Modbus®-Rtu Communication - Mitsubishi Electric FR-E700 Instruction Manual

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Parameter
6.19.5
Modbus®-RTU communication
(Pr. 117, Pr. 118, Pr. 120, Pr. 122, Pr. 343, Pr. 549)
Using the Modbus® RTU communication protocol, communication operation or parameter setting
can be performed from the PU connector of the inverter.
Pr. No.
Name
PU communication
117
station number
PU communication
118
speed
PU communication
120
parity check
PU communication
122
check time interval
Communication error
343
count
Stop mode selection at
502
communication error
549
Protocol selection
The above parameter can be set when Pr. 160 "User group read selection" = 0.
When Modbus®-RTU communication is performed from the master with address 0 (station num-
ber 0) set, broadcast communication is selected and the inverter does not send a response mes-
sage. When response from the inverter is necessary, set a value other than "0" (initial value is 0)
in Pr. 117 "PU communication station number". Some functions are invalid for broadcast com-
munication. (Refer to page 6-268.)
NOTES
When "1" (Modbus®-RTU protocol) is set in Pr. 549 and "384" (38400 bps) in Pr. 118, parameter unit
(FR-PU04/FR-PU07) is disabled. When using the parameter unit (FR-PU04/FR-PU07), change parame-
ter using the operation panel.
When using the Modbus®-RTU protocol, set Pr. 549 "Protocol selection" to "1".
When PU connector is selected as NET mode operation source (when Pr. 550 "NET mode operation
command source selection" = 2 or 9999 (initial value) without communication option), Modbus®
RTU communication operation can be performed. (Refer to section 6.19.2).
FR-E700 SC EC/ENE
Initial
Setting
Description
Value
Range
0
No reply to the master
0
Inverter station number specification
1–247
Set the inverter station numbers when two or more inverters are connected
to one personal computer.
Communication speed
48/96/
96
The setting value × 100 equals the communication speed.
192/384
(Example: 9600bps if 96)
Without parity check
0
Stop bit length 2bit
With odd parity check
2
1
Stop bit length 1bit
With even parity check
2
Stop bit length 1bit
RS-485 communication can be made. Note that a communication fault
0
(E.PUE) occurs as soon as the inverter is switched to the operation mode
with command source.
0.1
Communication check (signal loss detection) time interval
0
If a no-communication state persists for longer than the permissible time,
999.8 s
the inverter will come to trip (depends on Pr. 502).
9999
No communication check (signal loss detection)
Displays the number of communication errors during Modbus®-RTU
0
communication (reading only)
At Fault
Occurrence
0/3
Coasts to stop
0
Decelerates to
1
stop
Decelerates to
2
stop
0
Mitsubishi inverter (computer link) protocol
0
1
Modbus®-RTU protocol
Communication operation and setting
At Fault
Indication
Fault Output
Removal
Stop
E.PUE
Output
(E.PUE)
Output after
Stop
After stop E.PUE
stop
(E.PUE)
Automatic
After stop E.PUE Without output
restart
functions
Refer to
Parameters referred to
Section
6 - 265