Parameter Descriptions
34-70 MCO Alarm Word 1
Range:
0
[0 - 4294967295 ]
*
34-71 MCO Alarm Word 2
Range:
0
[0 - 4294967295 ]
*

3.27 Parameters: 35-** Sensor Input Option

Parameters for configuring the functionality of VLT
Input MCB 114.
3.27.1 35-0* Temp. Input Mode (MCB 114)
35-00 Term. X48/4 Temperature Unit
Select the unit to be used with temperature input X48/4 settings
and readouts:
Option:
[60]
°C
*
[160]
°F
35-01 Term. X48/4 Input Type
View the temperature sensor type detected at input X48/4:
Option:
[0]
Not Connected
*
[1]
PT100 2-wire
[3]
PT1000 2-wire
[5]
PT100 3-wire
[7]
PT1000 3-wire
35-02 Term. X48/7 Temperature Unit
Select the unit to be used with temperature input X48/7 settings
and readouts:
Option:
[60]
°C
*
[160]
°F
35-03 Term. X48/7 Input Type
View the temperature sensor type detected at input X48/7:
Option:
[0]
Not Connected
*
[1]
PT100 2-wire
[3]
PT1000 2-wire
[5]
PT100 3-wire
[7]
PT1000 3-wire
35-04 Term. X48/10 Temperature Unit
Select the unit to be used with temperature input X48/10
settings and readouts:
Option:
[60]
°C
*
[160]
°F
MG33MP02
Programming Guide
35-05 Term. X48/10 Input Type
Function:
View the temperature sensor type detected at input X48/10:
Option:
[0]
[1]
Function:
[3]
[5]
[7]
35-06 Temperature Sensor Alarm Function
®
Sensor
Select the alarm function:
Option:
[0]
[2]
[5]
[27]
3.27.2 35-1* Temp. Input X48/4 (MCB 114)
Function:
35-14 Term. X48/4 Filter Time Constant
Range:
0.001 s
Function:
35-15 Term. X48/4 Temp. Monitor
This parameter facilitates the possibility of enabling or disabling
the temperature monitor for terminal X48/4. Set the temperature
limits in parameter 35-16 Term. X48/4 Low Temp. Limit and
parameter 35-17 Term. X48/4 High Temp. Limit.
Function:
Option:
[0]
[1]
35-16 Term. X48/4 Low Temp. Limit
Range:
Function:
Size related
35-17 Term. X48/4 High Temp. Limit
Range:
Size related
Function:
Danfoss A/S © 10/2018 All rights reserved.
Not Connected
*
PT100 2-wire
PT1000 2-wire
PT100 3-wire
PT1000 3-wire
Off
Stop
Stop and trip
*
Forced stop and trip
Function:
[0.001 - 10
Enter the filter time constant. This is a
*
s]
first-order digital low-pass filter time
constant for suppressing electrical noise
in terminal X48/4. A high time constant
value improves dampening but also
increases the time delay through the
filter.
Disabled
*
Enabled
Function:
[ -50 - par.
Enter the minimum temperature
*
35-17 ]
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/4.
Function:
[ par. 35-16 -
Enter the maximum temperature
*
204 ]
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/4.
Function:
3
Function:
Function:
245