Trace function

• The operating status of the inverter can be traced and temporarily stored in the RAM in the inverter. The data stored in the
RAM is deleted when the power supply is turned OFF. (The data is retained at inverter reset.)
• Stored data can be monitored by FR Configurator2, and the status of the inverter can be analyzed.
Pr.
1020
Trace operation selection
A900
1022
Sampling cycle
A902
1023
Number of analog channels
A903
1024
Sampling auto start
A904
1025
Trigger mode selection
A905
1026
Number of sampling before
A906
trigger
1027
Analog source selection (1ch) 201
A910
1028
Analog source selection (2ch) 202
A911
1029
Analog source selection (3ch) 203
A912
1030
Analog source selection (4ch) 204
A913
1031
Analog source selection (5ch) 205
A914
1032
Analog source selection (6ch) 206
A915
1033
Analog source selection (7ch) 207
A916
1034
Analog source selection (8ch) 208
A917
1035
Analog trigger channel
A918
1036
Analog trigger operation
A919
selection
1037
Analog trigger level
A920
366
14. (A) Application Parameters
14.12 Trace function
Name
Initial value
0
1
4
0
0
90%
1
0
1000
Setting range
0
Without trace operation
1
Sampling start
2
Forced trigger
3
Sampling stop
Set the sampling cycle.
1, 2, 5, 10, 50,
1: 1 ms, 2: 2 ms, 5: 5 ms, 10: 10 ms, 50: 50 ms, 100: 100 ms,
100, 500, 1000
500: 500 ms, 1000: 1 s
1 to 8
Select the number of analog channels for sampling.
0
Manual sampling start
Sampling starts automatically when the power supply is turned
1
ON or at a reset
0
Fault trigger
1
Analog trigger
2
Digital trigger
3
Analog or digital trigger (OR logic)
4
Both analog and digital triggers (AND logic)
Set the percentage of the pre-trigger sampling time with
0% to 100%
respect to the overall sampling time.
1 to 3, 5 to 12, 14,
17, 18, 20, 23,
24, 32, 33, 40 to
42, 52 to 54, 61,
Select the analog data (monitor item) for sampling on each
62, 67, 83, 91,
channel.
97, 201 to 210,
212, 213, 230 to
*1
232, 235 to 238
1 to 8
Select the analog channel to be the trigger.
Sampling starts when the value of the analog monitor exceeds
0
the value set at the trigger level (Pr.1037)
Sampling starts when the value of the analog monitor falls
1
below the value set at the trigger level (Pr.1037)
Set the level at which the analog trigger turns ON.
600 to 1400
The trigger level is the value obtained by subtracting 1000 from
the set value.