4.2.50 Watt-hour meter clear/actual operation hour meter clear
(Pr. 170, Pr. 171)
Pr. 170 "watt-hour meter clear"
Pr. 171 "actual operation hour meter clear"
You can clear the watt-hour value and actual operation hour monitoring function.
Parameter Number
Factory Setting
170
171
<Setting>
Write "0" in the parameters to clear the watt-hour value and actual operation hour.
REMARKS
The watt-hour value is monitored at the Pr. 52 setting of "25", and the actual operation hour at the Pr. 52
setting of "23".
Pr. 173 to Pr. 176

4.2.51 Input terminal function selection (Pr. 180 to Pr. 186)

Pr. 180 "RL terminal function selection"
Pr. 181 "RM terminal function selection"
Pr. 182 "RH terminal function selection"
Pr. 183 "RT terminal function selection"
Pr. 184 "AU terminal function selection"
Pr. 185 "JOG terminal function selection"
Pr. 186 "CS terminal function selection"
Use these parameters to select/change the input terminal functions.
Parameter
Terminal
Number
Symbol
180
RL
181
RM
182
RH
183
RT
184
AU
185
JOG
186
CS
Setting Range
0
0
0
0
Refer to Pr. 160.
Factory Setting
Factory-Set Terminal Function
0
Low-speed operation command (RL)
1
Middle-speed operation command (RM)
2
High-speed operation command (RH)
3
Second function selection (RT)
4
Current input selection (AU)
5
Jog operation selection (JOG)
Automatic restart after instantaneous
6
power failure selection (CS)
159
Get other manuals https://www.bkmanuals.com
PARAMETERS
R elated param eters
P r. 52 "D U /P U m ain display data
selection"
Setting Range
0 to 99, 9999
0 to 99, 9999
0 to 99, 9999
0 to 99, 9999
0 to 99, 9999
0 to 99, 9999
0 to 99, 9999
4