Actual operation hour meter clear (Pr. 171)

4.2.42 Actual operation hour meter clear (Pr. 171)
Pr. 171 "actual operation hour meter
clear"
You can clear the actual operation hour of the monitoring function.
Parameter
Factory
Number
Setting
171
0
<Setting>
Write "0" in the parameter to clear the actual operation hour.
Pr. 173 to Pr. 176

4.2.43 Input terminal function selection (Pr. 180 to Pr. 183)

Input terminal function selection (Pr. 180 to Pr. 183)
Pr. 180 "RL terminal function selection"
Pr. 181 "RM terminal function selection"
Pr. 182 "RH terminal function selection"
Pr. 183 "MRS terminal function selection"
Use these parameters to select/change the input terminal functions.
Parameter
Terminal
Number
Symbol
180
RL
181
RM
182
RH
183
MRS
Setting
Range
0
Refer to Pr. 160.
Factory
Setting
Low-speed operation
0
command (RL)
Middle-speed operation
1
command (RM)
High-speed operation
2
command (RH)
6
Output shut-off (MRS)
142
PARAMETERS
Related parameter
Pr. 52 "Control panel/PU main
display data selection"
Factory-Set Terminal
Function
Setting
Range
0 to 8, 16, 18
4
0 to 8, 16, 18
0 to 8, 16, 18
0 to 8, 16, 18