4.10.3 Condition selection of function validity by second function selection signal (RT)

You can select the second function using the RT signal.
 When the RT signal turns ON, the second function becomes valid.
 For the RT signal, set "3" in any of Pr. 178 to Pr. 182 (input terminal function selection) to assign the function.
 The second function has the following applications.
(a) Switching between normal use and emergency use
(b) Switching between heavy load and light load
(c) Changing of acceleration/deceleration time by broken line acceleration/deceleration
(d) Switching of characteristic between the main motor and sub motor
Second function connection diagram
Start
Second function
selection
High speed
Middle speed
 When the RT signal is ON, the following second functions are selected at the same time.
Function
Torque boost
Base frequency
Acceleration time
Deceleration time
Electronic thermal O/L relay
Stall prevention
Applied motor
NOTE
Changing the terminal assignment using Pr. 178 to Pr. 182 (input terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 178 to Pr. 182 (input terminal function selection)
Function assignment of external terminal and control
Inverter
STF/STR
RT
RH
RM
SD
First Function
Second Function
Parameter Number
Parameter Number
Pr. 0
Pr. 3
Pr. 7
Pr. 8
Pr. 9
Pr. 22
Pr. 71
Refer to page 116.
Second acceleration/deceleration time
RT
RH
RM
Refer to
Page
Pr. 46
77
Pr. 47
88
Pr. 44
99
Pr. 44, Pr. 45
99
Pr. 51
103
Pr. 48
82
Pr. 450
106
Acceleration time
is reflected
Time
119
4