Parameter Descriptions

3.21 Parameters: 35-** Sensor Input Option

3.21.1 35-0* Temp. Input Mode (MCB 114)
35-00 Term. X48/4 Temperature Unit
3
3
Select the unit to be used with temperature input X48/4 settings
and readouts:
Option:
[60]
*
[160]
35-01 Term. X48/4 Input Type
View the temperature sensor type detected at input X48/4:
Option:
[0]
*
[1]
[3]
[5]
[7]
35-02 Term. X48/7 Temperature Unit
Select the unit to be used with temperature input X48/7 settings
and readouts:
Option:
[60]
*
[160]
35-03 Term. X48/7 Input Type
View the temperature sensor type detected at input X48/7:
Option:
[0]
*
[1]
[3]
[5]
[7]
35-04 Term. X48/10 Temperature Unit
Select the unit to be used with temperature input X48/10
settings and readouts:
Option:
[60]
*
[160]
35-05 Term. X48/10 Input Type
View the temperature sensor type detected at input X48/10:
Option:
[0]
*
[1]
[3]
[5]
[7]
172
VLT
Function:
°C
°F
Function:
Not Connected
PT100 2-wire
PT1000 2-wire
PT100 3-wire
PT1000 3-wire
Function:
°C
°F
Function:
Not Connected
PT100 2-wire
PT1000 2-wire
PT100 3-wire
PT1000 3-wire
Function:
°C
°F
Function:
Not Connected
PT100 2-wire
PT1000 2-wire
PT100 3-wire
PT1000 3-wire
Danfoss A/S © Rev. 10/2014 All rights reserved.
®
AutomationDrive FC 301/302
35-06 Temperature Sensor Alarm Function
Select the alarm function:
Option:
[0]
[2]
[5]
*
3.21.2 35-1* Temp. Input X48/4 (MCB 114)
35-14 Term. X48/4 Filter Time Constant
Range:
0.001 s
[0.001 - 10
*
s]
35-15 Term. X48/4 Temp. Monitor
This parameter facilitates the possibility of enabling or disabling
the temperature monitor for terminal X48/4. The temperature
limits can be set in parameter 35-16 Term. X48/4 Low Temp. Limit
and parameter 35-17 Term. X48/4 High Temp. Limit.
Option:
[0]
*
[1]
35-16 Term. X48/4 Low Temp. Limit
Range:
Size related
*
35-17 Term. X48/4 High Temp. Limit
Range:
Size related
*
3.21.3 35-2* Temp. Input X48/7 (MCB 114)
35-24 Term. X48/7 Filter Time Constant
Range:
0.001 s
[0.001 - 10
*
s]
Function:
Off
Stop
Stop and trip
Function:
Enter the filter time constant. This is a
first-order digital low-pass filter time
constant for suppressing electrical noise
in terminal X48/4. A high time constant
value improves dampening but also
increases the time delay through the
filter.
Function:
Disabled
Enabled
Function:
[ -50 - par.
Enter the minimum temperature
35-17]
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/4.
Function:
[ par. 35-16 -
Enter the maximum temperature
204]
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/4.
Function:
Enter the filter time constant. This is a
first-order digital low-pass filter time
constant for suppressing electrical noise
in terminal X48/7. A high time constant
value improves dampening but also
MG33MJ02