevant Measurement function as shown in the following table 57: Line distance protection REL670 2.2 IEC Application manual...
Page 779
Base setting for power in MVA 31.5 Set based on rated power Global base) Measurement function application for a generator SEMOD54481-110 v8 Single line diagram for this application is given in figure 392. Line distance protection REL670 2.2 IEC Application manual...
Page 780
PCM600 for analog input channels Connect, in PCM600, measurement function to the generator CT & VT inputs Set the setting parameters for relevant Measurement function as shown in the following table: Line distance protection REL670 2.2 IEC Application manual...
Binary information based on the gas pressure in the circuit breaker is used as an input signal to the function. The function generates alarms based on the received information. Line distance protection REL670 2.2 IEC Application manual...
This is used for the temperature lockout indication to reset after a set time delay in s. tResetTempAlm: This is used for the temperature alarm indication to reset after a set time delay in s. Line distance protection REL670 2.2 IEC Application manual...
This is used to set the time delay for a level lockout indication, given in s. tTempAlarm: This is used to set the time delay for a temperature alarm indication, given in s. Line distance protection REL670 2.2 IEC Application manual...
The breaker status is indicated by the binary outputs. These signals indicate whether the circuit breaker is in an open, closed or error state. Line distance protection REL670 2.2 IEC Application manual...
Page 785
10000/900 = 11 operations at the rated current. It is assumed that prior to tripping, the remaining life of a breaker is 10000 operations. Remaining life calculation for three different interrupted current conditions is explained below. Line distance protection REL670 2.2 IEC Application manual...
Page 786
Binary input available from the pressure sensor is based on the pressure levels inside the arc chamber. When the pressure becomes too low compared to the required value, the circuit breaker operation is blocked. Line distance protection REL670 2.2 IEC Application manual...
CloseTimeCorr: Correction factor for circuit breaker closing travel time. tTrOpenAlm: Setting of alarm level for opening travel time. tTrCloseAlm: Setting of alarm level for closing travel time. OperAlmLevel: Alarm limit for number of mechanical operations. Line distance protection REL670 2.2 IEC Application manual...
OperTimeDelay: Time delay between change of status of trip output and start of main contact separation. 18.5 Event function EVENT IP14590-1 v2 18.5.1 Identification SEMOD167950-2 v2 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Event function EVENT S00946 V1 EN-US Line distance protection REL670 2.2 IEC Application manual...
0, that is, no cyclic communication. M12811-34 v1 It is important to set the time interval for cyclic events in an optimized way to minimize the load on the station bus. Line distance protection REL670 2.2 IEC Application manual...
Thus, disturbance report is not dependent on the operation of protective functions, and it can record disturbances that were not discovered by protective functions for one reason or another. Disturbance report can be used as an advanced stand-alone disturbance recorder. Line distance protection REL670 2.2 IEC Application manual...
(TVR) uses analog information from the analog input function blocks (AxRADR), which is used by Fault locator (FL) after estimation by Trip Value Recorder (TVR). Disturbance report function acquires information from both AxRADR and BxRBDR. Line distance protection REL670 2.2 IEC Application manual...
Page 792
Flashing light The IED is in test mode Red LED: Steady light Triggered on binary signal N with SetLEDx = Trip (or Start and Trip) Flashing The IED is in configuration mode Line distance protection REL670 2.2 IEC Application manual...
Prefault recording time (PreFaultRecT) is the recording time before the starting point of the disturbance. The setting should be at least 0.1 s to ensure enough samples for the estimation of pre-fault values in the Trip value recorder (TVR) function. Line distance protection REL670 2.2 IEC Application manual...
(1) or negative (0) slope. OperationN: Disturbance report may trig for binary input N (On) or not (Off). TrigLevelN: Trig on positive (Trig on 1) or negative (Trig on 0) slope for binary input N. Line distance protection REL670 2.2 IEC Application manual...
HMI. If not set (Hide), status change will not be indicated. SetLEDN: Set red LED on local HMI in front of the IED if binary input N changes status. Line distance protection REL670 2.2 IEC Application manual...
How long is the longest expected fault clearing time? • Is it necessary to include reclosure in the recording or should a persistent fault generate a second recording (PostRetrig)? Minimize the number of recordings: Line distance protection REL670 2.2 IEC Application manual...
When an input is set, the respective output is set for a user defined time. If the input signal remains set for a longer period, the output will remain set until the input signal resets. Line distance protection REL670 2.2 IEC Application manual...
Beside this information the function must be informed about faulted phases for correct loop selection (phase selective outputs from differential protection, distance protection, directional OC protection, and so on). The following loops are used for different types of faults: Line distance protection REL670 2.2 IEC Application manual...
The list of parameters explains the meaning of the abbreviations. Figure also presents these system parameters graphically. Note, that all impedance values relate to their primary values and to the total length of the protected line. Line distance protection REL670 2.2 IEC Application manual...
If the actual values are not known, the values that correspond to the source impedance characteristic angle of 85° give satisfactory results. 18.8.3.1 Connection of analog currents M13769-16 v5 Connection diagram for analog currents included IN from parallel line shown in figure 397. Line distance protection REL670 2.2 IEC Application manual...
ANSI/IEEE C37.2 identification identification device number Limit counter L4UFCNT 18.9.2 Application GUID-41B13135-5069-4A5A-86CE-B7DBE9CFEF38 v2 Limit counter (L4UFCNT) is intended for applications where positive and/or negative flanks on a binary signal need to be counted. Line distance protection REL670 2.2 IEC Application manual...
18.10.3 Setting guidelines GUID-D3BED56A-BA80-486F-B2A8-E47F7AC63468 v1 The settings tAlarm and tWarning are user settable limits defined in hours. The achievable resolution of the settings is 0.1 hours (6 minutes). Line distance protection REL670 2.2 IEC Application manual...
Page 803
> tWarning. The limit for the overflow supervision is fixed at 99999.9 hours. The setting tAddToTime is a user settable time parameter in hours. Line distance protection REL670 2.2 IEC Application manual...
Parameters that can be set individually for each pulse counter from PCM600: • Operation: Off/On • tReporting: 0-3600s • EventMask: NoEvents/ReportEvents Configuration of inputs and outputs of PCFCNT is made via PCM600. Line distance protection REL670 2.2 IEC Application manual...
(CVMMXN). This function has a site calibration possibility to further increase the total accuracy. The function is connected to the instantaneous outputs of (CVMMXN) as shown in figure 398. Line distance protection REL670 2.2 IEC Application manual...
The following settings can be done for the energy calculation and demand handling function ETPMMTR: GlobalBaseSel: Selects the global base value group used by the function to define IBase, UBase and SBase as applicable. Operation: Off/On Line distance protection REL670 2.2 IEC Application manual...
Page 808
For the advanced user there are a number of settings for direction, zero clamping, max limit, and so on. Normally, the default values are suitable for these parameters. Line distance protection REL670 2.2 IEC Application manual...
ECT creates the access point in the SCL model. Unselecting the subnetwork removes the access point from the SCL model. This column is editable for IEC61850 Ed2 IEDs and not editable for Line distance protection REL670 2.2 IEC Application manual...
PRP-1 and HSR can be combined in a mixed network. If the access point is not taken into operation, the write option in Ethernet Configuration Tool can be used to activate the access point. Line distance protection REL670 2.2 IEC Application manual...
(or subscribers) in the system. Some merging units are able to get data from classical measuring transformers, others from non- conventional measuring transducers and yet others can pick up data from both types. Line distance protection REL670 2.2 IEC Application manual...
Operation for the route can be set to On/Off by checking and unchecking the check-box in the operation column. Gateway specifies the address of the gateway. Destination specifies the destination. Destination subnet mask specifies the subnetwork mask of the destination. Line distance protection REL670 2.2 IEC Application manual...
M13913-3 v6 Figure shows the topology of an IEC 61850–8–1 configuration. IEC 61850–8– 1 specifies only the interface to the substation LAN. The LAN itself is left to the system integrator. Line distance protection REL670 2.2 IEC Application manual...
Page 816
M16925-3 v4 Figure404 shows the GOOSE peer-to-peer communication. Station HSI MicroSCADA Gateway GOOSE Control Protection Control and protection Control Protection en05000734.vsd IEC05000734 V1 EN-US Figure 404: Example of a broadcasted GOOSE message Line distance protection REL670 2.2 IEC Application manual...
The settings available for Generic communication function for Measured Value (MVGAPC) function allows the user to choose a deadband and a zero deadband for the monitored signal. Values within the zero deadband are considered as zero. Line distance protection REL670 2.2 IEC Application manual...
Input1 Ext_Res_OK_To_Operate DataValid Input2 Noput Input2 Noput CommValid Input3 Input3 Test Input4 Input4 IEC16000082=1=en.vsd IEC16000082 V1 EN-US Figure 405: GOOSESPRCV and AND function blocks - checking the validity of the received data Line distance protection REL670 2.2 IEC Application manual...
The process bus physical layout can be arranged in several ways, described in Annex B of the standard, depending on what are the needs for sampled data in a substation. Line distance protection REL670 2.2 IEC Application manual...
Page 820
The electronic part of a non-conventional measuring transducer (like a Rogowski coil or a capacitive divider) can represent a MU by itself as long as it can send sampled data over process bus. Line distance protection REL670 2.2 IEC Application manual...
Page 821
1PPS Merging Unit Combi Sensor Conventional VT en08000069-3.vsd IEC08000069 V2 EN-US Figure 407: Example of a station configuration with the IED receiving analog values from both classical measuring transformers and merging units. Line distance protection REL670 2.2 IEC Application manual...
IEC08000070 V2 EN-US Figure 408: Example of a station configuration with the IED receiving analogue values from merging units 21.3.2 Setting guidelines GUID-29B296B3-6185-459F-B06F-8E7F0C6C9460 v4 Merging Units (MUs) have several settings on local HMI under: Line distance protection REL670 2.2 IEC Application manual...
Loss of communication when used with LDCM GUID-29EFBCB7-2B4F-4AA1-B593-8E89838722E0 v4 If IEC/UCA 61850-9-2LE communication is lost, see examples in figures 409, and 411, the protection functions in table are blocked as per graceful degradation. Case 1: Line distance protection REL670 2.2 IEC Application manual...
Page 824
Figure 410: MU failed, mixed system Case 3: Failure of one MU (sample lost) blocks the sending and receiving of binary signals through LDCM. →DTT from the remote end is not working. Line distance protection REL670 2.2 IEC Application manual...
Page 825
Four step residual EF4PTOC Sudden change in SCCVPTOC overcurrent protection current variation Instantaneous residual EFPIOC Sensitive Directional SDEPSDE overcurrent protection residual over current and power protetcion Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 826
Negative sequence LCNSPTOV Scheme ZCPSCH overvoltage protection communication logic for distance or overcurrent protection Three phase LCP3PTOC Current reversal and ZCRWPSCH overcurrent weak-end infeed logic for distance protection Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 827
Four step phase OC4PTOC Power swing detection ZMRPSB overcurrent protection Overexcitation OEXPVPH Mho Impedance ZSMGAPC protection supervision logic Out-of-step protection OOSPPAM Transformer tank TPPIOC overcurrent protection Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
When using an external clock, it is possible to set the IED to be synchronized via PPS,IRIG-B or PTP. It is also possible to use an internal GPS receiver in the IED (if the external clock is using GPS). Line distance protection REL670 2.2 IEC Application manual...
Page 829
SyncAccLevel: can be set to 1μs since this corresponds to a maximum phase angle error of 0.018 degrees at 50Hz Settings on the local HMI under Main menu/Configuration/Communication/ Ethernet configuration/Access point/AP_X: • Operation: On • PTP: On Line distance protection REL670 2.2 IEC Application manual...
Page 830
Setting example when MU is the synchronizing source Settings on the local HMI under Main menu/Configuration/Time/ Synchronization/TIMESYNCHGEN:1/IEC61850-9-2: • HwSyncSrc: set to PPS as generated by the MU (ABB MU) • SyncLostMode : set to Block to block protection functions if time synchronization is lost •...
Page 831
HWSyncSrc , “full-time” has to be acquired from another source. If station clock is on the local area network (LAN) and has an sntp-server, this is one option. Two status monitoring signals can be: Line distance protection REL670 2.2 IEC Application manual...
Page 832
• HwSyncSrc: set to Off • SyncLostMode: set to No block to indicate that protection functions are not blocked • SyncAccLevel: set to unspecified Two status monitoring signals with no time synchronization: Line distance protection REL670 2.2 IEC Application manual...
IED. The function outputs are updated once every second and, therefore, do not reflect the quality bits in real time. Line distance protection REL670 2.2 IEC Application manual...
The communication speed of the LON bus is set to the default of 1.25 Mbit/s. This can be changed by LNT. 21.4.2 MULTICMDRCV and MULTICMDSND SEMOD119881-1 v3 Line distance protection REL670 2.2 IEC Application manual...
LAN (see Figure 418), and when using the rear optical Ethernet port, the only hardware required for a station monitoring system is: • Optical fibers from the IED to the utility substation LAN • PC connected to the utility office LAN Line distance protection REL670 2.2 IEC Application manual...
When the communication protocol is selected, the IED is automatically restarted, and the port then operates as a SPA port. The SPA communication setting parameters are set on the local HMI under Main menu/Configuration/Communication/Station communication/SPA/SPA:1. Line distance protection REL670 2.2 IEC Application manual...
Page 838
The IED does not adapt its speed to the actual communication conditions because the communication speed is set on the local HMI. Line distance protection REL670 2.2 IEC Application manual...
The master must have software that can interpret the IEC 60870-5-103 communication messages. For detailed information about IEC 60870-5-103, refer to IEC 60870 standard part 5: Transmission Line distance protection REL670 2.2 IEC Application manual...
Function block with pre-defined functions in control direction, I103CMD. This block includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER parameter is defined for each output signal. • Function commands in control direction Line distance protection REL670 2.2 IEC Application manual...
Page 841
I103FLTPROT. This block includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER parameter is defined for each input signal. This block is suitable for distance protection, line differential, transformer differential, over-current and earth-fault protection functions. • Autorecloser indications in monitor direction Line distance protection REL670 2.2 IEC Application manual...
A1RADR to A4RADR. The eight first ones belong to the public range and the remaining ones to the private range. 21.6.2 Settings M17109-116 v1 Line distance protection REL670 2.2 IEC Application manual...
The protocol to activate on a physical port is selected under: Main menu/Configuration/Communication/Station Communication/Port configuration/ • RS485 port • RS485PROT:1 (off, DNP, IEC103) • SLM optical serial port • PROTOCOL:1 (off, DNP, IEC103, SPA) Line distance protection REL670 2.2 IEC Application manual...
ON_SET. In addition there is a setting on each event block for function type. Refer to description of the Main Function type set on the local HMI. Line distance protection REL670 2.2 IEC Application manual...
Page 845
IEC 60870-5-103 meaning Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Private range Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
REC 242 Private range, use default RED 192 Compatible range RET 176 Compatible range REB 207 Private range REG 150 Private range REQ 245 Private range RER 152 Private range RES 118 Private range Line distance protection REL670 2.2 IEC Application manual...
For more information, refer to IEC standard IEC 60870-5-103. 21.7 DNP3 Communication protocol 21.7.1 Application GUID-EF1F0C38-9FF6-4683-8B10-AAA372D42185 v1 For more information on the application and setting guidelines for the DNP3 communication protocol refer to the DNP3 Communication protocol manual. Line distance protection REL670 2.2 IEC Application manual...
Figure 421, only IED-B has access to all currents and, therefore, this is the only place where the differential current is evaluated. If the evaluation results in a trip, the trip signal will be sent over the two communication links. Line distance protection REL670 2.2 IEC Application manual...
The LDCM (Line Data Communication Module) has an optical connection such that two IEDs can be connected over a direct fiber (multimode), as shown in figure 422. The protocol used is IEEE/ANSI C37.94. The distance with this solution is typical 110 km. Line distance protection REL670 2.2 IEC Application manual...
IEDs in the system is out of service: it can either be done on the IED out of service by setting all local LDCMs to channel mode OutOfService or at the remote Line distance protection REL670 2.2 IEC Application manual...
Page 852
Slot 305: main channel • Slot 306: redundant channel The same is applicable for slot 312-313 and slot 322-323. DiffSync defines the method of time synchronization for the line differential function: Echo or GPS. Line distance protection REL670 2.2 IEC Application manual...
Page 853
Multi-mode fiber Single-mode fiber Single-mode fiber glass 50/125 μm glass 62.5/125 glass 9/125 μm glass 9/125 μm μm Modem type 1MRK0002122- 1MRK0002122- 1MRK002311-AA 1MRK002311-BA Contact type FC/PC FC/PC Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 854
80 km 120 km distance Attenuation in 6 dB 9 dB 25.6 dB 25.2 dB fibre-optic cables 2 contacts 2 dB 3 dB 0.6 dB 0.6 dB Table continues on next page Line distance protection REL670 2.2 IEC Application manual...
Page 855
1½ breaker arrangement has two local currents, and the Current Transformer (CT) earthing for those can differ. CT-SUM transmits the sum of the two CT groups. CT- Line distance protection REL670 2.2 IEC Application manual...
Page 856
LinkForwarded is used to configure the LDCM to merge the inter-trip and block signals from another LDCM-receiver. This is used when the analog signals for the LDCM-transmitter is connected to the receiver of another LDCM. Line distance protection REL670 2.2 IEC Application manual...
Apart from the built-in supervision of the various modules, events are also generated when the status changes for the: • built-in real time clock (in operation/out of order). • external time synchronization (in operation/out of order). Line distance protection REL670 2.2 IEC Application manual...
The binary input controlling the function is defined in ACT or SMT. The CHNGLCK function is configured using ACT. LOCK Binary input signal that will activate/deactivate the function, defined in ACT or SMT. Line distance protection REL670 2.2 IEC Application manual...
CHNGLCK input, that logic must be designed so that it cannot permanently issue a logical one to the CHNGLCK input. If such a situation would occur in spite of these precautions, then please contact the local ABB representative for remedial action. 23.4 Denial of service SCHLCCH/RCHLCCH 23.4.1...
ProductDef • FirmwareVer • SerialNo • OrderingNo • ProductionDate • IEDProdType Figure 424: IED summary This information is very helpful when interacting with ABB product support (for example during repair and maintenance). Line distance protection REL670 2.2 IEC Application manual...
• IEDMainFunType • Main function type code according to IEC 60870-5-103. Example: 128 (meaning line protection). • SerialNo • OrderingNo • ProductionDate 24.3 Measured value expander block RANGE_XP SEMOD52451-1 v2 Line distance protection REL670 2.2 IEC Application manual...
Six different groups of setting parameters are available in the IED. Any of them can be activated through the different programmable binary inputs by means of external or internal control signals. Line distance protection REL670 2.2 IEC Application manual...
24.5.3 Setting guidelines M15292-3 v2 Set the system rated frequency. Refer to section "Signal matrix for analog inputs SMAI" for description on frequency tracking. 24.6 Summation block 3 phase 3PHSUM SEMOD55968-1 v2 Line distance protection REL670 2.2 IEC Application manual...
Global base values GBASVAL 24.7.2 Application GUID-D58ECA9A-9771-443D-BF84-8EF582A346BF v4 Global base values function (GBASVAL) is used to provide global values, common for all applicable functions within the IED. One set of global values Line distance protection REL670 2.2 IEC Application manual...
These names will define SMBI function in the Signal Matrix tool. The user defined name for the input or output signal will also appear on the respective output or input signal. 24.9 Signal matrix for binary outputs SMBO SEMOD55215-1 v2 Line distance protection REL670 2.2 IEC Application manual...
RMS value, harmonics, sequence components and so on. This information is then used by the respective functions connected to this SMAI block in ACT (for example protection, measurement or monitoring functions). Line distance protection REL670 2.2 IEC Application manual...
SMAI inputs, the positive sequence voltage will be zero and the frequency functions will not work properly. The outputs from the above configured SMAI block shall only be used for Overfrequency protection (SAPTOF), Underfrequency protection (SAPTUF) and Rate-of-change frequency protection Line distance protection REL670 2.2 IEC Application manual...
GlobalBaseSel: Selects the global base value group used by the function to define (IBase), (UBase) and (SBase). MinValFreqMeas: The minimum value of the voltage for which the frequency is calculated, expressed as percent of UBase (for each instance n). Line distance protection REL670 2.2 IEC Application manual...
Page 870
When two or more preprocessing blocks are used to feed one protection function (e.g. over-power function GOPPDOP), it is of outmost importance that parameter setting DFTReference has the same set value for all of the preprocessing blocks involved Line distance protection REL670 2.2 IEC Application manual...
Page 871
In other application the usual setting of the parameter DFTReference of SMAI is InternalDFTRef. Example 1 Line distance protection REL670 2.2 IEC Application manual...
Page 872
SMAI1:13 – SMAI12:24: DFTReference = ExternalDFTRef to use DFTSPFC input of SMAI1:13 as reference (SMAI7:7) For task time group 3 this gives the following settings: SMAI1:25 – SMAI12:36: DFTReference = ExternalDFTRef to use DFTSPFC input as reference (SMAI7:7) Example 2 Line distance protection REL670 2.2 IEC Application manual...
Page 873
(see Figure 428) SMAI2:14 – SMAI12:24: DFTReference = DFTRefGrp4 to use SMAI4:16 as reference. For task time group 3 this gives the following settings: SMAI1:25 – SMAI12:36: DFTReference = ExternalDFTRef to use DFTSPFC input as reference (SMAI4:16) Line distance protection REL670 2.2 IEC Application manual...
The supported values of the function block TESTMODE are described in Communication protocol manual, IEC 61850 Edition 2. When the function block TESTMODE is in test mode the Start LED on the LHMI is turned on with steady light. Line distance protection REL670 2.2 IEC Application manual...
Page 875
The block status of a component is shown on the LHMI as the Blk output under the same path as for Beh:Main menu/Test/Function status/Function group/Function block descriptive name/LN name/Outputs. If the Blk output is not shown, the component cannot be blocked. Line distance protection REL670 2.2 IEC Application manual...
IED and all connected merging units. The time synchronization from the clock to the IED can be PTP, optical PPS or IRIG-B. For IEDs using IEC/UCA 61850-9-2LE from one single MU as analog Line distance protection REL670 2.2 IEC Application manual...
All the parameters related to time are divided into two categories: System time and Synchronization. 24.13.2.1 System time M11348-119 v6 The time is set with years, month, day, hour, minute, second and millisecond. Line distance protection REL670 2.2 IEC Application manual...
The time synchronization fine tunes the clock (seconds and milliseconds). The parameter SyncMaster defines if the IED is a master, or not a master for time synchronization within a Substation Automation System, for IEDs connected in a Line distance protection REL670 2.2 IEC Application manual...
Page 879
The PTP VLAN tag does not need to be the same on all access points in one IED. It is possible to mix as long as they are the same for all devices on each subnet. Line distance protection REL670 2.2 IEC Application manual...
If the merging unit supports PTP, use PTP. If PTP is used in the IED and the merging unit is not PTP capable, then synchronize the merging unit from the IED Line distance protection REL670 2.2 IEC Application manual...
If the PPS output from the GTM module is used to synchronize the merging unit and PTP is not used, the IED does not know how the merging unit is synchronized and the parameter LostSyncMode must be set to NoBlock. Line distance protection REL670 2.2 IEC Application manual...
). As the present CT standards have no limitation of the level of remanent flux, these CTs are also classified as for example, class TPX, P and PX according to IEC. The IEC TR 61869-100, Edition Line distance protection REL670 2.2 IEC Application manual...
Page 884
So far remanence factors of maximum 80% have been considered when CT requirements have been decided for ABB IEDs. Even in the future this level of remanent flux probably will be the maximum level that will be considered when decided the CT requirements.
VHR type CTs (i.e. with new material) to be used together with ABB protection IEDs. However, this may result in unacceptably big CT cores, which can be difficult to manufacture and fit in available space.
Even in a case where the phase- to-earth fault current is smaller than the three-phase fault current the phase-to-earth fault can be dimensioning for the CT depending on the higher burden. Line distance protection REL670 2.2 IEC Application manual...
CT (TPZ) is not well defined as far as the phase angle error is concerned. If no explicit recommendation is given for a specific function we therefore recommend contacting ABB to confirm that the non remanence type can be used.
E below: alreq æ ö × ³ × × k max sr ç ÷ alreq è ø (Equation 539) EQUATION1080 V2 EN-US Line distance protection REL670 2.2 IEC Application manual...
Page 889
= 3 for primary time constant Tp > 100 and £ 400 ms k = 4 for primary time constant Tp £ 40 ms k = 5 for primary time constant Tp > 40 and £ 150 ms Line distance protection REL670 2.2 IEC Application manual...
The value of the E is approximately equal to the corresponding E . Therefore, the CTs according to class P and PR must have a secondary limiting e.m.f. E that fulfills the following: Line distance protection REL670 2.2 IEC Application manual...
The CTs according to class C must have a calculated rated equivalent limiting secondary e.m.f. E that fulfils the following: alANSI > maximum of E alANSI alreq (Equation 545) EQUATION1384 V2 EN-US Line distance protection REL670 2.2 IEC Application manual...
SNTP server software. The SNTP server should be stable, that is, either synchronized from a stable source like GPS, or local without synchronization. Using a local SNTP server without synchronization as primary or secondary server in a redundant configuration is not recommended. Line distance protection REL670 2.2 IEC Application manual...
Jitter and Wander according to ITU-T G.823 and G.825 • Buffer memory <250 μs, <100 μs asymmetric difference • Format.G 704 frame, structured etc.Format. • No CRC-check Synchronization in PDH systems connected to SDH systems Line distance protection REL670 2.2 IEC Application manual...
Thus, the accuracy of the current and voltage inputs to the merging unit and the inaccuracy added by the merging unit must be coordinated with the requirement for actual type of protection function. Line distance protection REL670 2.2 IEC Application manual...
Page 895
In principle the accuracy of the current and voltage transformers, together with the merging unit, shall have the same quality as direct input of currents and voltages. Line distance protection REL670 2.2 IEC Application manual...
Binary signal transfer function, receiver blocks Binary signal transfer function, transmit blocks C37.94 IEEE/ANSI protocol used when sending binary signals between IEDs Controller Area Network. ISO standard (ISO 11898) for serial communication Circuit breaker Combined backplane module Line distance protection REL670 2.2 IEC Application manual...
Page 898
DARPA Defense Advanced Research Projects Agency (The US developer of the TCP/IP protocol etc.) DBDL Dead bus dead line DBLL Dead bus live line Direct current Data flow control Discrete Fourier transform Line distance protection REL670 2.2 IEC Application manual...
Page 899
Function type G.703 Electrical and functional description for digital lines used by local telephone companies. Can be transported over balanced and unbalanced lines Communication interface module with carrier of GPS receiver module Line distance protection REL670 2.2 IEC Application manual...
Page 900
PCI specifications from the PCI SIG (Special Interest Group) for the electrical EMF (Electromotive force). IEEE 1686 Standard for Substation Intelligent Electronic Devices (IEDs) Cyber Security Capabilities Intelligent electronic device Line distance protection REL670 2.2 IEC Application manual...
Page 901
Liquid crystal display LDCM Line data communication module Local detection device Light-emitting diode LON network tool Local operating network Miniature circuit breaker Mezzanine carrier module Milli-ampere module Main processing module MVAL Value of measurement Line distance protection REL670 2.2 IEC Application manual...
Page 902
Parallel redundancy protocol Power supply module Parameter setting tool within PCM600 Precision time protocol PT ratio Potential transformer or voltage transformer ratio PUTT Permissive underreach transfer trip RASC Synchrocheck relay, COMBIFLEX Relay characteristic angle Line distance protection REL670 2.2 IEC Application manual...
Page 903
Strömberg Protection Acquisition (SPA), a serial master/ slave protocol for point-to-point and ring communication. Switch for CB ready condition Switch or push button to trip Starpoint Neutral point of transformer or generator Line distance protection REL670 2.2 IEC Application manual...
Page 904
"leap seconds" to synchronize it with Universal Time 1 (UT1), thus allowing for the eccentricity of the Earth's orbit, the rotational axis tilt (23.5 degrees), but still showing the Line distance protection REL670 2.2 IEC Application manual...
Page 905
Three times zero-sequence current.Often referred to as the residual or the earth-fault current Three times the zero sequence voltage. Often referred to as the residual voltage or the neutral point voltage Line distance protection REL670 2.2 IEC Application manual...
Need help?
Do you have a question about the REL670 2.2 IEC and is the answer not in the manual?
Questions and answers