Section 4 Requirements For Measurement Transformers; Current Transformers; Current Transformer Requirements For Non-Directional Overcurrent Protection; Current Transformer Accuracy Class And Accuracy Limit Factor - ABB Relion 615 series Applications Manual

Motor protection and control
Hide thumbs Also See for Relion 615 series:
Table of Contents

Advertisement

1MRS756885 A
Section 4
4.1
4.1.1
4.1.1.1
REM615
Application Manual
Requirements for measurement transformers
Requirements for measurement
transformers

Current transformers

Current transformer requirements for non-directional
overcurrent protection
For reliable and correct operation of the overcurrent protection, the CT has to be
chosen carefully. The distortion of the secondary current of a saturated CT may
endanger the operation, selectivity, and co-ordination of protection. However,
when the CT is correctly selected, a fast and reliable short circuit protection can be
enabled.
The selection of a CT depends not only on the CT specifications but also on the
network fault current magnitude, desired protection objectives, and the actual CT
burden. The protection relay settings should be defined in accordance with the CT
performance as well as other factors.

Current transformer accuracy class and accuracy limit factor

The rated accuracy limit factor (F
current to the rated primary current. For example, a protective current transformer
of type 5P10 has the accuracy class 5P and the accuracy limit factor 10. For
protective current transformers, the accuracy class is designed by the highest
permissible percentage composite error at the rated accuracy limit primary current
prescribed for the accuracy class concerned, followed by the letter "P" (meaning
protection).
Table 14:
Limits of errors according to IEC 60044-1 for protective current transformers
Accuracy class
Current error at
rated primary
current (%)
5P
±1
10P
±3
The accuracy classes 5P and 10P are both suitable for non-directional overcurrent
protection. The 5P class provides a better accuracy. This should be noted also if
there are accuracy requirements for the metering functions (current metering,
power metering, and so on) of the relay.
) is the ratio of the rated accuracy limit primary
n
Phase displacement at rated primary
current
minutes
centiradians
±60
±1.8
-
-
Section 4
Composite error at
rated accuracy limit
primary current (%)
5
10
39