Connection Of The Power Regeneration Common Converter (Fr-Cv); Connection Of A Dc Reactor (Fr-Hel) - Mitsubishi Electric FR-E720-600 Instruction Manual

Hide thumbs Also See for FR-E720-600:
Table of Contents

Advertisement

2.4.4

Connection of the power regeneration common converter (FR-CV)

When connecting the power regeneration common converter (FR-CV), connect the inverter terminals (P/+, N/-) and power
regeneration common converter (FR-CV) terminals as shown below so that their symbols match with each other.
MC
MCCB
Three-phase
AC power supply
∗1
Always keep the power input terminals R/L1, S/L2, T/L3 open. Incorrect connection will damage the inverter.
∗2
Do not insert an MCCB between the terminals P/+-N/- (between P/L+-P/+, between N/L--N/-). Opposite polarity of terminals N/-, P/+ will
damage the inverter.
∗3
Always connect the power supply and terminals R/L11, S/L21, T/MC1.
Operating the inverter without connecting them will damage the power regeneration common converter.
NOTE
The voltage phases of terminals R/L11, S/L21, T/MC1 and terminals R2/L1, S2/L2, T2/L3 must be matched.
Use sink logic (factory setting) when the FR-CV is connected. The FR-CV cannot be connected when source logic is
selected.
Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.
2.4.5

Connection of a DC reactor (FR-HEL)

When using the DC reactor (FR-HEL), connect it across terminals P/+-P1.
In this case, the jumper connected across terminals P/+-P1 must be removed. Otherwise, the reactor will not exhibit its
performance.
NOTE
The wiring distance should be within 5m (16.4feet).
The size of the cables used should be equal to or larger than that of the power supply cables (R/L1, S/L2, T/L3). (Refer
to page 17)
Dedicated stand-alone
reactor (FR-CVL)
1
R/L
R2/L
11
12
S/L
S2/L
21
22
T/L
T2/L
31
32
Remove the jumper.
Connection of stand-alone option unit
FR-CV type power
regeneration common converter
R2/L
1
S2/L
P/L+
2
T2/L
3
N/L-
P24
R/L
11
SD
S/L
21
*3
RDYA
T/MC1
RDYB
RSO
SE
P1
P/+
FR-HEL
R/L1
U
S/L2
*1
IM
V
T/L3
W
Inverter
P/+
*2
N/-
PC
SD
MRS
RES
SD
33