Electronic thermal protection (ETR) is used in combination with a VZH Danfoss compressor.
ETR calculates motor temperature by measuring current, frequency, and operating time. The drive shows the thermal load on the
motor in percentage and can issue a warning at a programmable overload setpoint. Programmable options at the overload allow
the drive to stop the motor, reduce output, or ignore the condition. Even at low speeds, the drive meets I2t Class 20 electronic
motor overload standards.
t [s]
2000
1000
600
500
400
300
200
100
60
50
40
30
20
10
1.0
1.2
1.4
Illustration 8: ETR Characteristics
The X-axis shows the ratio between I
the drive. The curves show the characteristic nominal speed at twice the nominal speed and at 0.2 x the nominal speed. At lower
speed, the ETR cuts off at lower heat due to less cooling of the motor. In that way, the motor is protected from being overheated
even at low speed. The ETR feature calculates the motor temperature based on actual current and speed. The calculated tempera-
ture is visible as a readout parameter in parameter 16-18 Motor Thermal.

3.2.2.3 Built-in PID Controller

The built-in proportional, integral, derivative (PID) controller eliminates the need for auxiliary control devices. The PID controller
maintains constant control of closed-loop systems where regulated pressure, flow, temperature, or other system requirements must
be maintained.
The drive can use 2 feedback signals from 2 different devices, allowing the system to be regulated with different feedback require-
ments. The drive makes control decisions by comparing the 2 signals to optimize system performance.

3.2.2.4 Automatic Restart

The drive can be programmed to restart the motor automatically after a minor trip, such as momentary power loss or fluctuation.
This feature eliminates the need for manual resetting and enhances automated operation for remotely controlled systems. The
number of restart attempts and the duration between attempts can be limited.

3.2.2.5 Flying Start

Flying start allows the drive to synchronize with an operating motor rotating at up to full speed in either direction. This prevents
trips due to overcurrent draw. It minimizes mechanical stress to the system since the motor receives no abrupt change in speed
when the drive starts.

3.2.2.6 Frequency Bypass

In some applications, the system can have operational speeds that create a mechanical resonance. This mechanical resonance can
generate excessive noise and possibly damage mechanical components in the system. The drive has 4 programmable bypass-fre-
quency bandwidths (parameters 4-60 to 4-63). The bandwidths allow the motor to step over speeds that induce system resonance.

3.2.2.7 Motor Preheat

Instead of using a space heater, Danfoss provides motor preheat functionality. To preheat a motor in a cold or damp environment, a
small amount of DC current can be trickled continuously into the motor to protect it from condensation and cold starts.
Danfoss A/S © 2021.05
N O T I C E
f
= 2 x f
OUT
f
= 1 x f
OUT
f
= 0.2 x f
OUT
I
M
I
(parameter 1-24)
1.6
1.8
2.0
M,N
and I
nominal. The Y-axis shows the time in seconds before the ETR cuts off and trips
motor
motor
(parameter 1-23)
M,N
M,N
M,N
Product Overview
AJ330233902305en-000201 / 130R0596 | 17